INSTRUCTION MANUAL (ATEX / IECEx) 

BExBGL1D Flameproof LED Beacon

 

For use in Flammable Gas and Dust Atmospheres

 

 

1)  Introduction 

 
The  BExBGL1D  is  a  flameproof  LED  beacon  which  is 

certified to meet the ATEX directive 94/9/EC and the IECEx 
scheme.  The  beacon  produces  visual  warning  signals  and 

can be used in hazardous areas where potentially flammable 
gas and dust atmospheres may be present. The BExBGL1D 

LED  beacon  has  nine  different  flash  patterns  including  a 
steady  ON  state  and  can  also  be  remotely  switched  to  a 

second  and  third  flash  pattern.  The  beacon  can  be  used  in 
Zone 1 and Zone 2 areas with gases in groups IIA, IIB and 
IIC and Temperature Classifications of T1, T2, T3, and T4. It 

can  also  be  used  in  a  temperature  classification  T5,  if  the 
upper  ambient  temperature  is  restricted  to  +40ºC.  The  unit 

can be used in Zone 21 and Zone 22 areas for combustible 
dusts  and  has  an  IP  rating  of  IP  67  and  a  surface 

temperature rating of T120ºC or T105ºC if the upper ambient 
temperature  is  restricted  to  +55ºC  and  T95ºC  if  the  upper 
ambient temperature is restricted to +40ºC. 

 

2)  Marking 

 

All  units  have  a  rating  label,  which  carries  the  following 
important information:- 

 
Unit Type No.    

BExBGL1D

 

 

Input Voltage:    DC Units    10-50V 

            AC Units    10-35V or 230V or 115V 

 
Codes:    

Ex d IIC T4 for Ta –50ºC to +70ºC 

 

Ex d IIC T5 for Ta –50ºC to +40ºC

 

Ex tD A21 T120ºC based on max. Ta of +70ºC 

 

Certificate No’s

     

KEMA 00ATEX2006 
IECEx KEM 10.0002 

 

        

 

 

 

 

 
 

Warnings:        

DO NOT OPEN WHEN AN EXPLOSIVE                        

 

        GAS OR DUST ATMOSPHERE IS PRESENT 

 

      COVER BOLTS CLASS A4-80 

 
 

 USE HEAT RESISTING CABLES AND CABLE GLANDS 

  

(Rated 110ºC) AT AMB. TEMPERATURES OVER 40ºC 

 

Year of Construction /  
Serial No.       

 

 i.e.  10 / 1DB73000001 

 

3)  Type Approval Standards

 

The beacon has EC Type Examination and IECEx certificates 
issued  by  KEMA  and  have  been  approved  to  the  following 

standards:- 

 

EN60079-0:2006   IEC60079-0:2004 (Ed4)

      

General Requirements

 

EN60079-1:2007   IEC60079-1:2007

 

(Ed6)

        Flameproof Enclosure ‘d’ 

 
EN61241-0:2006   IEC61241-0:2004 (Ed1)       Dust General 

          Requirements 

EN61241-1:2004   IEC60079-1:2004 (Ed1)       Dust Enclosures tD 

 

 

4)  Installation Requirements

 

 
The  led  beacons  must  be  installed  in  accordance  with  the 

latest  issues  of  the  relevant  parts  of  the  BS  EN  60079 
specifications  or  the  equivalent  IEC  specifications  – 

Selection,  Installation  and  maintenance  of  electrical 
apparatus for use in potentially explosive atmospheres (other 
than  mining  applications  or  explosive  processing  and 

manufacture):- 
 

EN60079-14:2008

    

Electrical Installations in Hazardous 

IEC60079-14:2007 (Ed4) 

Areas (other than mines)

 

 

EN60079-10:2003

   

Classification of Hazardous Areas

 

IEC60079-10:2008 (Ed1) 

 
The installation of the units must also be in accordance with 
any  local  codes  that  may  apply  and  should  only  be  carried 

out  by  a  competent  electrical  engineer  who  has  the 
necessary training. 

 

5)  Zones,  Gas  Group,  Category,  IP  Rating  and 

Temperature Classification 

 

The BExBGL1D beacons have been certified Ex d IIC T4 for 
Ta –50ºC to +70ºC and Ex d IIC T5 for Ta –50ºC to +40ºC for 

gas and IP67 T120ºC Ta < +70ºC,  T105ºC Ta < +55ºC and 
T95ºC Ta < +40ºC for dust. This means that the units can be 

installed in locations with the following conditions:- 
  

Area Classification Gas: 

 

Zone 1 

Explosive  gas  air  mixture  likely  to  occur  in 
normal operation. 

Zone 2 

Explosive  gas  air  mixture  not  likely  to  occur, 
and if it does, it will only exist for a short time. 

  

Gas Groupings: 

 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC 

Hydrogen and Acetylene 

  

 

Temperature Classification: 

 

T1 

400

o

 C  

T2 

300

o

 C 

T3 

200

o

 C 

T4 

135

o

 C 

T5 

 100

o

 C 

Amb. +40ºC 

 

 

0518 

CE Marking 
Notified Body No. 

II 2G/D 

Epsilon x 

Equipment Group and 
Category: 

Summary of Contents for BExBGL1D

Page 1: ...USE HEAT RESISTING CABLES AND CABLE GLANDS Rated 110ºC AT AMB TEMPERATURES OVER 40ºC Year of Construction Serial No i e 10 1DB73000001 3 Type Approval Standards The beacon has EC Type Examination and IECEx certificates issued by KEMA and have been approved to the following standards EN60079 0 2006 IEC60079 0 2004 Ed4 General Requirements EN60079 1 2007 IEC60079 1 2007 Ed6 Flameproof Enclosure d EN...

Page 2: ...d only screws of this category can be used on the beacons It is therefore important that these screws and their spring washers are kept in a safe place during installation On completion of the cable wiring installation the flameproof joints should be inspected to ensure that they are clean and that they have not been damaged during installation Also check that the earth bonding wire between the tw...

Page 3: ... and also meet the requirements of the Ex d flameproof installation standard EN60079 14 2008 IEC60079 14 2007 When only one cable entry is used the other one must be closed with an Ex d flameproof blanking plug which must be suitably approved for the installation requirements For combustible dust applications the cable entry device and blanking elements shall be in type of explosion protection inc...

Page 4: ...e third stage flash pattern connect a ve supply line to terminal S3 The supply line to the S3 terminal will automatically override a supply to the S2 terminal AC Units Second and Third Stage Selection To select the second and third stage flash patterns on the BExBGL1D AC beacons the Common C terminal on the three way terminal block on the pcb is connected to the S2 terminal for the second stage to...

Page 5: ...ctrical Installations in Hazardous IEC60079 14 2007 Ed4 Areas other than mines EN60079 10 2003 Classification of Hazardous Areas IEC60079 10 2008 Ed1 Installation should only be carried out by competent personnel and local codes of practice applied 5 Zones Gas Group Category and Temperature Classification The units can be installed in locations with the following conditions Area Classification Gas...

Page 6: ...2008 IEC60079 14 2007 When only one cable entry is used the other one must be closed with an Ex d flameproof blanking plug which must be suitably approved for the installation requirements For combustible dust applications the cable entry device and blanking elements shall be in type of explosion protection increased safety e or flameproof enclosure d and shall have an IP 6X rating according to EN...

Page 7: ...ts 26 01 11 3 Flash Pattern Table Stage 1 LED Stage 2 Stage 3 Pattern Flash Pattern Pattern Pattern 1 ON 9 8 2 Rotating 3 LED on Fast 7 1 3 Rotating 6 LED on Fast 8 1 4 Rotating 3 LED on Slow 9 1 5 Rotating 6 LED on Slow 6 1 6 Double strike strobe 1 Hz 9 1 7 Single strike strobe 2 Hz 3 1 8 Double strike strobe 2 Hz 3 1 9 Alternate side flash 1 1 2 Hz 3 1 PIN HEADER POSITIONS Pattern No 1 Pattern N...

Page 8: ...ete el tornillo para asegurar Dra åt skruven för att fästa Loosen screw to adjust Løsn skruen for at tilpasse Schroef losdraaien om af te stellen Desserrer la vis pour régler Zum Regulieren Schraube lockern Allentare la vite per poter effettuare la regolazione Løsne skruen for å justere Desaperte o parafuso para ajustar Afloje el tornillo para ajustar Lossa skruven för att justera Lossen screw to ...

Page 9: ...llte nur von qualifiziertem Fachpersonal vorgenommen werden Örtliche anerkannte Verfahren sind zu beachten 5 Zonen Gasgruppe Kategorie und Temperaturklassifizierung Die Geräte können an Standorten aufgestellt werden an denen die folgenden Bedingungen vorliegen Bereichseinteilung Gas Zone 1 Bei normalem Betrieb kann mit hoher Wahrscheinlichkeit eine explosive Gas Luft Mischung vorliegen Zone 2 Expl...

Page 10: ... verwendet werden die für Ex d Anwendungen zugelassen sind Die Kabelverschraubungen müssen für den eingesetzten Kabeltyp geeignet sein und zudem den Anforderungen der Ex d Norm zur Installation drucksicherer Geräte EN60079 14 2008 IEC60079 14 2007 entsprechen Wenn nur ein Kabeleingang verwendet wird muss der andere mit einem druckfesten Ex d Stopfen der für die Installationsbedingungen zugelassen ...

Page 11: ...n Kontrollwiderstand für das Leitungsende können über die Klemmen und angeschlossen werden Wird ein Widerstand für das Leitungsende verwendet muss sein Widerstandswert mindestens 3k3 Ohm und die Mindestleistung 0 5 Watt betragen oder aber es muss ein Widerstandswert von mindestens 500 Ohm und eine Mindestleistung von 2 Watt vorliegen Blinkmuster Tabelle Stufe 1 LED Stufe 2 Stufe 3 Muster Blinkmust...

Page 12: ...ions fulfilled by the equipment ll2 G Ex d llC T3 to T6 or ll2 G Exde llC T4 to T6 ll2 D Ex tD A21 lP66 or lP67 T85 C to T200 C Standards applied EN 60079 0 2006 EN 60079 1 2007 EN 60079 7 2003 EN 61241 0 2006 EN61241 1 2004 Directive 2004 108 EC Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 EN 61000 6 4 2007 The standards EN 60...

Reviews: