Flow Range O&M Manual 

Содержание POWERBOOST FLOW V Series

Страница 1: ...POWERBOOST Clean Water Booster Sets Flow Range O M Manual...

Страница 2: ...ontents General 3 Installation Checklist 4 Location Consideration 5 Installation Information Diagrams 5 Commissioning 6 Pressure Vessel 7 Pump Speci cation 8 Controller Speci c Instructions Troublesho...

Страница 3: ...t commercial pressure boosting The POWERBOOST unit should not be installed in areas that are classified as hazardous or where there is a risk of an explosion or harm to people The manufacturer does no...

Страница 4: ...solation Valves should be fitted before and after the unit to allow for reliable service or repair 4 Fit the supplied pressure vessel to the discharge manifold See Page 7 5 In accordance with the late...

Страница 5: ...olation mounts are provided and should be fitted if required Outlet Manifold NB Pipe Work connections can be made to either end of the inlet outlet Manifold to suit your site layout Blanking Caps are...

Страница 6: ...rotected by a suitable MCB or fuse Wiring Connections The POWERBOOST unit has provision for an external level switch input and a volt free general alarm output BMS connection Connections for these fea...

Страница 7: ...oster unit if required Pressure Vessel Theairpre chargeinthepressurevesselshouldbeset65 ofthepre setworkingpressureformaximum e ectiveness It is recommended to check the tank air pressure every 4 6 mo...

Страница 8: ...00V Cut In System Pressure Flow Pressure 4CR80 0 55 0 75 3 4 2 2 3 80 5 2 5CR80 0 75 1 4 3 2 5 3 4 80 6 7 4CR100 0 75 1 4 5 2 6 2 3 100 5 0 5CR100 1 1 1 5 4 2 2 4 3 4 100 6 3 4CR200 1 5 2 7 3 4 2 3 4...

Страница 9: ...Steadypres Light Signals Steadypres Keyboard ON OFF BLINKING STATUS POWER STEADYPRES does not detect power supply WARNING cannot guarantee the absence of power supply the electronic board may be faul...

Страница 10: ...te and the inverter re starts in automatic mode HIGH TEMP BOX Only T T models The temperature inside the inverter has reached 65 C is automatically limited the maximum frequency of 5 Hz but the drive...

Страница 11: ...llowing documents ISO 12100 Safety of machinery General principles for design Risk assessment and risk reduction I hereby declare that the equipment above has been designed assembled and tested to com...

Страница 12: ...POWERBOOST byEPSGroup IRL NI powerboost ie info powerboost ie 094 963 3500 IRL 028 9181 8347 NI UK power boost co uk info power boost co uk 01543 415200...