ZEOS-AD

ANALOGUE ALGORITHMIC

ADDRESSABLE FIRE DETECTOR

MANUAL 210729

MADE IN PORTUGAL - EU

GLOBAL FIRE EQUIPMENT S.A.

Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL  | Tel: +351 289 896 560

Email[email protected]  | Technical Support: [email protected]  | www.globalfire-equipment.com

TECHNICAL SPECIFICATIONS

SUPPLY VOLTAGE

Loop Powered - 17V to 30V DC

CURRENT - QUIESCENT / SURGE

450uA max.

CURRENT - DEVICE IN ALARM

4 mA - Alarm LED illuminated

SENSITIVITY / CABLE SIZE

According to EN54-5 and EN54-7 / 0.5-2.5 mm²

RESET/START-UP TIMES

20 seconds max.

COLOUR / CASE MATERIAL / MAX. HUMIDITY

White / ABS / 95% RH Non-Condensing

NORMAL / TRANSIENT OPER. TEMPERATURE

0°C to 50°C / -10°C to 85°C

DIMENSIONS / WEIGHT

100 (D) x 50 (H) mm included base / 92g without base & 144g inc. base

For EN54-13 compliance, please check the control panel manual specifications.

ORDER CODE

DESCRIPTION

CERTIFICATE

ZEOS-AD-S

ANALOGUE ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR

1328-CPR-0521

ZEOS-AD-H

ANALOGUE ADDRESSABLE TEMPERATURE/HEAT DETECTOR

1328-CPR-0520

ZEOS-AD-SH

ANALOGUE ADDRESSABLE COMBINED SMOKE & HEAT DETECTOR

1328-CPR-0519

ZEOS-AD-SI

ANALOGUE ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR WITH ISOLATOR

1328-CPR-0607

ZEOS-AD-HI

ANALOGUE ADDRESSABLE TEMPERATURE/HEAT DETECTOR WITH ISOLATOR

1328-CPR-0610

ZEOS-AD-SHI

ANALOGUE ADDRESSABLE COMBINED SMOKE & HEAT DETECTOR WITH ISOLATOR

1328-CPR-0492

INSTALLATION

INSTALLING THE BASE - To ensure proper fit of the detector head to the base, all wires should be properly dressed at installation by positioning all wires flat against terminals and
fastening the wires away from connector terminals. The detector base can be mounted directly onto most standard electrical junction boxes.
INSTALLING THE HEAD - Align detector components using provided alignment marks on both the head and base. Align detector mark and short alignment mark on base. Fit the
detector head onto the base and twist clockwise to secure it. After all detectors are installed, apply power to the control unit and activate the detection loop. Test the detectors as
described below.
TESTING - All remote signalling systems, releasing devices and extinguishing systems should be disconnected during the test period and reconnected at the conclusion of testing.
SMOKE: Allow smoke from a cotton wick or test smoke aerosol to enter the detector’s smoke chamber for at least 10 seconds. When sufficient smoke has entered, the detector will
signal an alarm. This will be indicated by the illumination of the 2 Red LEDs provided. Make sure to clear smoke out of the chamber before resetting in order to keep the detector at
its current sensitivity setting.
HEAT: The detector to be tested should be subject to a flow of warm air at a temperature of between 65°C and 80°C. This requirement can be met by some domestic hair dryers.
Switch on the warm airflow and check that the temperature is correct and stable. From a distance of several cms, direct the airflow at the guard protecting the thermistor. The
detector should alarm within 60 seconds. Upon alarm immediately remove the heat source and check that the Red LEDs of the detector are illuminated. If a detector fails to
activate within 60 seconds, confirm connections and programming.If necessary, replace the unit.
NOTE: After testing, check that the system is returned to normal operation.Notify the appropriate authorities that the testing procedure has been completed and the system is
active again.
MAINTENANCE - The recommended minimum requirement for detector maintenance consists of annual cleaning of dust from the detector head using a low power
vacuum cleaner.

DO NOT ATTEMPT TO DISASSEMBLE THE DETECTOR.