Operating Instructions and Safety Precautions for the EHF Series Charger 

Safety  

 

Only  a t rained  person  should  operate  this  equipment.  The  input 

and output voltages used with this equipment may be high enough 

to endanger life, so insulated, shrouded connectors must be fitted. 

Please read this manual completely and convey instructions to all 

personnel 

concerned

. Keep the manual in a safe and convenient 

place.  

It is advisable to thoroughly read the information on battery safety 

supplied with the battery, prior to charging.  

Towards the end of charge, lead acid batteries give off hydrogen 

gas,  which  is  explosive  if  in  sufficient  concentration,  therefore 

avoid flames and sparks. Appropriate measures must be taken to 

ensure adequate ventilation.  

Incorrect  use  of  a  charger  or  maladjustment  of  its  controls  can 

damage a battery. The equipment has been factory set and does 

not require user adjustment.  

This product has been designed, manufactured and certified to be 

in conformance with UL Standards. Testing has ensured that the 

battery  and c harger  combination conform  as  a system  for  use  in 

Light  and  Heavy  Industrial  environments  for  each  respective 

product  variant.  The  following  notes  are  for  the  guidance  of  the 

person installing and using the product. 

 

The  charger  must  be i solated  from  the  input  supply  and t he 

battery,  before  any  of  the  panels  are  removed.  It  is  strongly

 

recommended that a Safety Warning Notice is placed at the input 

supply  isolator,  to  warn  against  inadvertent  reconnection  of  the 

mains supply and the isolator is locked in the off position. 

 

DANGER  -  Risk  of  electric  shock.  Do  not  touch  un-insulated 

portion of output connector or un-insulated battery terminal. 

 

Installation 

 

Installation must only be carried out by suitably qualified personnel 

and  in  accordance  with  current  local  and  national  wiring 

regulations.  

 

The unit should be positioned using lifting equipment, placed under 

the base. 

 

Battery leads should not be altered without prior consultation with 

service personnel. 

 

The charger should be sited in a cool, dry, well-ventilated location 

away from corrosive fumes and humid atmospheres. Ambient

temperature range must be maintained between 32°F - 95°F. 

 

The  charger  must

  have  a  minimum  clearance  overhead  of  eight 

inches (8”), ensuring ventilation is not obstructed at the rear intake 

and the front exhaust vents.

  

 

The charger is for inside use only.

  

 

Before installation, check that: 

 

 

The charger has not sustained any transit damage.  

 

The rating is suitable for the intended input supply and ‘lead 

acid’ battery to be charged. 

 

The connector polarity is correct and matches the polarity of 

the battery connector. 

 

 

Input supply 

 

A  hand  operated  lockable  isolator  should  be  used  in  the 

installation,  to  enable  the  charger  to  be  disconnected  from  the 

supply,  for  maintenance  or  repair  work.  The  charger  does  not 

exhibit high in-rush current, therefore type B or C circuit breakers 

can be used.  

 

 

CAUTION  - To reduce the risk of fire, use only on circuits provided 

with branch circuit protection consistent with the current indicated 

on the rating label and in accordance with the National Electrical 

Code, ANSI/NFPA 70 or equivalent. 

 

The  circuit  breakers  rating  should  be bas ed  on  the  chargers 

maximum input current, as stated on the rating label. 

 

Careful consideration must be taken when connecting this charger 

to  a  generator.  The  generator  must  be  capable  of  at  least  four 

times the input power requirements of the charger, failure to do so 

can  result  in  damage to  the charger.  The  generator  should  have 

load  step  immunity  to  prevent  undershoot  and  overshoot  with 

typical loads. Typically the generator control bandwidth should be 

less than 7Hz with good gain and phase margins. 

 

Display and Control 

 

Overview 

 

 

 

 

 

 

 

 

 

 

 

1. 

Communications Port 

2. 

High Visibility - Charge Status Indicator 

3. 

Soft-keys (The function of the button will be displayed on the LCD Display) 

4. 

LCD Display 

5. 

Pause Button 

 

Charge Status Indicator 

 

INDICATION  CHARGE STATUS 

INDICATION 

MODE 

Cycling red 

Bulk charge /  battery recovery 

mode 

Cycling yellow 

Second stage / watering 

All green 

Charge complete 

Green with cycling red 

Auto-balance pulse  / refresh 

pulse / equalising / cool down 

All flashing red 

Critical fault 

All off 

Standby / pause / inhibit 

Left hand indicator red 

Power save mode 

 

LCD Symbols 

 

*Watering system (Shown when enabled, flashing during operation) 

 

 

Communications port (Shown when active) 

 

Equalise (Shown when enabled, flashing during operation) 

 

 

Automatic Equalise (Shown when enabled, flashing during operation) 

 

Warning (Shown when a warning is active) 

 

 

Battery Recovery Mode (Shown when enabled, flashing during operation)

 

 

*Air system enabled (Shown when enabled, flashing during operation) 

 

 

* Optional extra 

 

Operation 

 
Before connecting the battery, check that the battery voltage 
corresponds to the voltage indicated inside the battery 
symbol  on the LCD Display.  The charger should be 
permanently connected to the mains supply. 

 

Standby 

 

With  the  input  supply  connected  and  no  battery,  the  charger  will 

e

nter  the  standby  mode.  During  this  mode  the  charge  status 

indicator will show indication 6 and the LCD display will show the 

following: 

Summary of Contents for EHF Series

Page 1: ...amage The rating is suitable for the intended input supply and lead acid battery to be charged The connector polarity is correct and matches the polarity of the battery connector Input supply A hand operated lockable isolator should be used in the installation to enable the charger to be disconnected from the supply for maintenance or repair work The charger does not exhibit high in rush current t...

Page 2: ...e charge cycle a second press will clear this function The equalize function can not be c leared once it has started and onl y one equalize is allowed per cycle In addition to enabling equalize manually the equalize feature can be set to initiate automatically by configuring the automatic equalize feature in the programming mode Automatic equalize may be set to occur every 0 to 250 cycles Once set...

Page 3: ...e F23 Batt ID PCB error F24 Batt ID Antenna error F25 Batt ID Tag read error F26 Batt ID not programmed F27 Slave 1 incorrect correct current F28 Slave 2 incorrect correct current F29 Slave 3 incorrect correct current F30 Slave 1 temperature fault F31 Slave 2 temperature fault F32 Slave 3 temperature fault These faults are usually associated with the battery check battery condition Only applicable...

Page 4: ...EHF EHP EMC ESS CHARGER INSTALLATION EHF 1PH Installation Wiring EHF 3PH Installation Wiring ...

Page 5: ...EHF EHP EMC ESS CHARGER INSTALLATION EHP 1PH Installation Wiring EHP 3PH Installation Wiring ...

Page 6: ...EHF EHP EMC ESS CHARGER INSTALLATION EMC ESS 1PH Installation Wiring EMC ESS 3PH Installation Wiring ...

Reviews: