Enphase S-Series Microinverter and Engage Cable Safety 

Important Safety Information 

(S280-60-LL and S230-60-LL) 

This document contains important instructions to use during installation of the Enphase Microinverter™. To reduce the risk of 
electrical shock, and to ensure the safe installation and operation of the Enphase Microinverter System, follow these instruc-
tions. The following safety symbols and information indicate dangerous conditions and important safety instructions.

Product Labels

WARNING:

 Hot surface.

DANGER

: Refer to safety instructions.

DANGER

: Risk of electric shock.

Safety Instructions

General Safety

DANGER

: Before installing or using the Enphase Micro-

inverter, read all instructions and cautionary markings in 
the technical description, on the Enphase Microinverter 
System, and on the photovoltaic (PV) equipment.

DANGER

: Risk of electric shock. Do not use Enphase 

equipment in a manner not specified by the manufac

-

turer. Doing so may cause death or injury to persons, or 
damage to equipment.

DANGER

: Risk of electric shock. Be aware that installa-

tion of this equipment includes risk of electric shock. Do 

not install the AC junction box without first removing AC 

power from the Enphase System. 

DANGER

: Risk of electric shock. The DC conductors 

of this photovoltaic system are ungrounded and may be 
energized.

WARNING

: Risk of electric shock. Always de-energize 

the AC branch circuit before servicing. Never disconnect 
the DC connectors under load. 

WARNING

Risk of electric shock. Risk of fire. Only use 

electrical system components approved for wet locations. 

WARNING

: Risk of electric shock. Risk of fire. Only 

qualified personnel should troubleshoot, install, or re

-

place Enphase Microinverters or the Engage Cable and 
Accessories.

WARNING

: Risk of electric shock. Risk of fire. Ensure 

that all AC and DC wiring is correct and that none of the 
AC or DC wires are pinched or damaged. Ensure that all 
AC junction boxes are properly closed. 

WARNING

: Risk of electric shock. Risk of fire. Do not 

exceed the maximum number of microinverters in an AC 
branch circuit as listed in this guide. You must protect 
each microinverter AC branch circuit with a 20A maxi-
mum breaker.

+

WARNING

: Do not connect Enphase Microinverters 

to the grid or energize the AC circuit(s) until you have 
completed all of the installation procedures and have re-
ceived prior approval from the electrical utility company. 

NOTE

: To ensure optimal reliability and to meet warranty 

requirements, install the Enphase Microinverters and 
Engage Cable according to the instructions in this guide.

NOTE

: Perform all electrical installations in accordance 

with all applicable local electrical codes and the National 
Electrical Code (NEC), ANSI/NFPA 70.

NOTE

: The AC and DC connectors on the cabling are 

rated as a disconnect only when used with an Enphase 
Microinverter.

NOTE

: Protection against lightning and resulting voltage 

surge must be in accordance with local standards. 

NOTE

: Many PV modules have a central stiffening 

brace. In these cases, do 

not

 position the connector 

and microinverter at the exact center of the PV module. 
Instead, position the drop connectors so that the con-

nectors do not conflict with the braces.

NOTE

: Completely install all microinverters and all sys-

tem AC connections prior to installing the PV modules. 

Safety and Advisory Symbols

DANGER

! This indicates a hazardous situation, which if 

not avoided, will result in death or serious injury.

+

WARNING

! This indicates a situation where failure to 

follow instructions may be a safety hazard or cause 
equipment malfunction. Use extreme caution and follow 
instructions carefully.

WARNING

! This indicates a situation where failure to 

follow instructions may result in burn injury. 

NOTE

: This indicates information particularly important 

for optimal system operation. Follow instructions care-
fully.

  S A F E T Y

®

Summary of Contents for Enphase S Series

Page 1: ... is correct and that none of the AC or DC wires are pinched or damaged Ensure that all AC junction boxes are properly closed WARNING Risk of electric shock Risk of fire Do not exceed the maximum number of microinverters in an AC branch circuit as listed in this guide You must protect each microinverter AC branch circuit with a 20A maxi mum breaker WARNING Do not connect Enphase Microinverters to t...

Page 2: ...sk of electric shock Risk of fire Do not leave AC connectors on the Engage Cable uncovered for an extended period If you do not replace the microin verter immediately you must cover any unused connec tor with a sealing cap Sealing caps may not be reused WARNING Risk of electric shock Risk of fire Make sure protective sealing caps have been installed on all unused AC connectors Unused AC connectors...

Page 3: ...oy S Enphase Installer Toolkit mobil app optional but strongly recommended Engage Cable single phase 240 VAC or three phase 208 VAC Cable clips Sealing caps as needed for any unused drops on the Engage Cable Terminators as needed one needed at the end of each AC branch circuit Enphase disconnect tool Other Items Outdoor rated weather proof AC junction box es Gland or strain relief fitting one per ...

Page 4: ...tall the microinverter as shown with the contoured side up Failure to do so could allow the microinverter to come in contact with the PV module back sheet Dress the Cable a Use cable clips or tie wraps to attach the cable to the racking b Dress any excess cabling in loops so that it does not contact the roof Do not form loops smaller than 4 75 inches 12 cm in diameter Keep the drop connector relea...

Page 5: ...and connect the microinverter Listen for two clicks as the connectors engage b Cover any unused connectors with Enphase Sealing Caps Listen for two clicks as the connec tors engage See notes in Step Details c Attach the terminated cable end to the PV racking with a cable clip or tie wrap WARNING Install sealing caps on all unused AC connectors as these become live when the system is energized by t...

Page 6: ...s LED Connect the PV Modules a Mount the PV modules above the microinverters b Connect the DC leads of each PV module to the DC input connectors of the corresponding micro inverter c Check the LED on the side of the microinverter The LED flashes six times at start up All green flashes indicate normal start up This table lists microinverter LED status for normal operation after startup LED Indicate...

Page 7: ...C SHOCK HAZARD THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE UNGROUNDED AND MAY BE ENERGIZED WARNING Allow a minimum of 1 9 cm 0 75 between the roof and the microinverter Also allow 1 3 cm 0 50 between the back of the PV module and the top of the microinverter NOTE Torque the microinverter fasteners to the values shown Do not over torque 1 4 mounting hardware 5 N m 45 50 in lbs 5 16 mounting h...

Page 8: ... to Enphase Click Add a New System at https enlighten enphaseenergy com Use this map to build the virtual array in Enlighten s Array Builder DOCUMENT NUMBER ENPHASEENERGY COM INSTALLATION MAP REVISION 140 00003 04 A B C D E F G H J K L M 1 2 3 4 5 6 7 To Sheet ________ To Sheet ________ To Sheet ________ To Sheet ________ Envoy Serial Label ...