INSTRUCTION MANUAL (ATEX / IECEx) 

BExDCS110-05D 

Flameproof Combined Sounder / Beacon 

For use in Flammable Gas and Dust Atmospheres 

 

 
 
 
 
 
 
 

1)  Introduction 

 

The  BExDCS110-05D  is  flameproof  combined  sounder  / 
beacon  which  is  certified  to  meet  the  requirements  of  the 

ATEX directive 94/9/EC and the IECEx scheme. The sounder 
section produces loud audio warning signals and the beacon 
section  produces  a  synchronised  visual  warning  signal.  The 

unit  can  be  used  in  hazardous  areas  where  potentially 
flammable  gas  and  dust  atmospheres  may  be  present.  

Thirty-two  different  first  stage  audio  alarm  sounds  can  be 
selected by internal switches, and each one can be externally 

changed  to  a second or  third  stage  alarm sound   (

see  tone 

table on Page 5

).  The sounder produces output levels in the 

110dB(A)  range  and  the  beacon  has  a  flash  energy  of  5 

joules. The unit can be used in Zone 1 and Zone 2 areas with 
gases  in  groups  IIA  and  IIB  and  with  Temperature 

Classifications of  T1, T2, T3 and T4 and can also be used in 
Zone 21  and  Zone 22  areas  for combustible dusts  and  has 

an  IP  rating  of  IP  67  and  a  surface  temperature  rating  of 
T115ºC based on a Ta max. of 70ºC (T100ºC at +55ºC). 

 

2)  Marking 

 
All  units  have  a  rating  label,  which  carries  the  following 

important information:- 
 
Unit Type No.     

       BExDCS110-05D

 

 
Input Voltage:    DC Units    12V  or 24V  or  48V 

            AC Units         230V or 115V 

 

Codes:   Ex d IIB T4 for Ta –50°C to +70ºC 

Ex tD A21 IP6X T115°C based on max Ta of +70°C 

 

       

 

            

Certificate No.

 

KEMA 01ATEX2223X 
IECEx KEM 10.0025X 

    

 

 

 

 

 

“Warnings”

 

 

DO NOT OPEN WHEN AN EXPLOSIVE  

                              GAS / DUST ATMOSPHERE IS PESENT 
 

      COVER BOLTS CLASS A4-80 

 

                    USE HEAT RESISTING CABLES AND        

                   CABLEGLANDS (Rated 110ºC) AT  

                       AMB. TEMPERATURES OVER 40ºC 

 
Year of Construction /  

Serial No.       

 

 i.e.  10 / 1DCS21000001 

 

 
 

 

 
 

 
 

 
 

 
 

3) 

Type Approval Standards

 

 

The units have an EC Type examination certificate issued by 
KEMA and have been approved to the following standards:- 

 

EN60079-0:2006   IEC60079-0:2004 (Ed4)

      

General Requirements

 

EN60079-1:2007   IEC60079-1:2007

 

(Ed6)

        Flameproof Enclosure ‘d’ 

EN61241-0:2006   IEC61241-0:2004 (Ed1)       Dust General 

          Requirements 

EN61241-1:2004   IEC60079-1:2004 (Ed1)       Dust Enclosures tD 

 

4) 

Installation Requirements

 

 

The  unit  must  be  installed  in  accordance  with  the  latest 
issues of the relevant parts of the EN60079 specifications or 

the equivalent IEC specifications – Selection, Installation and 
maintenance  of  electrical  apparatus  for  use  in  potentially 

explosive  atmospheres  (other  than  mining  applications  or 
explosive processing and manufacture):- 

 

EN60079-14:2008

    

Electrical Installations in Hazardous 

IEC60079-14:2007 (Ed4) 

Areas (other than mines)

 

 

EN60079-10:2003

   

Classification of Hazardous Areas

 

IEC60079-10:2008 (Ed1) 

 
The  installation  of  the  unit  must  also be  in  accordance  with 

any  local  codes  that  may  apply  and  should  only  be  carried 
out  by  a  competent  electrical  engineer  who  has  the 

necessary training. 

 

5) 

Zones,  Gas  Group,  Category,  IP  Rating  and 
Temperature Classification 

 

The BExDCS110-05D unit has been certified Ex d IIB T4 for 

Ta  –50°C  to  +70ºC  for  gas  and  Ex  tD  A21  IP6X  T115ºC 
based  on  max.  Ta  of  +70ºC  for  dust.  This  means  that  the 

units  can  be  installed  in  locations  with  the  following 
conditions:- 
  

Area Classification Gas: 

 

Zone 1 

Explosive  gas  air  mixture  likely  to  occur  in 

normal operation. 

Zone 2 

Explosive  gas  air  mixture  not  likely  to  occur, 

and if it does, it will only exist for a short time. 

  

Gas Groupings: 

 

Group IIA 

Propane 

Group IIB 

Ethylene 

  

 

Temperature Classification: 

 

T1 

400

o

 C  

T2 

300

o

 C 

T3 

200

o

 C 

T4 

135

o

 C 

0518 

CE Marking: 
Notified Body No. 

 

II 2G/D 

Epsilon x: 
Equipment Group and 
Category: 

Summary of Contents for BE DCS110-05D Series

Page 1: ...O NOT OPEN WHEN AN EXPLOSIVE GAS DUST ATMOSPHERE IS PESENT COVER BOLTS CLASS A4 80 USE HEAT RESISTING CABLES AND CABLEGLANDS Rated 110 C AT AMB TEMPERATURES OVER 40 C Year of Construction Serial No i...

Page 2: ...installation On completion of the cable wiring installation the flameproof joints should be inspected to ensure that they are clean and that they have not been damaged during installation Also check t...

Page 3: ...glands approved for Ex d applications can be used which must be suitable for the type of cable being used and also meet the requirements of the Ex d flameproof installation standard EN60079 14 2008 I...

Page 4: ...operate the sounder on stage one simply connect the supply voltage to the normal supply terminals ve and ve for DC units L and N for AC units The operation of the second and third stages is different...

Page 5: ...ency Description 1 2 3 4 5 Stage 2 Stage 3 1 Continuous 1000Hz Toxic gas alarm 0 0 0 0 0 Tone 31 Tone 11 2 Alternating 800 1000Hz at 0 25s intervals 1 0 0 0 0 Tone 17 Tone 5 3 Slow Whoop 500 1200Hz at...

Page 6: ...r PCB Unit No 1 L N Beacon PCB L N Beacon PCB L N Beacon PCB L N C S2 S3 Sounder PCB L N C S2 S3 Sounder PCB Unit No 3 Unit No 2 C N S3 S2 L Sounder PCB Unit No 1 L N C S2 S3 Beacon PCB L N L N L N Be...

Page 7: ...ccleston Chester CH4 9JN UK Quality Assurance Notification SIRA 05 ATEX M342 Provisions fulfilled by the equipment ll2 G Ex d llB T4 ll 2 D Ex tD A21 IPGX T100 C or T115 C Standards applied EN 60079 0...

Reviews: