Proximity   

Access Control System 

 

721H5 

 

 

 

 

 

OPERATION MANUAL 

 

 

 

 

 

 

 

 

 

 

 

 

Ver. 3.2 

 

 

 

 

 

 

Date: 07-05-2001 

Summary of Contents for 721H5

Page 1: ...Proximity Access Control System 721H5 OPERATION MANUAL Ver 3 2 Date 07 05 2001 ...

Page 2: ...nal 721L module the 701H5 can be performed as On Line Reader LED Indicators LED Status Description LED GREEN blinking every 1 5 seconds LED GREEN on off moderately LED GREEN blinking every 0 6 seconds LED GREEN on off fast LED GREEN on LED RED on LED RED on off fast LED RED blinking every 0 4 seconds Power on in User Mode normal condition System waits for PIN or Function Code inputs completed The ...

Page 3: ...off mode the delay time is infinite and there will be no alarm activated Arming Idle Time Setting This idle time can provide user an enough time to close the door without entering Alarm Delay Time period Once system enters Alarm Delay Time period the user has to disarm the system to avoid the alarm generated The Arming Idle Time is keypad programmable and can be programmed from 1 600 seconds Defau...

Page 4: ...ent card with address 00000 to the reader and input PIN Code and sign if the card is in Card and PIN Code access mode 2 Press key in 3 seconds PPPPPP 6 digit Password Either way can enter Edit Mode Default setting PPPPPP 123456 or Either way can exit Edit Mode and then in User Mode however will also set the arming 00 NNN Assign a Reader Number 001 254 to itself If NNN 000 or NNN 254 system will as...

Page 5: ...llowed with DEV to activate the Alarm Relay FFFF 0001 9999 Default setting FFFF 1234 18 TTT Arming Idle Time Setting 1 600 seconds TTT 001 600 If TTT 600 system will assign a default setting Default setting TTT 015 19 SSSSS NNNNN Register a number of card s to the system After registered the cardholder can access the system by using Card Only mode Note Cards can not be registered through 721K or 7...

Page 6: ... disable disable enable 144 disable enable enable enable 146 enable enable enable enable 152 disable disable enable enable 154 enable disable enable enable If NNN 255 system will assign a default setting Default setting NNN 024 26 SSSSS EEEEE X Define the proximity cards with addresses starting from SSSSS to EEEEE to have or not to have an anti passback feature For example If enter 26 00005 00008 ...

Page 7: ...Code 1234 Auto Re Lock Disable Power on Arming Disable Door Exit Release Enable Anti passback Disable Hardware Specifications Power Input 10 12 VDC Power Consumption 200mA Door Relay Output COM NC and NO 2A 30VAC 2A 24VDC Alarm Signal Output Transistor output active low 12VDC 100mA Max Tamper Switch Output 1 SPDT 1A 24VAC 1A 24VDC Door Monitor Input C and NC contacted when door closed Door Exit Re...

Page 8: ... 100 mA 12VDC Max YELLOW ORANGE RED CN3 CN2 CN1 TAMPER SWITCH 1A 24VAC 1A 24VDC NC C NO WHITE PURPLE W NC C GND Power To Lock POSITIVE BLUE W WHITE NO C GND LOCK POSITIVE Power To Open GRAY BLUE DAT 1 721K CN2 BLUE DAT 0 721K CN2 GREEN LED G 721K CN2 BROWN LED R 721K CN2 YELLOW 721K CN2 PINK BUZZ BUZZER OUTPUT CN2 CN1 721H5 PCB or 721U BLUE or 721U GREEN or 721U PURPLE or 721U BROWN or 721U YELLOW...

Page 9: ...ED G BROWN YELLOW BUZZER INPUT PINK BUZZ WIEGAND WIRING LED INPUT BUZZER INPUT ABA II OUTPUT CN2 LED G LED R BROWN YELLOW CLOCK DATA BUZZ CARD PRESENT ORANGE PINK N A N A BLUE GREEN ABA II WIRING 1A 24VDC 1A 24VAC TAMPER SWITCH CN3 ORANGE YELLOW NO C RED NC CN3 WG ABA BITS WG ABA BITS WG ABA BITS ABA II WG ABA BITS Wiegand 26 Bits Wiegand 34 Bits ...

Page 10: ...A LED G BUZZ IN BLUE GREEN PURPLE BROWN ABA II WIRING 9 12 VDC GND BLACK RED 721U PCB 34 26 ABA Wiegand 34 BITS ABA 34 26 ABA Wiegand 26 BITS 34 26 ABA 34 26 ABA II GREEN GREEN RS485 B 12VDC RED RS485 TO 701E 704E 716E RS485 A BLUE YELLOW BLACK CONTROLLER RS 232 34 26 ABA BUZZ IN TTL INVERTED SERIAL OUTPUT BUZZ OUT CARD PRESENT BUZZER OUTPUT BUZZER INPUT GRAY PURPLE GREEN WHITE 9 12 VDC LED G TTL ...

Page 11: ...o turn off the alarm which is activating Door opened by using Forced Open and if Forced Open feature Command 28 is disabled In arming situation the system enters A Al la ar rm m D De el la ay y T Ti im me e right away once the door is opened by using Forced Open and if Forced Open feature is disabled The alarm is activated after T Ti im me e P Pe er ri io od d D D User can disarm the system in T T...

Page 12: ... Card E is registered system assigns group 01 and address 00004 to it The system is still in 19 00005 00001 command 12 00001 1234 Assign PIN Code 1234 to Card with address 00001 I E Card B 19 00005 00001 Register Command Individual registration Present Card C Card C was registered before five beep tones are generated to indicate this error The system is still in 19 00005 00001 command 19 00005 000...

Page 13: ...ds PIN Code has to be entered in 3 seconds after present card 123456 PASSWORD ERROR New password is 654321 Error count is 1 123456 PASSWORD ERROR New password is 654321 Error count is 2 Invalid Card Present Invalid card present error count reset to 1 Present Card A Valid card present error count reset to 0 123456 PASSWORD ERROR New password is 654321 Error count is 1 123456 Wrong password Error co...

Page 14: ...unction Code present Card J 9999 5555 There are 3 seconds timeout between present valid card and Function Code between PIN Code and Function Code i e User has 3 seconds to start inputting the Function Code There are 5 seconds timeout between valid address and PIN Code between present valid card and PIN Code between each key pressed i e User has 5 seconds to start inputting the PIN Code If last pre...

Page 15: ...ign a PIN Code PPPP to an individual card with address SSSSS After assigned the cardholder can access the system by using Card or PIN Code mode 13 SSSSS PPPP Assign a PIN Code PPPP to an individual card with address SSSSS After assigned the cardholder can access the system by using Card and PIN Code mode 17 FFFF Assign 4 digit Function Code FFFF 18 TTT Arming Idle Time Setting 1 600 seconds 19 SSS...

Page 16: ...rd 5 digits in the left called Site Code and 5 digits in the right called Card Code System can accept only the Card Code in the range from 00001 to 65200 cards with continuous codes is required 721H7 The 721H7 is a self contained and non tracking standalone Proximity Door Access Elevator Control Reader It supports up to 1000 cardholders for Door Access Control and 630 cardholders for Elevator Cont...

Page 17: ...ee access modes Card and PIN Code or Card or PIN Code or Card Only There is a 10 digit number in each card 5 digits in the left called Site Code and 5 digits in the right called Card Code 721H5 721L On Line Proximity Reader The 721H5 721L On Line Proximity Reader is for Networking Proximity Access Control System The networking system with maximum 5000 cardholders can connect up to 254 any combinat...

Page 18: ...tall outside or 721U install inside secured area CASE 4 721H5 secured area install outside CASE 3 721H5 721L to 701E 704E 716E Controller RS485 to 701E 704E 716E Controller 721L RS485 wire connection wire connection wire connection 721K or 721U install outside unsecured area READER READER READER READER READ HEAD READ HEAD ON LINE MODULE ON LINE MODULE ...

Page 19: ...ill be on if gray wire buzz output and purple wire are connected and card is presented 721U LED G LED R will be on if white wire card present and brown wire yellow wire is connected and card is presented 1N4148 Two 1N4148s have to be added to 721U side if there are more than two read heads are connected to 721H Reader For example NOTE If 1x721K 1x721U are connected then 2 1N4148s added to 721U sid...