NEX RO 500

User Guide

Содержание NEX RO 500

Страница 1: ...info gcwater com 20 Opportunity Road Camdenton MO 65020 805 484 1589 www GCWater com NEX RO 500 User Guide ...

Страница 2: ...urposes without specific written permission from GC Water Contents 2 Unit Information 3 RO Unit Diagram 4 Installation Hardware 5 Installation Tools 5 Installation Notes 6 Installation Instructions 7 Hand Held TDS Meter 8 Emergency Bypass 9 Filtered Bypass 10 Filter Membrane Replacement 11 Production Rate Check 12 Routine System Check Guide 13 Troubleshooting Guide 14 Gauge Info 15 Warranty 16 CON...

Страница 3: ...get total draw Operating Parameters Open Flow Rate 0 35 GPM Daily Production Rate 500 GPD Sound Emission 50dB max Unit Dimensions Height 19 5 Width 19 5 Depth 9 25 Ship Weight 25 lbs Wet weight 37 lbs Production rates are calculated with incoming water pressure at 70 psi and temperature at 77 F Warning Do not use where water is microbiologically unsafe or of unknown quality Replacement components ...

Страница 4: ... Sediment Pre Filter 5 Carbon Pre Filter 6 Membrane 7 Membrane Drain 8 City In Fitting 9 Unit Connection Plug 10 Drain Fitting 11 Filtered Bypass Fitting 12 RO Out Fitting 13 Solenoid Incoming Pressure Outgoing Pressure 1 2 4 5 6 7 3 City In Filtered Bypass RO Out Drain 8 11 10 9 12 13 PAGE 4 ...

Страница 5: ...TION TOOLS RO Unit Mounting Bracket Tubing Cutters 7 Unit Connection Cord 20 of 3 8 Tubing 2 1 1 4 x 1 1 2 Lag Bolts 2 1 4 Lag Bot Washers 1 4 Wrench Not Included 3 32 Drill Bit Not Included Electric Power Drill Not Included PAGE 5 ...

Страница 6: ... level rim of the receptor The vertical distance between the conveyor and receptor shall be no less than 1 inch 7 Installation must comply with existing local plumbing codes Air gaps must comply with drawings or an approved air gap device may be used In addition some local plumbing codes require back flow devices Both the air gap device and back flow device are not supplied as part of the unit The...

Страница 7: ...y In 8 in RO Unit Diagram on page 4 on the RO unit Do not turn on the city water at this time 7 Run 3 8 tubing from the RO Out 12 in RO Unit Diagram on page 4 on the RO unit to RO In on the storage tank 8 Run 3 8 tubing from Drain 10 in RO Unit Diagram on page 4 on the RO unit to a city drain NOTE When connecting the drain make sure there are no obstruction for the flow of the water The drain shou...

Страница 8: ...ored in water or a solution Changing the Batteries 1 When the meter displays a flashing battery symbol your batteries are getting weak and should be replaced soon To change the batteries 2 Pull out the blue battery compartment using your thumb nail 3 Remove the three batteries 4 Insert new batteries in the direction as depicted inside the compartment The flat side of the battery is the positive si...

Страница 9: ...Location will be in the unit guide that came with the water processing unit 3 Turn the yellow handle located on the water processing unit towards ON 3 in RO Unit Diagram on page 4 Note Tank will not refill while in bypass System pressure will read zero psi Removing the system from bypass 1 Turn the yellow handle located on the water processing unit towards OFF 3 in RO Unit Diagram on page 4 2 Turn...

Страница 10: ...handle located on the front panel of the water storage unit Location on the water storage unit towards ON 9 Turn the feed water going to the unit ON The Incoming and Outgoing gauges should both begin to read pressure Removing the system from filtered bypass 1 Turn the feed water going to the unit OFF 2 Turn the yellow bypass handle located on the front panel of the water storage unit Location on t...

Страница 11: ...nstall apply pressure to the top of one hand and insert the filter with the other 1 Remove blue cap on new filter and line up notches on filter to match placement on head Push up snugly on filter while holding the top of the processing unit Turn the filter to the right to lock 3 4 Repeat for all other filters you are installing 2 If membranes were replaced reinstall the drain fittings by pushing t...

Страница 12: ...essing system is filling the storage tank 7 Place the RO Out line into the 500 ml graduated cylinder for 15 seconds 8 Note amount of water in graduated cylinder and use the calculation method below for gallons per day GPD Multiply by 4 then multiply by 60 then multiply by 24 and then divide by 3785 ____ gallons per day 9 When your calibration is completed turn off the incoming water to the unit 10...

Страница 13: ...asis Verify that all the gauges are reading the correct psi Make sure that the system bypass handles are in the off position Please contact your service provider when bypass handle is moved into bypass Only emergency situations require putting the bypass handle into the bypass position Listen for any changes in the sounds coming from the unit Check on a weekly basis Verify that there are no leaks ...

Страница 14: ...sso machine or brew coffee during troubleshooting procedures equipment damage may result Y STEP INSTRUCTIONS 1 Check the system pressure gauge reading If the pressure reading is normal 35 60 psi then there is no immediate problem with the system If the pressure moves below 35 psi or is at 0 psi this means the city water pressure to system is too low or the electric and or water is turned off to sy...

Страница 15: ...at is coming out of the filters on the water processing unit This gauge should be relatively close to the incoming pressure gauge It will typically sit about 5 psi less then the incoming pressure gauge If it is showing a difference of 20 psi with the incoming pressure gauge your filters will need to be replaced right away The outgoing pressure gauge will have a resting psi of 0 psi when the storag...

Страница 16: ...s installed and used in compliance with the instructions enclosed with the system The Warranty does not cover any non GC Water parts the costs of repairs or adjustments to the unit that may be needed because of the use of improper parts equipment or materials unauthorized alterations of the unit or failure of a unit caused by such alter ations or by unauthorized repairs The Warranty does not cover...