background image

 

GSM SMS Alarm Messenger 

Premium Edition 

 

 

SMS Basic 

SMS GSM alarm device [Basic] 

SMS Pro 

SMS GSM alarm device [Advanced] 

SMS Pro-X 

SMS GSM alarm & data capturing device [Professional] 

SMS Pro-S 

SMS GSM alarm device   

 [Temperature 

Sensor] 

SMS Pro-SX 

SMS GSM alarm device   

 [External 

Temperature & Humidity Sensor] 

SMS Pro-QX 

SMS GSM alarm & data capturing device [Quad Band] 

SMS Pro-QS 

SMS GSM alarm & data capturing device  

 

[Temperature  Quad Band] 

SMS Pro-QSX 

SMS GSM alarm & data capturing device  

 

[External Temperature & Humidity Quad Band] 

 

Features 

Basic 

Pro 

Pro-X 

Pro-QX 

Pro-S 

Pro-SX 

Alarm 

Input  8 8 8 8 8 8 

Relay 

Output  1 3 3 3 3 3 

Phone 

Number  6 6 6 6 6 6 

Low Voltage Alert 

9

 

9

 

9

 

9

 

9

 

9

 

Program by SMS 

9

 

9

 

9

 

9

 

9

 

9

 

Program by PC Software 

9

 

9

 

9

 

9

 

9

 

9

 

Voice 

9

 

9

 

9

 

9

 

9

 

9

 

AD 

Channels  -  - 2 2 1 0 

AD Hi/Lo Alert 

9

 

9

 

9

 

9

 

Temperature 

Sensor 

- - - - 1 1 

Humidity 

Sensor - - - - - 1 

Temp Hi/Lo Alert 

9

 

9

 

Humidity 

Hi/Lo 

Alert 

- - - - - 

9

 

GSM Band (MHz) 

900/1800  900/1800  900/1800  900/1800 

850/1900  900/1800 900/1800 

 

Version 6.6C

Summary of Contents for Pro-S

Page 1: ...pturing device Temperature Sensor Quad Band SMS Pro QSX SMS GSM alarm data capturing device External Temperature Humidity Sensor Quad Band Features Basic Pro Pro X Pro QX Pro S Pro SX Alarm Input 8 8 8 8 8 8 Relay Output 1 3 3 3 3 3 Phone Number 6 6 6 6 6 6 Low Voltage Alert 9 9 9 9 9 9 Program by SMS 9 9 9 9 9 9 Program by PC Software 9 9 9 9 9 9 Voice 9 9 9 9 9 9 AD Channels 2 2 1 0 AD Hi Lo Ale...

Page 2: ...N 5 3 INSERTING SIM CARD 6 4 TEMPERATURE SENSOR PRO S 7 5 EXTERNAL TEMPERATURE HUMIDITY SENSOR PRO SX 8 6 SCHEMATIC DIAGRAM 9 7 PC SETUP SOFTWARE 12 8 QUICK STARTUP 13 9 ALARM TRIGGER RESPONSE TIME 13 10 GSM NETWORK CONNECTIVITY 13 11 COMMAND LIST 14 12 DEAD LOOP PROBLEM 38 ...

Page 3: ...RS232 Arm Disarm by GSM mobile phone 8 x Alarm Inputs Opto isolated N C N O State Change O C triggered levels 2 x AD channels Threshold High Threshold Low Closed 3 x Relay Outputs NC NO Alarm or SMS activated 4 x Mobile Fixed Phone Number Alarm Alert Modes SMS Phone Dial or SMS Phone Dial System status reporting in Automatic Schedule or Alarm triggered modes Central Station monitoring number Sound...

Page 4: ... mm Operating Temperature 25 C 55 C Weight 600g RS232 9600bps 8 Data Bits None Parity 1 Stop Bit f Antenna Requirement GSM 900 GSM 1800 RF Frequency 925 960MHz 1805 1880MHz TX Frequency 880 912MHz 1710 1785MHz RF Rating 2W 12 5 Loop Loading 1W 12 5 Loop Loading Resistance 50Ohm Radiation S N 0dBi Note GSM850 900 1800 1900MHZ is available in US or worldwide version Pro Q g Operation ...

Page 5: ...nal Flashing Off On duration GSM Module Normal Operation Flashing Same On Off duration GSM Network Connection Problem Reason Antenna not connected No SIM Card Defective SIM Card GSM Module Defect LED2 red Operation Status On Normal Flash Searching GSM Network Connecting GSM Network Receiving SMS messages Sending SMS messages Phone dialing RS232 Pin Assignment Connecting to PC 9600bps 8bit No Parit...

Page 6: ...Alarm Messenger Pro X Premium 6 3 Inserting SIM card Press the yellow button to release the SIM card caddy as shown below Make sure that the golden contact is facing down when inserting the SIM card caddy n o p ...

Page 7: ...ensor LM35DZ Temperature Range 0 100 C Accuracy 0 1 C AD Channel 2 High Temperature SMS Alert Low Temperature SMS Alert B External Version An external temperature sensor is integrated inside the SMS alarm metal case detecting the surrounding temperature Temperature Sensor DS80B20 Temperature Range 50 125 C Accuracy 0 1 C AD Channel 2 High Temperature SMS Alert Low Temperature SMS Alert Internal te...

Page 8: ... lower if cable is longer External Temperature Sensor Temperature Range 50 125 C Accuracy 0 1 C AD Channel 2 High Temperature SMS Alert Low Temperature SMS Alert External Humidity Sensor Humidity Range 0 100 RH Accuracy 5 RH AD Channel 1 High Humidity SMS Alert Low Humidity SMS Alert NOTE Humidity Sensor must be installed upwards External Temperature Humidity sensor ...

Page 9: ...Close 2 3 Short Normal Open Default 6 Schematic Diagram The relay on off start up status is determined by the jumper setting The relay will resume its start up status when power is off POW Power Input DC7 12V GND Power Ground 5VDC Power Output DC5V power supply for voltage type sensor ...

Page 10: ...o isolated Inputs 1KΩ Input Resistance 24VDC resistor 1 2 2KΩ should be used in serial a IN1 IN3 IN4 IN5 IN6 IN7 IN8 Alarm Input DC12V 7 15mA GND Common Ground b IN2 IN2 IN2 DC7 12V IN2 Ground Relay Output OUT1 OUT2 OUT3 Max 1A 24VDC 1A 120VAC NC NO selected by jumper on board ...

Page 11: ...Analog Digital Channel 1 DC 7 15V Current 4 20mA AD2 Analog Digital Channel 1 DC 7 15V Current 4 20mA Models 1 Pro X AD1 2 are available 2 Pro S AD2 is used for temperature sensor AD1 is available 3 Pro SH AD2 is used for temperature sensor AD1 is used for humidity sensor ...

Page 12: ...and run SMSPro_Setup exe under Windows 1 Select the COM port of PC connecting to the device 2 Click Connect button to activate the connection between PC and SMS alarm unit 3 Select Number ID Click Init to reset or Ver to get the version of the device Please refer to the manual of SMSPro_Setup software A Programmed by SMS command via mobile B Programmed by PC Software via RS232 port n o p p ...

Page 13: ...Time After power on the unit will take about 30 seconds for GSM module initialization and accessing the GSM network Upon alarm triggered the unit will send the SMS alert message to Control Centre and then other 4 programmable phone numbers Control Centre can be disabled in order to make the users phone number receiving the alarm sooner 10 GSM Network Connectivity 1 When GSM network is inaccessible...

Page 14: ...L 25 13 RELAY OUTPUT DELAY TIME 25 14 OPERATING VOLTAGE LOW LEVEL ALARM SMS 25 15 INPUT VOLTAGE LOW LEVEL ALARM 26 16 INPUT VOLTAGE THRESHOLD LEVEL SETUP 26 17 ARM DISARM SETUP 27 Device Information Report 18 DEFAULT SETTING 27 19 SYSTEM PARAMETERS RESET 27 20 SYSTEM VERSION CHECK 27 21 RETURN MESSAGE 27 22 SYSTEM PARAMETERS REPORT 28 AD Channel Setup 23 AD PARAMETERS SETUP 30 24 AD CHANNEL ALARM ...

Page 15: ...222 Default Password 1234 New Password 2222 11 2 Manual Health Reporting Command PWD XXXX STATUS SMS Message received ST XXX T 2005 01 28 13 00 V XXXX AI1 0000 AI2 0000 K1 X K2 X K3 X K4 X K5 X K6 X K7 X K8 X OUT1 Y OUT2 Y OUT3 Y Example ST 002 2005 01 28 13 00 V 8 15 AI1 0000 AI2 0000 K1 1 K2 0 K3 0 K4 1 K5 1 K6 0 K7 0 K8 1 OUT1 1 OUT2 1 OUT3 1 ST Unit Serial Number XXX ASCII code T Unit Internal...

Page 16: ... CTRZ YYYYYYYYYYY MM XXXX Password Z Control Centre Number Max 2 centres 1 means the first centre number 2 means the second centre number YYYYYYYY Phone number in control centre MM Period Code of Automatic Scheduled Health Report Example PWD 1234 CTR1 123456789 05 Password 1234 Report Health Status every 1 hour refer Table 1 2 Periodic health status and any command from other mobile phone will be ...

Page 17: ... 8 K1 0 means Open K1 1 means Closed OUT1 Relay Output 1 OUT2 3 Relay Output 2 3 OUT1 0 means Open OUT1 1 means Closed Example SMS Message received ST 001 2005 01 27 12 00 V 8 14 AI1 2312 AI2 2131 K1 1 K2 0 K3 0 K4 1 O 1 SMS Unit Current Status ST Unit Serial Number 001 TIME Unit Internal Clock Date 27 Jan 2005 Time 12 00 V Operating Voltage 8 14VDC AI1 A D Channel 1 2132 AI2 A D Channel 2 X2131 K...

Page 18: ...2 ZZZZZZZZZZZ 3 ZZZZZZZZZZZ 4 ZZZZZZZZZZZ XXXX Password ZZZZZZZZZZZ Phone Number Example 1 PWD 1234 ALMNU1 12345678 2 36925814712 3 159357456 4 951753621 Password 1234 Upon Alarm is triggered call or SMS is made to following numbers Number 1 12345678 Number 2 36925814712 Number 3 159357456 Number 4 951753621 Example 2 PWD 1234 ALMNU1 NUL 3 NUL Password 1234 Upon first example setup call to followi...

Page 19: ...1 means alarm report to Control Centre 1 and 2 ZZZZ Selection of alarm phone dial and alarm SMS 0 means no alarm report 1 means SMS only 2 means phone dial only 3 means SMS first and then phone dial Z Z Z Z NNN Relay Output Control 0 means no relay output control 1 means relay output triggered by alarm N N N Note on PC Setup Software Alarm Default Level SMS Command Value X PC Setup Display 0 means...

Page 20: ... is closed alarm is triggered Control Centre 1 2 will be reported by SMS Phone Number 1 SMS alert Phone Number 2 alarm phone dial Phone Number 3 SMS alert then phone dial Phone Number 4 no report Relay Output 1 triggered CLOSE by alarm Relay Output 2 no control Relay Output 3 no control Example 3 How to make the Relay Output 3 triggered by alarm channels 2 5 Once set the relay output 3 will no lon...

Page 21: ... defined mobile phone numbers AD Channel 1 2 Command PWD XXXX ACHYTEXT XXXX Password Y AD Channel Number 0 2 0 Low Power Input Voltage Level Alarm 1 AD Channel 1 Alarm 2 AD Channel 2 Alarm SMS Message max 100 characters Example PWD 1234 ACH2TEXT High Temperature Alert Threshold High 4 250 AD value 5 123 Password 1234 Date 2007 06 12 Time 19 23 AD value captured is higher than threshold high so ale...

Page 22: ...ssage ST001 T 2008 01 22 15 45 This command is used to read the message content for verification AD Channel 0 2 Command PWD XXXX RDACHYTEXT XXXX Password Y AD Channel Number 0 2 0 Low Power Input Voltage Level Alarm 1 AD Channel 1 Alarm 2 AD Channel 2 Alarm Command PWD XXXX RDACH0TEXT Reply Message ST001 T 2008 01 22 15 45 V 12 3 Command PWD XXXX RDACH2TEXT Reply Message ST001 T 2008 01 22 15 45 I...

Page 23: ...nual input message content A AD Channel 1 B AD Channel 2 C AD Channel 0 low voltage alarm For example PWD 1234 SENDMS4 9 Good Morning SMS message Good Morning will be sent to the phone number 4 Error message about setting A Number Choice Miss A is not within 1 4 Number Non Exist No phone number is preset in that location Error message about setting B Did not specify SMS contents B is not 0 9 A B o...

Page 24: ... SMSPro_Setup Software SMS Alarm Messenger can be used as a GSM Modem sending SMS message to a user alarm mobile phone number Please select the following o Select alarm phone number o Type the message on SENDTEXT fill in Manual Input box o Click button ...

Page 25: ...d to reset the relay output after the alarm is triggered 11 13 Relay Output Delay Time Command PWD XXXX OUTNDLAY YYYY XXXX Password N Relay Output Channel 1 3 YYYYY 0000 9999 seconds 0000 Turn On or Off the output default 0005 Turn On the output for 5 seconds and then Off again Turn Off the output for 5 seconds and then On again Relay output delay time is good for controlling the device e g electr...

Page 26: ...election of alarm phone dial and alarm SMS 0 means no alarm report 1 means SMS only 2 means phone dial only 3 means SMS first and then phone dial Z Z Z Z NNN Relay Output Control 0 means no relay output control 1 means relay output triggered by alarm N N N 11 16 Input Voltage Threshold Level Setup Command PWD XXXX POWVL mmmm XXXX Password Mmmm when power input is lower than this value alarm is tri...

Page 27: ...1M 5 000 1 000 0 5 000 0 500 O 00 0000 000 A2M 5 000 1 000 0 5 000 0 000 O 00 0000 000 K1 1 O 00 0000 000 PWD 1234 PARAMETER3 ST 000 K2 1 O 00 000 0 K3 1 O 00 000 0 K4 1 O 00 000 0 K5 1 O 00 000 0 K6 1 O 0 0 000 0 K7 1 O 00 000 0 K8 1 O 00 000 0 11 19 System Parameters RESET PWD XXXX PARAMETER This is to reset the parameters and password into default setting SMS Message received Parameter initiali...

Page 28: ...trength 1 31 PWD XXXX PARAMETER2 about Alarm Channel SMS Message received ST XXX VL XXXXX O AX BBBB CCC A1M XXXXX XXXXX R WWWWW WWWWW O AX BB BB CCC A2M XXXXX XXXXX R WWWWW WWWWW O AX BBBB CCC K1 N O AX BBBB C CC VL Min Operating Voltage below this level will trigger alarm 7VDC by default A alarm report to Control Centre 1 0 means no report 1 means report X alarm report to Control Centre 2 0 means...

Page 29: ...red alarm 2 means Open triggered alarm 3 means both Close or Open triggered alarm O Control Centre Report Setting A alarm report to Control Centre 1 0 means no report 1 means report X alarm report to Control Centre 2 0 means no report 1 means report BBBB report status for 4 phone numbers 0 means no report 1 means SMS but no phone dialing 2 means phone dialing but no SMS 3 means SMS and then phone ...

Page 30: ...Alarm disabled ZZZZZ Threshold High Value Setup WWWWW Threshold Low Value Setup Operation a When the captured analog value is higher or lower than the threshold values alarm is triggered within 0 5 second b SMS Relay On Off Dial Phone etc corresponding actions described on next page will be taken c Alarm will only be re triggered when the captured analog value returns to normal range and then reac...

Page 31: ...t to Control Centre 1 01 means alarm report to Control Centre 2 11 means alarm report to Control Centre 1 and 2 ZZZZ Selection of alarm phone dial and alarm SMS 0 means no alarm report 1 means SMS only 2 means phone dial only 3 means SMS first and then phone dial Z Z Z Z NNN Relay Output Control 0 means no relay output control 1 means relay output triggered by alarm N N N 1st phone number 2nd phon...

Page 32: ...d WWWWW WWWWW Alarm Triggered Threshold High Value Alarm Triggered Threshold Low Value A alarm report to Control Centre 1 0 means no report 1 means report X alarm report to Control Centre 2 0 means no report 1 means report BBBB report status for 4 phone numbers 0 means no report 1 means SMS but no phone dialing 2 means phone dialing but no SMS 3 means SMS and then phone dialing CCC relay output co...

Page 33: ...current type transducer c x 250 Start Value AI1 x Range 0 02 x 250 Start Value AI1 reported value will be Range x 0 012 x 250 Start Value 5 Start Value When current input is 12mA AI1 0 6 x 0 012 x 250 1 5 1 0 3 When user requires High level alarm at 0 018mA Low level alarm at 0 008mA H 0 018 x 250 1 x 0 6 0 02 x 250 1 0 525 L 0 008 x 250 1 x 0 6 0 02 x 250 1 0 15 When AI1 value is over 0 525 or be...

Page 34: ...X AI1 0000 AI2 0000 K1 X K2 X K3 X K4 X K5 X K6 X K7 X K8 X OUT1 Y OUT2 Y OUT3 Y AI2 Current Temperature 11 27 Temperature Alarm Setup PWD XXXX ADVALE2 XXXXX NNNNN Y ZZZZZ WWWWW 2 AD Channel 2 XXXXX Measuring Range 250 0 Default NNNNN Start Value 000 0 Default Y 1 Triggered Alarm enabled 0 Triggered Alarm disabled ZZZZZ Threshold High Temperature Setup WWWWW Threshold Low Temperature Setup Example...

Page 35: ...d High Temperature Setup 070 0 Threshold Low Temperature Setup 015 0 PWD 1234 ADVALE2 250 0 01 55 1 070 0 015 0 Case 2 When sensor reports a value higher than the actual start value adjustment will be 10 14 Actual Temperature 25 Sensor Report 27 45 Necessary Adjustment 25 27 45 02 45 AD Channel 2 Measuring Range 250 0 Start Value 12 45 Triggered Alarm enabled 1 Threshold High Temperature Setup 070...

Page 36: ...ent Humidity 11 30 Humidity Alarm Setup PWD XXXX ADVALE1 XXXXX NNNNN Y ZZZZZ WWWWW 1 AD Channel 1 XXXXX Measuring Range 140 0 Default NNNNN Start Value 000 0 Default Y 1 Triggered Alarm enabled 0 Triggered Alarm disabled ZZZZZ Threshold High Humidity Setup WWWWW Threshold Low Humidity Setup Example When humidity is above 70 RH or below 15 RH SMS alarm message will be sent to phone number 2 and rel...

Page 37: ... avg Operating Range Temperature 0 60 C Humidity 10 95 RH Measuring Range 0 100 RH Temperature Factor 0 4 RH C 30 80 RH 5V Operating Voltage Temperature Range 10 40 C reference point 25 C Accuracy 5 RH at 25 Input 5V Output Signal 0 3 DCV 0VDC 0RH 3VDC 100RH AD1 Channel Setup Start Value 000 0 Default Range 140 0 Default Fine Tuning of Measuring Humidity Adjust the Range of AD1 Channel Setup from ...

Page 38: ...one number or control centre phone number is set to the phone number of another SMS Alarm Unit Unit B Dead Loop problem happens 3 Unit B receives the alarm message from Unit A Since it will consider this incoming text as a wrong command message Unit B will reply to Unit A a message SMS format is error 4 Then Unit A receives the message SMS format is error from Unit B it also considers this incomin...

Page 39: ... by another command e g PWD XXXX SN YYY ARM status will be kept when power is lost and resumed 2 PWD 1234 ARM No other command is followed DISARM status will be as default when power is lost and resumed SMS message SMS format is error SMS message SMS format is error SMS message SMS format is error SMS alarm message Alarm is triggered ...

Reviews: