MANUAL ZIGBEE CONFIGURATION 

BINDING BETWEEN THE GWA1521 ACTUATOR AND THE GWA1502 INTERFACE 

 

 

 

TECHNICAL MANUAL 

 

 

Summary of Contents for Chorus GWA1521

Page 1: ...MANUAL ZIGBEE CONFIGURATION BINDING BETWEEN THE GWA1521 ACTUATOR AND THE GWA1502 INTERFACE TECHNICAL MANUAL ...

Page 2: ...page 2 ZIGBEE TECHNICAL MANUAL BINDING BETWEEN GWA1521 AND GWA1502 ...

Page 3: ...NICAL FILES 5 DIMENSIONS 6 BREAKDOWN OF THE ZIGBEE DEVICES 7 ELECTRIC DIAGRAMS 8 CONFIGURATION 9 CREATING AND JOINING TO THE ZIGBEE NETWORK 9 ASSOCIATION BETWEEN DEVICES 9 ACTUATOR PARAMETERS GWA1521 10 HOW TO SET THE DURATION OF THE TIMING 10 INTERFACE PARAMETERS GWA1502 11 INTERFACE GWA1502 FACTORY RESET 12 ACTUATOR GWA1521 FACTORY RESET 12 ...

Page 4: ... will use 3 Generate the PAN Personal Area Network 4 Generate the decoding key used by that specific network 5 Assign a short address to all the devices which are part of that ZigBee network 6 Transmit the decoding key to those devices End device Battery controlled ZigBee devices Joining Operation via which a ZigBee device becomes part of a ZigBee network Permit Join Operation via which a ZigBee n...

Page 5: ...DEGREE OF PROTECTION IP20 OPERATING TEMPERATURE 5 45 C STORAGE TEMPERATURE 25 70 C RELATIVE HUMIDITY NON CONDENSATIVE Max 93 DIMENSIONS L X H X D MM 42x40x20 COMMUNICATION PROTOCOL ZigBee IEEE 802 15 4 REFERENCE STANDARDS 2014 53 EU GWA1502 CATEGORY Contact interface SUPPLY VOLTAGE 230V AC 50 Hz INPUT VOLTAGE 230V AC OUTPUT POWER 8 dBm NO OF INPUT CHANNELS 2 MAX CABLE LENGTH DEGREE OF PROTECTION I...

Page 6: ...page 6 ZIGBEE TECHNICAL MANUAL BINDING BETWEEN GWA1521 AND GWA1502 DIMENSIONS GWA1521 GWA1502 ...

Page 7: ...IGBEE page 7 BREAKDOWN OF THE ZIGBEE DEVICES GWA1502 A1 DIP switch with 4 one way switches A2 Miniature button key for joining functions A3 Status LED GWA1521 A1 DIP switch with 3 one way switches A2 Miniature button key for joining functions A3 Status LED ...

Page 8: ...ETWEEN GWA1521 AND GWA1502 ELECTRIC DIAGRAMS GWA1502 L Power supply neutral N Power supply phase I1 Channel 1 input I2 Channel 2 input GWA1521 N Power supply neutral L Power supply phase 1 Output common wire 2 NO output I1 Local command input ...

Page 9: ...n for a few seconds and then begin flashing From this moment Permit Join is activated for 15 minutes this device is now the network coordinator 4 Make sure the interface is in its factory set condition if it isn t make a factory reset 5 When the device is powered a scan will be launched red LED to identify an open ZigBee network 6 When the association has been made the status LED will begin flashi...

Page 10: ...ated when the contact opens no command is sent The selected position merely determines the behaviour of the local input it doesn t influence overall product operation How to set the duration of the timing The duration of the timing function activation time stair raiser light can be modified as follows 1 Bring the dip switches to the position shown to enter activation time configuration mode 2 Wait...

Page 11: ...operating mode selected and the actuators associated the behaviour of each channel upon the closure opening of the corresponding input is as follows MODE ASSOCIATION WITH ON OFF ACTUATOR Independent push button Closure inversion of current load status toggle Opening no effect Combined push button Closure sends ON if channel 1 OFF if channel 2 Opening no effect Toggle switch Closure and opening inv...

Page 12: ...tivation push button A2 for at least 10 seconds The status LED will flash red and green alternately for 3 seconds then become red fixed ACTUATOR GWA1521 FACTORY RESET Press and hold the Permit Join activation push button A2 for at least 10 seconds The status LED will flash red and green alternately for 3 seconds then become red fixed ...

Page 13: ...TECHNICAL MANUAL BINDING BETWEEN GWA1521 AND GWA1502 ZIGBEE page 13 LAST REVISION 07 2020 code 70194238 ...