Ethernet Switch Quantity I/O controller

E830-DIO(ETH-2A)

Summary of Contents for E830 Series

Page 1: ...Ethernet Switch Quantity I O controller E830 DIO ETH 2A ...

Page 2: ...t mask gateway 8 3 2 DNS Server Address 10 4 Socket Features 11 4 1 TCP Server 11 4 2 TCP Client 12 4 3 UDP Server 13 5 Special Function 14 5 1 Short connection 14 5 2 Registration package mechanism 14 5 3 Heartbeat mechanism 15 5 4 Overtime restart 15 5 5 TCP Multi Connection Function 15 6 Register Configuration Table 16 6 1 ModBus address table 16 7 Instruction format 17 7 1 03 read single regis...

Page 3: ...al fields Features wide operating temperature range This product can work in 40 C 85 C adapting to a variety of harsh working environment It s a real industrial grade products Power Supply Design Power polarity protection over connection protection increased reliability 8 28V DC ModBus protocol using ModBus protocol Q A mode of communication simple cheap versatile easy to use communication design ...

Page 4: ...an 28V or module will be destroyed 7 Working current 40mA 24V 40mA in normal status 54mA in data transmitting 8 Device address 0 248 0 248 are configurable default is 1 9 Working temperature 40 85 Industrial grade 10 Isolation protection 4000V DC Lightning strike and surge protection 1 1 E830 Series Model No Size Interfac e Signal type Input channel Output channel Protection level V DC E830 DIO 48...

Page 5: ...nt 2 Input voltage DC not AC DC voltage is between 8 28V Under 8V device won t work beyond 28V device will be damaged 3 Input channel 2 channel digital isolated input DC input voltage difference should be 6 28V 4 Waterproof It is not water proof keep it away from water or permanent damage will be caused 5 Write register Registers 4004 and 4005 are reserved registers and cannot be written After a w...

Page 6: ...Chengdu Ebyte Electronic Technology Co Ltd E830 DIO ETH 2A User Manual Copyright 2012 2019 Chengdu Ebyte Electronic Technology Co Ltd 5 2 Functional description 2 1 Pin definition ...

Page 7: ...output channel 2 indicator It s blue when input has signal it s green when output has signal It s light blue when both has signals DIO1 digital input output channel 1 indicator It s blue when input has signal it s green when output has signal It s light blue when both has signals PWR Power indication It shows red light when power working normally DI2 digital input channel 2 Digital acquisition opt...

Page 8: ...Chengdu Ebyte Electronic Technology Co Ltd E830 DIO ETH 2A User Manual Copyright 2012 2019 Chengdu Ebyte Electronic Technology Co Ltd 7 2 2 2 Connection method for output channel ...

Page 9: ...eway host dynamics so as to avoid the tedious steps of setting up the IP address It s suitable for those scenes that no any requirement for IP and do not force IP to correspond with the module one by one Advantages Access routers and other devices with DHCP Server can communicate directly Disadvantages Access the network without DHCP Serve such as the direct connection with computer E830 DIO ETH 2...

Page 10: ...ngdu Ebyte Electronic Technology Co Ltd E830 DIO ETH 2A User Manual Copyright 2012 2019 Chengdu Ebyte Electronic Technology Co Ltd 9 Figure 1 parameter setting software Figure 2 parameter setting interface ...

Page 11: ...an be resolved when the local domain name server is not perfect Users can also set specific DNS server addresses as required When the E830 DIO ETH 2A needs domain name resolution it will submit a resolution request to the set DNS server The usage is more flexible and reliable In Static IP mode the default DNS host address is 61 139 2 69 and the standby DNS server address is 192 168 4 1 In DHCP mod...

Page 12: ... 4 Socket Features The socket working mode of E830 DIO ETH 2A has TCP Client TCP Server UDP Server which can be set up by the host computer software E830 DIO ETH 2A cannot set up as UDP Client It s because the modbus protocol is a master slave mode response The setting interface is as follows Figure 4 1 Settings interface 4 1 TCP Server ...

Page 13: ...a TCP Server it can accept 6 Client connections at most the local port number is a fixed value and cannot be set to 0 4 2 TCP Client Figure 4 3 TCP Client 1 TCP Client provides client connections for TCP network services Initiatively initiates connection requests to the server and establishes connection to realize the interaction between serial data and server data According to the relevant provis...

Page 14: ...ess is not verified on the basis of normal UDP After each UDP packet is received the target IP is changed to data source IP and port number The IP and port number that was sent to the most recent communication when sending data 2 This mode is usually used for data transmission scenarios where multiple network devices need to communicate with the module and do not want to use TCP due to the high sp...

Page 15: ...by default and the disconnection time can be set after the function is opened The setting range is 2 255S 5 2 Registration package mechanism In transparent transmission mode the user can choose to make the module send a registration package to the server The registration package is designed to enable the server to identify the data source device or to access the password for the server function E8...

Page 16: ...tion where the server sends a fixed query to the device to reduce traffic flow the user can choose to send a heartbeat packet query command to the serial device instead of sending a query from the server The user defined packet defaults to hexadecimal data ASCII code optional and the E830 DIO ETH 2A module supports up to 40 bytes of custom heartbeat packet content 5 4 Overtime restart Overtime res...

Page 17: ...on 10001 DI1 1 Read only 0 1 The status of digital output is 1 10002 DI2 1 Read only 0 1 The status of digital output is 2 3 Hold register description Hold register Function code 0x03H 0x06H Address Parameters Length Read Write Min value Max value description 40001 D I 1 8 2 Read only 0 0xff Reading the status of eight digital inputs 40002 DO 1 8 2 Read Write 0 0xff Reading and writing the status ...

Page 18: ...owing values 01 03 02 00 00 B8 44 Modbus address of device Read command Read the returning bytes DI value see more details in maintain registers CRC check code 7 2 06 Write a register command Use the 06 command to write a register value such as writing a 40002 port output register 01 06 00 01 00 01 58 75 ModBus address of device Write command Write registers address Write register s value CRC chec...

Page 19: ...tate the use of serial port tools to debug E830 DIO ETH 2A our company will provide CRC16 calculator which will automatically add CRC16 check code after input data 8 2 Network Configuration Host Computer If users forget the device parameters press the reset button 5S 10S to reset the device configuration parameters After reset users need to reconfigure the network parameters and modbus register pa...

Page 20: ...tecting the environment to reduce the use of paper we only provide electronic documents of the English manual if necessary please go to our official website to download 10 Revision history About Us CDEBYTE after sales technical support support cdebyte com For file download and more product information please visit www cdebyte com en Thank you for using the CDEBYTE products Any questions or suggest...