INSTRUCTION MANUAL (ATEX / IECEx)
BExDCS110-05D
Flameproof Combined Sounder / Beacon
For use in Flammable Gas and Dust Atmospheres
1) Introduction
The BExDCS110-05D is flameproof combined sounder /
beacon which is certified to meet the requirements of the
ATEX directive 94/9/EC and the IECEx scheme. The sounder
section produces loud audio warning signals and the beacon
section produces a synchronised visual warning signal. The
unit can be used in hazardous areas where potentially
flammable gas and dust atmospheres may be present.
Thirty-two different first stage audio alarm sounds can be
selected by internal switches, and each one can be externally
changed to a second or third stage alarm sound (
see tone
table on Page 5
). The sounder produces output levels in the
110dB(A) range and the beacon has a flash energy of 5
joules. The unit can be used in Zone 1 and Zone 2 areas with
gases in groups IIA and IIB and with Temperature
Classifications of T1, T2, T3 and T4 and can also be used in
Zone 21 and Zone 22 areas for combustible dusts and has
an IP rating of IP 67 and a surface temperature rating of
T115ºC based on a Ta max. of 70ºC (T100ºC at +55ºC).
2) Marking
All units have a rating label, which carries the following
important information:-
Unit Type No.
BExDCS110-05D
Input Voltage: DC Units 12V or 24V or 48V
AC Units 230V or 115V
Codes: Ex d IIB T4 for Ta –50°C to +70ºC
Ex tD A21 IP6X T115°C based on max Ta of +70°C
Certificate No.
KEMA 01ATEX2223X
IECEx KEM 10.0025X
“Warnings”
DO NOT OPEN WHEN AN EXPLOSIVE
GAS / DUST ATMOSPHERE IS PESENT
COVER BOLTS CLASS A4-80
USE HEAT RESISTING CABLES AND
CABLEGLANDS (Rated 110ºC) AT
AMB. TEMPERATURES OVER 40ºC
Year of Construction /
Serial No.
i.e. 10 / 1DCS21000001
3)
Type Approval Standards
The units have an EC Type examination certificate issued by
KEMA and have been approved to the following standards:-
EN60079-0:2006 IEC60079-0:2004 (Ed4)
General Requirements
EN60079-1:2007 IEC60079-1:2007
(Ed6)
Flameproof Enclosure ‘d’
EN61241-0:2006 IEC61241-0:2004 (Ed1) Dust General
Requirements
EN61241-1:2004 IEC60079-1:2004 (Ed1) Dust Enclosures tD
4)
Installation Requirements
The unit must be installed in accordance with the latest
issues of the relevant parts of the EN60079 specifications or
the equivalent IEC specifications – Selection, Installation and
maintenance of electrical apparatus for use in potentially
explosive atmospheres (other than mining applications or
explosive processing and manufacture):-
EN60079-14:2008
Electrical Installations in Hazardous
IEC60079-14:2007 (Ed4)
Areas (other than mines)
EN60079-10:2003
Classification of Hazardous Areas
IEC60079-10:2008 (Ed1)
The installation of the unit must also be in accordance with
any local codes that may apply and should only be carried
out by a competent electrical engineer who has the
necessary training.
5)
Zones, Gas Group, Category, IP Rating and
Temperature Classification
The BExDCS110-05D unit has been certified Ex d IIB T4 for
Ta –50°C to +70ºC for gas and Ex tD A21 IP6X T115ºC
based on max. Ta of +70ºC for dust. This means that the
units can be installed in locations with the following
conditions:-
Area Classification Gas:
Zone 1
Explosive gas air mixture likely to occur in
normal operation.
Zone 2
Explosive gas air mixture not likely to occur,
and if it does, it will only exist for a short time.
Gas Groupings:
Group IIA
Propane
Group IIB
Ethylene
Temperature Classification:
T1
400
o
C
T2
300
o
C
T3
200
o
C
T4
135
o
C
0518
CE Marking:
Notified Body No.
II 2G/D
Epsilon x:
Equipment Group and
Category: