background image

MPX-SNDR-DG V2

SOUNDER MODULE WITH 4

AND 8 SOUNDERS OUTPUTS

MANUAL 210628

MADE IN PORTUGAL - EU

GLOBAL FIRE EQUIPMENT S.A.

Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL  | Tel: +351 289 896 560

Email[email protected]  | Technical Support: [email protected]  | www.globalfire-equipment.com

TECHNICAL SPECIFICATIONS

SUPPLY VOLTAGE

24V DC to 30V DC

NORMAL OPERATION

6mA ( ) + 5.5mA per activated channel, 50mA on evacuation mode (all sounders)

 𝐼

𝑞

EOL RESISTOR

22K Ohms - 1/4 Watts

MAX. CABLE SIZE

2.5 mm²

COLOUR / CASE MATERIAL

White / ABS

OPER. TEMPERATURE / MAX. HUMIDITY

-10

º

C to 50

º

C / 95% RH Non-Condensing

DIMENSIONS / WEIGHT

150 (W) x 90 (L) x 32 (H) mm / 216 g inc. packaging

ORDER CODE

MPX-SNDR-DG - 4 V2

4 SOUNDER MODULE FOR ORION FAMILY

MPX-SNDR-DG - 8 V2

8 SOUNDER MODULE FOR ORION FAMILY

CONNECTIONS

Remove all power before connections!

Connections:

a.

Direct connection (flat cable directly connected
to conventional panel).

i. Connect panel and MPX-SNDR-DG V2 using

molex flat cable.

ii. Set both communication jumpers UP

(option “panel”).

iii. Remove supply jumper.

iv. Power supply from Panel, ensure it won’t

exceed the maximum allowed current from this
source.

b.

Remote connection (remote connection using an
interface module connected to panel).

i. Connect Interface and MPX-SNDR-DG V2 using

molex flat cable.

ii. Set both communication jumpers DOWN

(option “interface”).

iii. Fit the supply jumper. Power supply from

MPX-SNDR-DG V2.