Simatic S7 PG router 

 

 

 

 

Summary of Contents for Simatic S7 PG

Page 1: ...User Manual 12 2010 MN04802060Z EN replaces M000902 03 10 2009 Simatic S7 PG router ...

Page 2: ...send an E Mail to automation eaton com Original instructions The German version of this document is the original instructions Editor Al Brand and product names All brand and product names are trademarks or registered trademarks of the owner concerned Copyright Eaton Automation AG CH 9008 St Gallen All rights reserved also for the translation None of this document may be reproduced or processed dup...

Page 3: ...o warranty claims will be recognised for faults arising from the improper handling of devices and modules The devices even by means of communication should not be used for the implementation of any safety functions relating to the protection of personnel and machinery No liability is accepted for claims for damages arising from a failure or functional defect in the device All data specified in thi...

Page 4: ...allation on the Programming PC 6 2 Operating principle 10 3 Creating a Network 11 4 SIMATIC Manager Settings 12 4 1 Adding a Router 13 4 2 Configuring the Network 15 5 MICRO PANEL Settings 19 6 Galileo Settings 21 6 1 Priority of the MPI Parameters 21 7 Special Features 22 7 1 Restrictions 22 7 2 Limitations 22 8 Error Messages 23 9 Command Line Reference 24 9 1 Parameters 24 9 2 Examples 24 ...

Page 5: ...t be available on the device Temporary use The product cannot be used simultaneously with the GRS or when GRS is started with limited runtime 1 1 SCOPE OF DELIVERY Description S7 PG Router software incl electronic documentation License product LIC OPT 2ND_LEVEL Note If you have any questions on license products please contact your local MICRO PANEL sales distributor 1 2 SYSTEM REQUIREMENTS 1 2 1 P...

Page 6: ... PG Router Setup Wizard will be launched automatically once the installation CD is inserted in the CD drive If the Setup Wizard does not launch automatically run the file S7PGRouter exe on the installation CD Select the desired language from the drop down menu Click OK Confirm the subsequent dialog by clicking Next ...

Page 7: ...on com 7 Important installation information appears Confirm the subsequent dialog by clicking Next The following dialog will ask you to select an installation directory The selected directory must contain a Galileo installation Confirm the dialog by clicking Next ...

Page 8: ...8 Simatic S7 PG router 12 2010 MN04802060Z EN www eaton com Select the directory in which the program shortcut will be created Confirm the dialog by clicking Next Confirm the subsequent dialog by clicking Install ...

Page 9: ...1 General Simatic S7 PG router 12 2010 MN04802060Z EN www eaton com 9 The next dialog indicates that the installation was successfully completed Confirm by clicking Finish ...

Page 10: ...e than one PG connection via a MICRO PANEL The S7 Routing function can also be used if a started GALILEO project is communicating with the controller at the same time Note The S7 Routing function is only supported by MICRO PANELs with an onboard MPI interface and a WinCE operating system from version 2 12 or higher Refer to your MICRO PANEL user manual for further information on connection commiss...

Page 11: ... shown are only given as examples It is essential that every device has a unique and unambiguous IP and MPI address The following software should already be installed and users should be familiar with their operation Siemens Step 7 PLC programming software GALILEO HMI programming software The following documentation provides more useful information on creating networks System Description Networks ...

Page 12: ...e of the following versions of the SIMATIC Manager is required in order to use the S7 PG Router software a Step7 V5 2 Net driver b Step7 V5 3 Note All the following screenshots shown and the instructions given apply to Step7 V5 3 First load the S7 project in the SIMATIC Manager In our example this is a project for an S7 312IFM ...

Page 13: ... is simply a representative of the MICRO PANEL in the Step7 project Specify the Router further by selecting any S7 CPU type with an integrated Ethernet interface In our example this is a CPU 317 2 PN DP Note The S7 Routing function of the MICRO PANEL is similar to the Routing function of S7 controllers Refer to the SIMATIC Manager documentation for further information on routing in conjunction wit...

Page 14: ... 12 2010 MN04802060Z EN www eaton com Now move to the hardware settings tab of the Router and add an S7 CPU with an Ethernet interface In the Properties dialog enter the IP address set on the MICRO PANEL Router Connect the CPU with the Ethernet subnet ...

Page 15: ...RK Save the new hardware configuration once you have added the Router and then move to the Network Configuration screen The network configuration will now show you the Router MICRO PANEL represented by an S7 station next to the actual S7 station Add an additional network object of the type PG PC Configure network ...

Page 16: ...4 SIMATIC Manager Settings 16 Simatic S7 PG router 12 2010 MN04802060Z EN www eaton com Now define a free MPI address for the Router and select the MPI subnet ...

Page 17: ...0Z EN www eaton com 17 For the PG PC connection enter the IP address of the PC on which SIMATIC Manager is running and select under Subnet the already configured Ethernet connection Under Assigned on the Assignment tab select TCP IP Auto and activate S7ONLINE Access ...

Page 18: ...MN04802060Z EN www eaton com The Ethernet connection on the PG PC highlighted in yellow indicates that the Routing function is active In our example the S7 station MPI address 2 can now be programmed via the MICRO PANEL MPI address 31 192 168 6 11 192 168 6 10 ...

Page 19: ...ject In our example this is 192 168 6 10 Now start the S7 PG Router software S7ROUTE EXE on the MICRO PANEL Note Refer to the Windows CE operating system documentation for further information on IP address setting transferring and starting programs Modify the Baud rate SA MPI address of MICRO PANEL and HSA parameters according to the settings you have predefined for the Router station in the SIMAT...

Page 20: ...om You can also provide these settings as command line parameters as described in chapter 9 The router connection is now fully configured and you can now access the connected S7 controller When the PG connection is active this is indicated by the S7 PG Router as shown in the figure ...

Page 21: ... OF THE MPI PARAMETERS The MPI interface can be used by several applications at the same time The following basic principles must be observed in order to prevent conflicts when the interface is initialised Î If the interface is already initialised the existing initialisation has priority The MPI interface is initialised when the S7 PG Router is started or when GRS is started If the S7 PG Router is...

Page 22: ...owing PG functions are not supported by the Router Î Who is Online poll of all active MPI stations 7 2 LIMITATIONS The general limitations of the S7 CPU with regard to the number of simultaneous MPI and PG connections apply S7 PG Router has no limitations regarding the number of connections that can be routed simultaneously ...

Page 23: ...ss on the Router is incorrect Use the same HSA for all MPI stations MPI baud rate The wrong baud rate 187 5 Kbit or 1500 Kbit was set on the Router PG conflict A PG connection via MPI to the S7 CPU already exists GRS Apart from the general errors relating to communication with S7 controllers the following conflict may also occur Error Cause MPI address definition The Router was started before GRS ...

Page 24: ...0000 sa Station address 0 to hsa hsa Highest station address 15 31 63 126 close Closes an already running S7 PG Router 9 2 EXAMPLES s7route exe will start S7 PG Router and ask the user for the actual MPI parameters s7route exe BR 187500 sa 31 hsa 31 will start S7 PG Router with MPI 187 5 kBit as station 31 where the highest station address is also 31 s7route exe close will close an already running...