H3C S10500 Switch Series

Installation Quick Start

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
New H3C Technologies Co., Ltd.  
http://www.h3c.com.hk 
 
Document version: 6PW103-20170430

 

 

Summary of Contents for S10506

Page 1: ...H3C S10500 Switch Series Installation Quick Start New H3C Technologies Co Ltd http www h3c com hk Document version 6PW103 20170430...

Page 2: ...her trademarks that may be mentioned in this manual are the property of their respective owners Notice The information in this document is subject to change without notice Every effort has been made i...

Page 3: ...nstalling the switch 4 Attaching the slide rails to the rack 4 Installing cage nuts 5 Installing the switch in the rack 7 Grounding the switch 7 Installing FRUs 8 Installing a power module 10 Connecti...

Page 4: ...H3C S10500 Switch Series Installation Guide The installation procedure is similar for all S10500 switch models This installation quick start uses the S10508 V switch as an example NOTE The figures in...

Page 5: ...0 mm 17 32 in 660 mm 25 98 in S10508 620 mm 24 41 in 14 RU 440 mm 17 32 in 660 mm 25 98 in S10508 V 886 mm 34 88 in 20 RU 440 mm 17 32 in 660 mm 25 98 in S10510 620 mm 24 41 in 14 RU 440 mm 17 32 in 6...

Page 6: ...e or bodily injury caused by improper use read the following safety recommendations before installation Note that the recommendations do not cover every possible hazardous condition To prevent ESD dam...

Page 7: ...rails Sign Meaning Remarks F L Front end of the left slide rail Mount this end to the front left rack post F R Front end of the right slide rail Mount this end to the front right rack post 2 Mark the...

Page 8: ...rail horizontal and adjust its length until the installation holes on the rear end of the slide rail touch the cage nuts on the rear rack post Then use screws to attach the slide rail to the rear rack...

Page 9: ...S10510 switches you can use the cage nut installation template to determine the cage nut installation holes on the rack posts For more information about the cage nut installation template see H3C S10...

Page 10: ...r vents of chassis to carry the chassis Any attempt to carry the switch with these parts might cause equipment damage or even bodily injury After placing the switch on the slide rails do not leave go...

Page 11: ...8 Figure 10 Grounding the switch Installing FRUs Installing a card CAUTION Before installing a card in the chassis make sure the connectors on the card are not broken or blocked...

Page 12: ...9 Figure 11 Installing a card Installing a subcard CAUTION Before installing a subcard in the chassis make sure the connectors on the subcard are not broken or blocked...

Page 13: ...efore installation Do not install power modules of different models on the same switch To avoid power module damage move the power module by supporting its bottom instead of holding its handle After y...

Page 14: ...1 Figure 13 Installing a power module Connecting power cords Connecting an AC power cord CAUTION Before you connect an AC power cord make sure the circuit breaker for the power cord is switched off 1...

Page 15: ...re the circuit breakers for both the positive and negative lines are switched off Figure 15 Connecting a DC power cord Accessing the switch for the first time Connecting the console cable The first ti...

Page 16: ...USB A connector of the console cable to the USB port on the terminal 2 Connect the mini USB A B connector of the console cable to the USB console port on the switch Figure 16 Connecting the console po...

Page 17: ...en the switching is operating correctly Card LED Status MPU LSU1SUPB0 LINK Steady on ACT Flashing or off OK Steady on FAIL Off RUN Flashing ALM Flashing or off LSUM1MPU06B0 LSUM1MPU10C0 LINK ACT Flash...

Page 18: ...I O S A Accessing the switch for the first time 12 C Chassis views and technical specifications 1 E Examining the installation site 4 I Installing the switch 4 O Obtaining documentation 14 S Safety re...