background image

Introduction

This installation guide provides instructions for installation, 

startup and adjustment. To receive a copy of the instruction 

manual, contact your local Sales Office or view a copy 

at www.fisher.com. For further information refer to: 

CSB600 Series Commercial / Industrial Pressure Reducing 

Regulators Instruction Manual, D103130X012.

PED Categories

This product may be used as a pressure accessory with 

pressure equipment in the following Pressure Equipment 

Directive. For information on the current PED revision see 

Bulletin: 

D103053X012

. Pressure regulator does not require 

any supplementary upstream safety accessory for protection 

against overpressure compared with its design pressure 

PS, when upstream reducing station is sized for a max 

downstream incidental MIPd <= 1.1 PS.

tyPE

DEsCrIPtIon

PED CatEgory

FluID grouP

CSB600, CSB600F, 

CSB620, CSB620F 

and CSB650

Base regulator

I

Groups 1 and 

2 according to 

PED 2014/68/EU 

1st and 2nd family 

gas according to 

EN 437 or other 

gases (compressed 

air, Nitrogen). The 

gas must be non-

corrosive, clean 

(filtration on inlet side 

necessary) and dry.

CSB604, CSB604F, 

CSB624, CSB624F 

and CSB654

Regulator with 

slam shut

IV

European En reference standards

EN 334 and  

EN 14382

specifications

available Configurations

See Table 1

regulator type

Differential Strength (DS)

accuracy Class

Up to AC5 (depending on Outlet Pressure)

lockup Class

Up to SG10 (depending on Outlet Pressure)

Failure Mode per En334

Fail Open (FO)

Integral strength (Is) Pressure rating

(1)

See Table 2

Differential strength (Ds) Pressure ratings

(1)

See Table 3

Body sizes, Materials, End Connections and  

Pressure ratings

(1)

See Table 4

operating Pressure range

(1)

regulator: 

See Table 5

slam-shut Module: 

See Tables 7a, 7b, 7c and 7d

Maximum outlet Pressure

(1)

Emergency Casing:

 

Type CSB600/CSB600F/CSB620/CSB620F:

 

4.0 bar / 58.0 psig

Type CSB650:

 5.0 bar / 72.5 psig

to avoid Internal Metallic Parts Damage:

Type CSB600/CSB600F/CSB620/CSB620F:

  

0.34 bar / 5.0 psig over set pressure

Type CSB650:

 1.5 bar / 21.8 psig – not to exceed 

maximum emergency outlet

operating Casing:

Types CSB600 and CSB620:

 1.1 bar / 16.2 psig

Type CSB650:

 5.0 bar / 72.5 psig

outlet Pressure ranges

(1)

9.0 mbar to 4.0 bar / 0.13 to 58.0 psig

See Table 5

orifice size

25 mm / 1.0 in.

Pressure registration

External

temperature Capabilities

(1)(2)(3)

according to PED standards:

 

-20 to 66°C / -4 to 151°F

non-PED:

  

-30 to 66°C / -22 to 151°F

spring Case Vent Connection

1 nPt:

 Types CSB600 and CSB620

1/2 nPt:

 Type CSB650

type VsX8 slam-shut Device Maximum Inlet 

Pressure (P

umax

)

(1)

:

Differential strength (Ds):

 16 bar / 232 psig

Integral strength (Is):

 6.0 bar / 87 psig

approximate Weights

with threaded body

Type CSB600/CSB620:

 13 kg / 29 lbs

Type CSB650:

 14 kg / 31 lbs

Type CSB604/CSB624:

 14 kg / 31 lbs

Type CSB654:

 15 kg / 33 lbs

with Flanged body

Add 5.2 kg / 11 lbs to weights listed

Designed, tested and Evaluated Consistent With:

ANSI B16, ASME BPVC Sec. VIII Div. I, ASTM B117 
(Corrosion Resistance), EN 334 and EN 14382

Directive atEX Information

See Table 6
For information about ATEX, refer to CSB600 Series
(D103130X012) and VSX8 Series
(D103127X012) Instruction Manuals.

1. The pressure/temperature limits in this Installation Guide or any applicable standard limitation should not be exceeded.

2. Standard token relief set values listed in Tables 7a, 7b, 7c and 7d are based on -20 to 60°C / -4 to 140°F.

3. Product has passed Emerson Process Management Regulator Technologies, Inc. (Emerson) testing for lockup, relief start-to-discharge and reseal down to -40°.

CSB600 Series

Installation Guide

D103130X014

English ‒ October 2018

Summary of Contents for CSB600 Series

Page 1: ...Regulator See Table 5 Slam Shut Module See Tables 7a 7b 7c and 7d Maximum Outlet Pressure 1 Emergency Casing Type CSB600 CSB600F CSB620 CSB620F 4 0 bar 58 0 psig Type CSB650 5 0 bar 72 5 psig To Avoid Internal Metallic Parts Damage Type CSB600 CSB600F CSB620 CSB620F 0 34 bar 5 0 psig over set pressure Type CSB650 1 5 bar 21 8 psig not to exceed maximum emergency outlet Operating Casing Types CSB60...

Page 2: ...imits in this Installation Guide and any applicable standard or code limitation should not be exceeded TYPE NUMBER OPTION C S B 6 PRESSURE CONSTRUCTION 0 Low Pressure Applications Outlet Pressure 9 0 to 110 mbar 3 6 in w c to 1 6 psig 2 2 Medium Pressure Applications Outlet Pressure 61 to 780 mbar 0 9 to 11 3 psig 2 5 High Pressure Applications Outlet Pressure 0 70 to 4 0 bar 10 2 to 58 0 psig 2 O...

Page 3: ... ERSA03656A0 Dark Green 4 88 0 192 224 8 82 CSB620 and CSB624 61 to 110 0 9 to 1 6 ERSA03656A0 Dark Green 4 88 0 192 224 8 82 105 to 220 1 5 to 3 2 ERSA03657A0 Blue 5 94 0 234 217 8 54 210 to 380 3 1 to 5 5 GG06247X012 Black 8 00 0 315 206 8 11 320 to 570 4 6 to 8 3 ERSA01582A0 Red with White Stripe 8 71 0 343 177 6 97 510 to 780 7 4 to 11 3 ERSA05055A0 Blue with White Stripe 10 0 0 394 181 7 13 C...

Page 4: ...1 3400 4000 3100 to 4000 4400 Grey areas indicate that token relief is not available above 500 mbar setpoint 1 Max OPSO setpoint truncated to reflect maximum outlet pressure for spring range Table 7a North American Overpressure Shut off OPSO Only Ranges REGULATOR SLAM SHUT DEVICE Type Typical Setpoint Spring Range Type Maximum Operating Inlet Token Relief Set Relief Range Shown as a of Regulator S...

Page 5: ...75 835 to 1120 1 1050 CSB624F 300 270 to 325 VSX8L 8 6 bar 100 to 500 179 to 386 200 379 to 586 400 CSB654 GrDF 1 bar 0 7 to 1 19 bar VSX8L 16 bar 100 to 500 460 to 932 750 1210 to 1682 1210 CSB654 1 bar 0 7 to 1 19 bar 100 to 500 460 to 932 500 960 to 1432 1320 1 2 bar 1 05 to 2 7 bar VSX8H 16 bar 500 to 2000 1050 to 1570 600 1650 to 2170 1650 1 5 bar 750 1800 to 2320 1900 2 bar 1250 to 2300 1000...

Page 6: ...stallation Warning Failure to install a downstream control line could result in a hazardous condition Install downstream control line s to the slam shut device when construction uses external pressure registration The regulator and slam shut device will not control pressure or shutoff if a downstream control line is not installed on those constructions where external pressure registration is requi...

Page 7: ...600 Series regulators have a 1 NPT screened vent opening in the spring case If necessary to vent escaping gas away from the regulator install a remote vent line in the spring case tapping Vent piping should be as short and direct as possible with a minimum number of bends and elbows The remote vent line should have the largest practical diameter Vent piping on regulators with token relief must be ...

Page 8: ...c plated steel with token relief 45 Screw Zinc plated steel without token relief 46 Token Relief Nut 1 required Steel 50 Pusher Post Aluminum 51 Relief Valve Seat Aluminum 52 Pusher Post O ring Nitrile NBR 53 Pin Stainless steel 54 Roller Pin Brass 55 Diaphragm Assembly 60 Closing Cap Aluminum 61 Bonnet Zinc plated steel 62 O ring Nitrile NBR 63 Upper Spring Seat Zinc plated Carbon steel 64 Adjust...

Page 9: ...ent Pointed Downward and with a Type 289H Relief Valve for High Capacity Relief Protect vent pipe with rain cap CSB600 SERIES regulator DN 50 nps 2 Type 289H relief valve Figure 2 CSB600 Series Regulator Vent Line Installation 1 NPT 3 4 G CSB600 Series 9 ...

Page 10: ...N m 50 TO 60 IN LBS 111F 112 111B 111E 111F 111G 111A 111G 111C 111A 55 43 51 44 53 54 10 14 13 11 17 18 L2 52 L2 19 L2 75 L2 77 TORQUE 3 5 TO 4 N m 31 TO 35 IN LBS 50 76 74 68 L2 L2 100 L1 L1 L1 38 L1 60 S 72 L1 65 L2 62 46 42 41 40 106 36 20 L2 21 L2 TORQUE 34 TO 47 N m 25 TO 35 FT LBS 25 L2 82 8 6 TORQUE 1 7 TO 3 4 N m 15 TO 30 IN LBS 111D 95 80 70 TORQUE 6 TO 8 N m 4 TO 6 FT LBS 71 TORQUE 14 T...

Page 11: ... 10 TO 13 FT LBS 71 70 TORQUE 6 TO 8 N m 4 TO 6 FT LBS 80 15 INITIAL TORQUE 7 TO 9 N m 5 TO 7 FT LBS MINIMUM RELAXATION TORQUE 5 N m 4 FT LBS 64 66 63 40 51 36 TORQUE 3 5 TO 4 N m 31 TO 35 IN LBS 14 112 13 11 76 74 53 68 10 18 96 L2 19 L2 75 L2 77 L2 82 L1 61 L1 L1 111B 105 114 111D 111C 111E 1 9 55 43 50 52 L2 L2 54 L2 TORQUE 34 TO 47 N m 25 TO 35 FT LBS 25 TORQUE 6 TO 7 N m 50 TO 60 IN LBS 45 TO...

Page 12: ...051 419 0611 Asia Pacific Singapore 128461 Singapore T 65 6777 8211 Middle East and Africa Dubai United Arab Emirates T 971 4 811 8100 D103130X014 2017 2018 Emerson Process Management Regulator Technologies Inc All rights reserved 10 18 The Emerson logo is a trademark and service mark of Emerson Electric Co All other marks are the property of their prospective owners Fisher is a mark owned by Fish...