background image

1

LMS SG PIR LIGHT SENSOR-R LONG

B29004005

307424

Presence detectors

EN

1.  Product characteristics

 

Passive infrared presence detector for ceiling installation

 

Rectangular detection area of 360°, up to  
30 m x 5 m (150 m

2

)  

 

2 separate detection zones

 

Restriction of detection area with cover clips

 

Automatic presence- and brightness-dependent control 
for lighting and HVAC

 

Mixed light measurement suitable for fluorescent lamps 

(FL/PL/ESL), halogen/incandescent lamps and LEDs

 

Channel A light: relay, 230 V

 

Fully or semi-automatic operation, switchable

 

Brightness setpoint adjustable, teach-in function

 

Reduction of time delay when present briefly (short-term 

presence)

 

Connection option for push buttons or switches for 
manual switching with automatic detection of push 
button/switch

 

Staircase light function

 

Pulse function for staircase light timer switch

 

Channel H, presence: relay, floating e.g. for HVAC control

 

Switch-on delay and time delay configurable

 

Detection sensitivity configurable

 

Ready for immediate use due to factory presetting

 

Test mode for checking function and detection area

 

Extension of detection area via Master/Master switching, 
a maximum of 10 detectors can be switched in parallel 
with each other

 

Ceiling installation in flush-mounted box

 

Accessories

: Surface mounting on ceilings possible with 

back box LMS MG SURFACE MNT FRAME (B29011002), 
optional; user remote control LMS MG USER REMOTE 
(B29012001), optional; app remote control LMS MG 
PROGRAM REMOTE BT (B29012003) optional, and the 
corresponding Glamox Sensor-app (iOS/Android); safety 
cover LMS SENSOR SAFETY COVER (B29011001), optional

2.  Safety

Danger of death through electric shock or fire!

¾

¾

Installation should only be carried out by a 

qualified electrician!

WARNING

 

Work on electrical systems may only be carried out by 

qualified electricians or by instructed persons under the 
guidance and supervision of a qualified electrician in 

accordance with the technical regulations applying to 

electricity! 

 

Comply with the country-specific safety regulations for 
work on electrical systems! Ensure absence of voltage in 
the cable before installation!

 

The device is maintenance-free. If the device is opened 
or penetrated, the guarantee lapses.

3.  Proper use

The presence detector is intended for indoor installation. 

4.  Function

The presence detector is primarily used in passage areas, 

staircases, garages, basements and warehouses for conveni-

ent and energy-efficient control of lighting as well as HVAC. 

The switch contact "light" switches lighting on with presence 

and insufficient brightness, and off with absence or sufficient 

brightness. The light can also be switched on/off manually 

using push buttons or switches.

The "Presence" switch contact controls heating, ventilation 

and air conditioning systems. The contact closes when some

-

one is present, a switch-on delay permits delayed switch on.

Function description

 Mixed light measurement 

 Presence detection

 Artificial light

 Push button for manual lighting control

 Incident daylight

Settings

 Brightness setpoint value (lux)

 Lighting time delay 

Summary of Contents for B29004005

Page 1: ...l app remote control LMS MG PROGRAM REMOTE BT B29012003 optional and the corresponding Glamox Sensor app iOS Android safety cover LMS SENSOR SAFETY COVER B29011001 optional 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed pe...

Page 2: ...tact is closed the time delay will be restarted at every movement Push buttons or switches do not influence the contact Switch on delay The switch on delay prevents instantaneous switching on The contact closes only on expiry of the switch on delay provided that people are permanently present Time delay The time delay enables delayed switching off of HVAC devices and systems after the room is vaca...

Page 3: ...h inrush current levels of the EBs and LED drivers The use of an external contactor helps with large loads Parallel switching enables allocation of load to several Masters All switched loads must be properly suppressed 6 Installation Flush mounted fitting The presence detector is flush mounted using a size 1 stan dard flush mounting installation socket Surface mounted installation with LMS MG SURF...

Page 4: ... on presence Potentiometer Lighting time delay The following guidance values have proved themselves in practice and are recommended as settings Transit zones no work area approx 5 min Classroom approx 10 min Work areas office meeting room approx 10 min Pulse Control of staircase light timer switch 0 5 s on 10 s off Settings of switch contact H presence Potentiometer Presence time delay The contact...

Page 5: ...of the different brightness measurements at the ceiling and on the work surface the brightness value depends on the ambient conditions Room correction factor Brightness value at the ceiling Brightness value on the floor The brightness measurement value at the ceiling is influenced by the installation location incidence of light position of the sun weather conditions the reflection properties of th...

Page 6: ... to absence or brightness man Control input S Control input S for manual switch on off of channel A light automatically detects push buttons or switches Several push buttons can be connected to control input S Use light push button only with neutral conductor connector Value range Glamox Sensor app Automatic detection of push button or switch A signal that is present for less than 0 7 s is detecte...

Page 7: ... light switch contact opens after 10 s y y Brightness measurement deactivated detector does not react to brightness y y The detector reacts as in configuration type fully auto matic device even if semi automatic is set y y Teach in cannot be activated in test mode Test mode ends automatically after 10 min The detector restarts itself see switch on behaviour 10 Technical data Operating voltage 110 ...

Page 8: ...r Push button not fed to the Master Light cannot be swit ched off with the push button Push button not fed to the detector Check wiring to the push button Device does not respond Short circuit or several phases in parallel swit ching Disconnect detector from the power supply for 5 min thermal fuse Error flashing 4 x per second Error in self test device not functional LED display LED Description Fl...

Reviews: