European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                            www.e-2-s.com              Fax: +44 (0)208 740 4200 
Document No.D210-00-601-IS 

Issue 2        24-08-16                         Sheet 1 of 8

 

                                                           

INSTRUCTION MANUAL (ATEX / IECEx) 

BExCS110-05D-P and BExCS110-05D-R-P Combined Sounder 

/ Beacon For use in Flammable Gas and Dust Atmospheres

 

 

 

 

 

 

 

1) Warnings 

 DO NOT OPEN WHEN AN EXPLOSIVE 

ATMOSPHERE IS PRESENT 

 DO NOT OPEN WHEN ENERGIZED 

 POTENTIAL ELECTROSTATIC CHARGING 

HAZARD 

 COVER BOLTS CLASS A4-80 

 USE HEAT RESISTING CABLES AND CABLE 

GLANDS (RATED 110°C) AT AMB. 
TEMPERATURES OVER 40°C 

 

2)  Rating & Marking Information 

 

All units have a rating label, which carries the following 
important information:- 

 

Model No.:

  

BExCS110-05D-P or BExCS110-05D-R-P 

 

Input Voltage:

     DC Units    12V or 24V or 48V 

              AC Units    115V or 230V 

 

BExCS110-05D-P or BExCS110-05D-R-P Codes:  

Ex d IIB T5 Gb Ta. -50°C to +40°C 
Ex d IIB T4 Gb Ta. -50°C to +70°C 
Ex tb IIIC T110°C Db Ta. -50°C to +55°C 
Ex tb IIIC T125°C Db Ta. -50°C to +70°C 

 

Certificate No.

    KEMA 01ATEX2223X 

  IECEx 

KEM 

10.0025X 

 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

The units can be installed in locations with the following 
conditions: 

 

Area Classification Gas: 

Zone 1 

Explosive gas air mixture likely to occur in 
normal operation. 

Zone 2 

Explosive gas atmosphere not likely to 
occur in normal operation but may be 
present for short periods. 

 

Gas Groupings: 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC 

Hydrogen and Acetylene 

 

Temperature Classification: 

T1 450ºC 

 

T2 300ºC 
T3 200ºC 
T4 135ºC 
T5 

100ºC (up to 40

°C

 ambient) 

 

Area Classification Dust: 

Zone 21 

Explosive dust air mixture likely to occur in 
normal operation. 

Zone 22 

Explosive dust air mixture not likely to 
occur in normal operation, and if it does, it 
will only exist for a short time. 

 

Dust Groupings: 

Group IIIA 

Combustible Dusts 

Group IIIB 

Non-Conductive Dust 

Group IIIC 

Conductive Dust 

 

Maximum Surface Temperature for Dust Applications: 

110ºC at +55 ºC ambient 

125 ºC at +70 ºC ambient 

 

IP Rating:  

IP66/67 to EN/IEC60529 and IP6X to 
EN/IEC60079-0, EN/IEC60079-31 

 

Equipment Category:

 

2G / 2D 

 

Equipment Protection Level:

 

Gb / Db 

 

Ambient Temperature Range:

 

-50°C to +70°C Gas Groups IIA and IIB 

-50°C to +70°C Dust Groups IIIA, IIIB and IIIC 

0518 

II  2G 
II  2D 

Epsilon x 
Equipment Group and 
Category: 

CE Marking 
Notified Body No. 

BExCS110-05D-P 

BExCS110-05D-R-P 

Summary of Contents for BExCS110-05D-PDC012

Page 1: ...Ta 50 C to 70 C Certificate No KEMA 01ATEX2223X IECEx KEM 10 0025X The units can be installed in locations with the following conditions Area Classification Gas Zone 1 Explosive gas air mixture likely...

Page 2: ...cation of the combined sounder beacon should be made with due regard to the area over which the warning signal must be visible They should only be fixed to services that can carry the weight of the un...

Page 3: ...r beacon range can be supplied with the following types of adapters M20 to NPT M20 to NPT M20 to M25 It is important to note that stopping plugs cannot be fitted onto adapters only directly onto the M...

Page 4: ...2 1 Wiring Diagrams Fig 3a BExCS110 05D AC Simplified Block Diagram for simultaneous operation Fig 3b BExCS110 05D AC Simplified Block Diagram for independent operation 12 2 Sounder Stage Switching 12...

Page 5: ...he S3 terminal Dip switch alters stage 3 tone For units set up for ve switching refer to 13 3 Stage two S2 Operation Power ve and ve link a ve supply line to the S2 terminal Dip switch alters stage 2...

Page 6: ...it should be used to link the supply from the interconnecting terminals on the beacon board down to the supply terminals on the sounder board 15 Settings 15 1 Tone Selection The sounders have 32 diffe...

Page 7: ...Cover and Guard Fixtures 17 Maintenance Overhaul Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current rele...

Page 8: ...1 0 Tone 31 Tone 1 12 Alternating 800 1000Hz at 0 875Hz 1 1 0 1 0 Tone 4 Tone 5 13 Intermittent 2400Hz at 1Hz 0 0 1 1 0 Tone 15 Tone 5 14 Intermittent 800Hz 0 25s on 1s off 1 0 1 1 0 Tone 4 Tone 5 15...