manualshive.com logo in svg
background image

This Quick Start Guide is intended for experienced installing technicians. It is a basic reference to ensure all connections are properly made.
Models include Conekt CSR-35P presentation and CSR-35L long-range readers. For additional information please reference Farpointe Data’s 
website www.farpointedata.com.

1.0 Introduction

A key component of a physical security electronic access control system, a mobile-ready reader combining BLE and contactless smart card 
technologies is based on RFID technology. In operation it is capable of reading data stored on a contactless smartcard credential via high 
frequency—or reading data from mobile credential stored in a smartphone’s wallet app via BLE technology—and without physical contact, and 
then passing the data obtained to the physical access control system. Access control systems typically manage and record the movement of 
individuals through a protected area, such as a locked door.

2.0 Mounting Provisions

Each reader may be installed either indoors or outdoors. Mounting options shown in the table below. Use supplied #6 mounting screws, or 
equivalent security screws, for installation. 

CSR-35P

CSR-35L

Mullion Mount

Single-gang Wall Mount*

*Plastic or metal.

3.0 Reader Wiring

Wiegand

Magstripe

Conductor

Function

Conductor

Function

Red

DC (8-14 VDC)

Red

DC (8-14 VDC)

Black

Ground

Black

Ground

Green

Data 0

Green

Clock

White

Data 1

White

Data

Brown

Red LED

a

Brown

Red LED

Orange

Green LED

b

Orange

Green LED

Yellow

Not Used

Yellow

Not Used

Blue

Beeper

Blue

Beeper

Violet

Read Mode

c

Violet

Read Mode

Drain

Shield Ground

Drain

Shield Ground

4.0 Cable Requirements

24 AWG minimum, multi-conductor stranded with an overall foil shield, for example Belden 9535 or similar, supporting the five conductors 
comprising the physical layer of the Wiegand interface (power, ground, data 0, data 1, and/or beeper and LED). Alternatively, Belden 9539 or 
similar, for all reader functions. Contact your access control system manufacturer for their specific requirements. Per the SIA’s Wiegand 
specification, maximum cable length is 500 feet (152 m).

5.0 Output Formats

Wiegand (industry standard 26-bit Wiegand and custom Wiegand formats)
Magnetic Stripe (ABA Track II, clock and data, with card present)

6.0 Grounding

Shield (drain) continuity must run from the reader to the access panel. Shield (drain) and reader ground must be tied together at the access panel 
and connect to an earth ground at one point.

7.0 Power

Reader may be powered by the access panel. A linear power supply is recommended for best operation.

QUICK START GUIDE

CONEKT

®

 MOBILE-READY  

CONTACTLESS SMARTCARD READER

NOTES:

a

Single Line LED:

 This is the standard operating mode and does not make use of the 

Orange conductor. The LED is Red when the reader is idle and flashes when a card is 
presented. The LED turns Green when the Brown Conductor is pulled low by the access 
control panel.

b

Dual Line LED:

 This mode makes use of both the Brown and Orange conductors. The 

Brown conductor controls the Red LED and the Orange conductor controls the Green 
LED. LED states are determined by the access control system option and capability.

c

Read Mode:

 In regards to contactless smart card credentials, the reader will only read 

and output the credential’s Card Serial Number (CSN) when the Violet conductor is 
pulled low (connected to ground). Otherwise, the reader will only read and output the 
credential’s programmed Sector data.

Unused conductors should be trimmed, isolated and taped back to prevent unintended 
current flows. Apply positive voltage only to the Red DC Conductor.