background image

Page  1

INTRODUCTION

The CO

2

 sensor series uses a highly accurate and reliable 

non-dispersive infrared (NDIR) sensor in an attractive, duct 

mount enclosure to monitor return air CO

2

 levels for indoor 

applications. The compact dual channel CO

2

 sensor achieves 

excellent performance characteristics, including high 

accuracy and low power consumption to ensure stable long 

term operation. The device is also available with an optional 

resistive temperature sensor.

BEFORE INSTALLATION

Read these instructions carefully before installing and commissioning the device. Failure to follow these 

instructions may result in product damage. Do not use in an explosive or hazardous environment, with 

combustible or flammable gases, as a safety or emergency stop device or in any other application where 

failure of the product could result in personal injury. 

Take electrostatic discharge precautions during 

installation and do not exceed the device ratings.

NOTE:

 This CO

2

 sensor incorporates a Self Calibration feature to correct CO

2

 sensor drift. This CO

2

 sensor 

is recommended for applications where the CO

2

 level will be close to normal (400 ppm) at least one hour 

per day. If the monitored space is occupied 24 hours or consistently maintains higher levels of CO

2

 level, 

the CD Series is recommended.

MOUNTING

The CO

2

 duct type sensor installs on the outside of a return air duct with the sampling tube inserted into 

the duct. Mount the sensor in an easily accessible location in a straight section of duct at least five feet 

from corners and other items that may cause disturbances in the air flow. Avoid areas where the detector 

is exposed to vibrations or rapid temperature changes. See Figure 1.
The duct CO

2

 detector principal of operation is based on the Venturi effect of the probe that extends into 

the HVAC duct. Air flowing through the duct is forced into the vent holes on one side of the probe, into the 

enclosure, over the CO

2

 sensor and then is drawn back out of the enclosure via the probe vent holes on the 

opposite side. 

NOTE

 to ensure proper humidity and temperature readings, the RH/T inlet on the probe must be installed 

directly into the airflow. See Figure 1.

Drill or punch a 7/8” or 1” hole in the duct at the preferred location and insert the probe into the hole to mark 

the enclosure mounting holes. Remove the unit and drill the two mounting holes. Clean all drilled holes 

of debris before mounting the device. Mount the enclosure to the duct with two sheet metal screws such 

that the duct air flow is parallel with the vent holes in the probe (i.e.: air flows directly into the probe holes). 

To prevent air leaks, ensure the gasket is compressed around the probe between the device enclosure and 

the air duct.

The enclosure has a hinged cover with a latch. Open the cover by pulling slightly on the latch on the 

bottom side of the enclosure and at the same time pulling on the cover, as illustrated in Figure 2. 

A 1/2" NPT threaded connection hole is provided in the left side of the enclosure. Screw the EMT connector 

or cable gland connector in until tight. See Figure 3. It is recommended that weatherproof conduit or 

cable gland fittings be used. The F style enclosure includes a 1/2" NPT to M16 thread adapter and cable 

gland fitting.

Two security screws are provided which can be installed to help secure the cover once settings and wiring 

connections are complete. See Figure 4.

Figure 1

Figure 3

Figure 2

Thread adapter and cable 

gland fitting

EMT Connector

IN-GE-CEDTXXX-03

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Duct Carbon Dioxide Sensor

CEDT Series - Installation Instructions

Summary of Contents for CEDT Series

Page 1: ...l of operation is based on the Venturi effect of the probe that extends into the HVAC duct Air flowing through the duct is forced into the vent holes on one side of the probe into the enclosure over the CO2 sensor and then is drawn back out of the enclosure via the probe vent holes on the opposite side NOTE to ensure proper humidity and temperature readings the RH T inlet on the probe must be inst...

Page 2: ...but not both at the same time This signal is used for either voltage or 4 20 mA active output as shown in Figure 5 In voltage mode the output is selectable for either 0 5 or 0 10Vdc using the PCB jumper The current output operates in the active mode and does not require a loop power supply the signal current is generated by the transmitter and must not be connected to a powered input or device dam...

Page 3: ...ee operation As such field calibration is not available or recommended on the product OUTPUT SIGNAL The CO2 output is scaled such that 4 20 mA or 0 5 Vdc or 0 10 Vdc equals 0 to 2000 ppm For 4 20 mA output type connect the mA output terminal to the controller analog input The COMMON terminal is the signal reference Typically this type of input would have a 250 ohm input impedance If using voltage ...

Page 4: ... 4 DIMENSIONS 116 5 mm 4 585 99 7 mm 3 93 0 5 NPT 112 5 mm 4 43 53 7 mm 2 11 152 mm 6 22 5 mm 0 88 IN GE CEDTXXX 03 Copyright Greystone Energy Systems Inc All Rights Reserved Phone 1 506 853 3057 Web www greystoneenergy com ...

Reviews: