Overview

The SC1008 Branch Circuit Emergency Lighting Transfer Switch (BCELTS) transfers a single lighting
circuit from its normal power source to an emergency power source in the event of the loss of normal
power or an external trigger (e.g., fire alarm).

The SC1008 BCELTS includes the following features and functions:

a front panel accessible push–and–hold Test Switch

a front panel accessible Laser Test, enabling remote testing with the use of a laser pointer (or
similar)

front panel status indicators for Normal Power (green) and Emergency Power (red)

a fire alarm dry contact input, which can be set for normally open or normally closed operation

an auxiliary relay for 0–10V or Digital Addressable Lighting Interface (DALI) control signals

Compliance

The SC1008 meets or exceeds the following regulatory standards:

UL Listed to UL 1008 for Branch Circuit Emergency Transfer Switch Equipment

cUL Listed to CSA C22.2 Emergency Transfer Switch Equipment

UL Listed to UL 2043 for plenum rated products

Complies with ANSI/NFPA 110, Standard for Emergency and Standby Power Systems

Satisfies requirements of the National Electrical Code (NFPA 70):

-

Article 700 – Emergency Systems

-

Article 701 – Legally Required Standby Systems

-

Article 702 – Optional Standby Systems

-

Section 518.3(C) – Assembly Occupancies

-

Section 520.7 – Theatres and Similar Locations

-

Section 540.11(C) – Motion Picture Projection Rooms

Summary of Contents for BCELTS

Page 1: ...ions a front panel accessible push and hold Test Switch a front panel accessible Laser Test enabling remote testing with the use of a laser pointer or similar front panel status indicators for Normal Power green and Emergency Power red a fire alarm dry contact input which can be set for normally open or normally closed operation an auxiliary relay for 0 10V or Digital Addressable Lighting Interfac...

Page 2: ...ion that conforms to the following ambient environment 0 C 40 C 5 95 non condensing humidity Electrical Specification Note Continuous load current not to exceed 100 of the switch rating Use copper wire only minimum 75 C conductors Normal and Emergency Rated Operational Voltage Input 120 277 VAC 10 50 60 Hz Load Rating Supports a continuous load of up to 20 A for tungsten and resistive load types a...

Page 3: ...of 18 AWG wire connected between the input and the switch Fire Alarm Inputs of up to ten SC1008 units can be wired together using a single normally open or normally closed contact See Fire Alarm Input on page 8 for details 0 10 V Auxiliary Output The 0 10 V Auxiliary Output provides an additional single pole relay that opens when the unit is in the emergency state This allows connection of 0 10 V ...

Page 4: ... or death AVERTISSEMENT RISQUE D ELECTROCUTION Travailler à l intérieur du panneau sans avoir déconnecté le courant peut entrainer des blessures graves voire mortelles Before you begin pulling and terminating wire to the SC1008 BCELTS enclosure make sure the main circuit breaker cabinet or other readily accessible input power disconnect device for both normal and emergency power input is locked ou...

Page 5: ...ed from the SC1008 b Terminate to the respective terminals LOAD 2N neutral and LOAD 1H hot in the SC1008 enclosure securing each terminal screw onto the wire 3 Install normal sense jumpers included Step 3 4 H 5 N 6 H N 3 SENSE NORMAL a Install a jumper wire between terminals SENSE 3H hot and NORMAL 5H hot b Install a jumper wire between SENSE 4N neutral and Normal 6N neutral 4 Terminate normal pow...

Page 6: ... the wire 3 Install a jumper wire included between SENSE 4N neutral and Normal 6N neutral Note If using a separate neutral for the sense circuit do not install the jumper If using a three wire feed as shown above install the jumper as described in step 3 4 Terminate normal power wires a Run a neutral and a hot wire through conduit from the normal power source controlled dimmer or switch to the SC1...

Page 7: ...ad position b Terminate to the respective terminals LOAD 2N neutral and LOAD 1H hot in the SC1008 enclosure securing each terminal screw onto the wire 3 Terminate normal power wires a Run a neutral and a hot wire through conduit from the dimmer module to the SC1008 b Terminate to the respective terminals NORMAL 6N neutral terminal and NORMAL 5H hot terminal in the SC1008 enclosure securing each te...

Page 8: ...ween 0 10 V ballast and the 0 10 V terminal 9 in the SC1008 and secure the terminal onto the wire 3 Run a common wire typically grey between the 0 10 V controller and the 0 10 V ballast Fire Alarm Input SC1008 SC1008 Connect up to 10 units Fire Alarm 11 12 FIRE ALARM 11 12 FIRE ALARM The SC1008 features a single dry contact input that can be used to force the transfer from normal to emergency stat...

Page 9: ... using either the test button or laser test as described in the following sections LED States Red LED Green LED State Notes On On Normal and emergency power are both present The SC1008 is supplying Normal power to the load Blinking Off The SC1008 is supplying emergency power to the load This may be due to the loss of normal power the making of the fire alarm contact or the activation of the test m...

Page 10: ...RIC SHOCK Failure to disconnect all power to the panel before working inside could result in serious injury or death AVERTISSEMENT RISQUE D ELECTROCUTION Travailler à l intérieur du panneau sans avoir déconnecté le courant peut entrainer des blessures graves voire mortelles Before you begin pulling and terminating wire to the SC1008 BCELTS enclosure make sure the main circuit breaker cabinet or ot...

Page 11: ...input power disconnect device for both normal and emergency power input is locked out and tagged out Enclosures installed without an accessible input power disconnect device cannot be serviced or operated safely Follow all local codes and restrictions When the disconnect device is not located near the installed enclosure the disconnect must allow for proper lockout tagout 1 Disconnect both power s...