background image

 

 
 
 
 
 
 
 
 
 
 

 
 
 

 

 

BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION! 

FOLLOW NATIONAL, STATE AND LOCAL CODES. 

READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION.

  

 
The ECIO-xxx-DN or ECOM-DN Module are convenient and cost-effective DeviceNet interfaces 
capable of providing discrete control and monitoring of motor starters, drives, and other devices over 
a DeviceNet network. The ECIO-xxx-DN or ECOM-DN is designed to provide the following benefits in 
both new and existing installations: 

 

reduced field wiring 

 

greater operator efficiency 

 

ease in system startup and commissioning 

The ECIO-xxx-DN, DeviceNet I/O Module provides four (4) inputs and two (2) AC/DC rated relay 
outputs. It can be DIN rail mounted, or mounted directly to a back panel. The ECIO-xxx-DN or 
ECOM-DN compact size, ease of wiring and DeviceNet communications capability makes the use of 
traditional discrete devices on DeviceNet cost-effective and simple. The ECIO-xxx-DN or ECOM-DN 
Module are compatible with Cutler-Hammer’s Model E777 overload relay. It simply connects to the 
side of the E777 and, in addition to the extended I/O functions (ECIO-xxx-DN), permits remote 
monitoring and control of the E777 over a DeviceNet network. An additional remote reset input is 
available on the ECIO-xxx-DN or ECOM-DN to reset a connected E777. 

 
CONNECTIONS 

 
1. Mount the ECIO-xxx-DN or ECOM-DN in a convenient location in a properly rated enclosure. 

ECIO-xxx-DN can be mounted to a back panel using screws or can be snapped onto DIN rail. 

 
2. Connect the five DeviceNet wires to the 5-pin connector on the front of the ECIO-xxx-DN or 

ECOM-DN Module. 24VDC should be connected to V+ and V-. Connect the other three wires to 
CAN High, CAN Low and Shield. 

 
3. 

ECIO-DN and ECIO-120-DN Connections

 

NOTE: ECIO-DN inputs are dry contact inputs only, and ECIO-120-DN input require AC 
voltage. 

 

ECIO-DN inputs

  

 
Connect one side of each input contact to V+ and connect the other side to I1, I2, I3, or I4. The 
ECIO-DN must see the V+ voltage to indicate the input is closed. 

 

ECIO-120-DN inputs 

 

Connect L1 of an AC source to C (AC common) connect L2 of an AC source to each input contact, 
Connect the other side of each input contact to I1, I2, I3, or I4. The ECIO-120-DN must see AC 
voltage to indicate the input is closed. 

 

4. The MNS LED indicates communication is established between the ECIO-xxx-DN and the 

DeviceNet master, and OLC indicates communication is established with the E777 overload (if 
installed). 

 

5. 

OUTPUT A, OUTPUT B and the REMOTE RESET connections are made to the top green 

connector of the ECIO-xxx-DN Module.

 

 

  

 

INSTALLATION INSTRUCTIONS FOR  

MODEL ECIO-DN, ECIO-120-DN, ECOM-DN  

 I/O MODULES 

Reviews: