background image

M

01

GIA-MDI-09M01 | 

GIA-

MDI-12M01 

GIA-MDI-18M01 

GIA-MDI-24M01 

Thanks for choossing our product. 

Please, read carefully this manual 

before using the product 

OWNER’S AND INSTALLATION

 MANUAL

DUCTS

ENGLSI

H

Summary of Contents for GIA-MDI-09M01

Page 1: ...M01 GIA MDI 09M01 GIA MDI 12M01 GIA MDI 18M01 GIA MDI 24M01 Thanks for choossing our product Please read carefully this manual before using the product OWNER S AND INSTALLATION MANUAL DUCTS ENGLSIH ...

Page 2: ... minutes later after power recovery During installation the communication cable and the power cord must not be twisted together but instead separated with an interval of at least 2cm otherwise the unit is likely to run abnormally This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they ...

Page 3: ...cates that this product should not be disposed with other household wastes throughout the EU To prevent possible harm to the environment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use the return and collection systems or contact the retailer where the product was purchased They can...

Page 4: ...f the Indoor Unit 8 5 Installation of the Air Supply Duct 8 6 Drawings of the Air Supply Outlet and Return Air Inlet 10 7 Installation of the Return Air Duct 10 8 Installation of the Condensate Pipe 11 9 Design of the Drain Pipe 12 10 Installation of the Drain Pipe 12 11 Precautions for the Lift Pipe 13 12 Test for the Drainage System 14 13 Piping 15 14 Insulation for the Refrigerant Pipe 16 15 Wi...

Page 5: ...ee the proper drainage meanwhile it should be insulated to prevent condensing otherwise the improper installation would cause water leakage and then wet the household wares in the room Do not use or place any inflammable or explosive substance near the unit Under the occurrence of an error like burning smell etc please cut off the main power supply of the unit Keep good ventilation in the room to ...

Page 6: ...ing water pipe lightening rod or phone cable s earth lead Turn off the unit after it runs at least five minutes otherwise its service life will be shortened Do not allow children operate this unit Do not operate this unit with wet hands Cut off the main power supply prior to the cleaning of the unit or the replacement of the air filter When the unit is not to be used for a long time please cut off...

Page 7: ... enough to withstand the weight of the unit c Where the drain pipe can be easily connected to outside d Where the flow of the air inlet and outlet are not blocked e Where the refrigerant pipe of the indoor unit can be easily led to outside f Where there is no inflammable explosive substances or their leakage g Where there is no corrosive gas heavy dust salt mist smog or moisture CUATION The unit w...

Page 8: ...nnel Besides the air switch coupled with the leakage current protection switch must be equipped which is of enough capacity and of both magnetic and thermal tripping functions in case of the short circuit and overload 3 Earthing Requirements a The air conditioner is classified into the Class I appliances so its earthing must be reliable b The yellow green line of the air conditioner is the earth l...

Page 9: ... is mm unless otherwise specified Fig 1 is applicable to GIA MDI 09M01 GIA MDI 12M01 GIA MDI 18M01 GIA MDI 24M01 Fig 1 Table 1 Outline Dimensions Item Model A B C D E F G H I J GIA MDI 09M01 742 491 662 620 700 615 782 156 200 635 GIA MDI 12M01 GIA MDI 18M01 942 491 862 820 900 615 982 156 200 635 1142 491 1062 1020 1100 615 1182 156 200 635 GIA MDI 24M01 ...

Page 10: ...2 is left for the access to maintenance 5 It should be far away from where there is heat source leakage of inflammable explosive substances or smog 6 It is the ceiling type unit concealed in the ceiling 7 The power cords and connection lines of the indoor and outdoor units must be at least 1m away from the TV set or radio to avoid the image interference and noise even if 1m is kept the noise may b...

Page 11: ...indoor unit on the ceiling as shown in Fig 5 Fig 5 CUATION Prior to the installation please make a good preparation for all piping refrigerant pipe drain pipe and wiring wires of the wired controller wires between the indoor and outdoor unit of the indoor unit to make the further installation much easier If there is an opening in the ceiling it is better to reinforce it to keep it flat and ...

Page 12: ...the actual installation environment 4 Horizontality Check of the Indoor Unit After the installation of the indoor unit its horizontality must be checked to make sure the unit keep horizontal fore and aft and keep an inclination of 5 toward the drain pipe right and left as shown in Fig 6 Fig 6 5 Installation of the Air Supply Duct a Installation of the Rectangular Air Supply Duct Fig 7 Table 2 No N...

Page 13: ...gth of the air supply duct plus the maximum length of the return air duct For the unit with the auxiliary electric heating function if the round duct is to be adopted then the straight length of the transition duct can not be less than 200mm The duct is either rectangular or round and connected with the air inlet outlet of the indoor unit Among all air supply outlets at least one should be kept op...

Page 14: ... MDI 09M01 156 662 580 162 156 862 780 162 GIA MDI 24M01 156 1062 980 162 7 Installation of the Return Air Duct a The default installation location of the rectangular flange is in the back and the return air cover plate is in the bottom as shown in Fig 11 Fig 11 b If the downward return air is desired just change the place of the rectangular flange and the return air cover plate c Connect one end ...

Page 15: ...ion method can be chose with considering the conditions of the building and maintenance etc as shown in Fig 12 Fig 12 Table 5 Parts and Components of the Return Air Duct No Name No Name 1 Return Air Louver with the filter screen 4 Indoor Unit 2 Canvas Duct 5 Air Supply Duct 3 Return Air Duct 6 Access Grille 8 Installation of the Condensate Pipe a The condensate pipe should keep a inclination angle...

Page 16: ...pipe can be the ordinary hard PVC pipe which can be purchased locally During the connection inset the end of the PVC pipe to the drain outlet then tighten it with the drain hose and binding wire but never connect the drain outlet and the drain hose by adhesive d When the drain pipe is used for multiple devices the public section of the pipe should be 100mm lower than the drain hole of each device ...

Page 17: ...nt of sponge for thermal insulation g The drain hose inside the room also should be insulated Fig 15 11 Precautions for the Lift Pipe The installation height of the lift pipe should be less than 850mm It is recommended to set an inclination angle 1 2 for the lift pipe toward the drainage direction If the lift pipe and the unit form a right angle the height of the lift pipe must be less than 800mm ...

Page 18: ...onverge please follow the installation steps below Fig 17 12 Test for the Drainage System a After the electric installation please take a test for the drainage system b During the test check if the water flow goes through the pipe correctly and observe carefully the joint to see if it leaks or not If this unit is installed in the newly built house it is suggested to take this test prior to the cei...

Page 19: ...0 φ15 9 60 65 a The bending degree of the pipe can not be too small otherwise it will crack And please use a pipe bender to bend the pipe b Wrap the exposed refrigerant pipe and the joints by sponge and then tighten them with the plastic tape CUATION During the connection of the indoor unit and the refrigerant pipe never pull any joints of the indoor unit by force otherwise the capillary pipe or o...

Page 20: ...pe 1 Bundle the refrigerant pipe and electric wire together with tape and separate them from the drain pipe to prevent the condensate water overflowing 2 Wrap the pipe from the bottom of the outdoor unit to the top of the pipe where it enters the wall During the wrapping the later circle should cover half of the former one 3 Fix the wrapped pipe on the wall with clamps CUATION Do not wrap the pipe...

Page 21: ...ir conditioning unit 3 Fix a wiring terminal matching with the size of the screw to the end of the multi core wire with the crimpling pliers 4 Let the screw go through the terminal of the multi core wire and then fix it on the wiring board Fig 20 WARNING If the power cord or the signal line is damaged they must be replaced with the dedicated one Prior to the wiring please check the voltage marked ...

Page 22: ... won t assume any responsibility for the damage or abnormal running of the unit 16 Wiring of the Power Cord single phase CAUTION The power supply for each indoor unit must be uniform Dismantle the cover of the electric box of the indoor unit Let the power cord go through the rubber ring Connect the wiring communication through the piping hole of the chassis and the bottom of the appliance upward t...

Page 23: ...uct Split Unitary Duct Split 19 GIA MO5 42M01 Fig 22 17 Wiring of the Signal Line of the Wired Controller 1 Open the cover of the electric box of the indoor unit 2 Let the signal line go through the rubber ring ...

Page 24: ... Fan Motor 220 240V 50Hz 220 240V 50Hz Cooling and Heating 220 240V 50Hz 220 240V 50Hz Notes The sectional area listed above is applicable to the power cord with at most a length of 15 meters For the longer cord its sectional area should be enlarged to avoid the cord burning out caused by the over current Ⅳ Rated Working Conditions Table 8 Working Temperature Range Indoor side state Outdoor side s...

Page 25: ...utlet The set temperature is too high poor heating effect The air filter screen is too dirty or clogged The door or window is not closed fully The set temperature is too low uncontrollable controller If the remote controller crashes even if the batteries have been replaced please open the back cover of it and press the button ACL to let it back to the normal condition Is the remoter controller in ...

Page 26: ... When the air conditioning unit is used under the environment with heavy dust the air filter should be cleaned often generally once every two weeks b Maintenance before seasonal use 1 Check if the air inlet outlet of the indoor unit is clogged 2 Check if the earthing is in good condition 3 Check if the wiring is in good condition 4 Check if the indicating lamp of the wired controller blinks after ...

Page 27: ...C Industria 13 l Polígono Industrial El Pedregar 08160 Montmeló Barcelona Spain Phone 0034 93 390 42 20 Fax 0034 93 390 42 05 info giatsu com www giatsu com ...

Reviews: