background image

BA_EE300Ex_e // V1.11.2 // Modification rights reserved // 194916

User Manual

EE300Ex 

HUMIDITY / TEMPERATURE 

SENSOR

Summary of Contents for EE300Ex

Page 1: ...BA_EE300Ex_e V1 11 2 Modification rights reserved 194916 User Manual EE300Ex HUMIDITY TEMPERATURE SENSOR...

Page 2: ...equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmf...

Page 3: ...e Feedthrough with Cut in Fitting 19 3 5 2 Mounting Flange 19 3 5 3 Ball Valve and Sliding Fitting 20 3 5 4 The Optional Probe Retraction Tool 21 4 Electrical Connections 22 4 1 General 22 4 2 Termina...

Page 4: ...com Installation electrical connection maintenance and commissioning shall be performed by qualified personnel only 1 2 2 Mounting Start up and Operation The device has been produced under state of t...

Page 5: ...d Temperature Sensor Blind front cover for housing base HA011401 Safety barrier 1 channel STAHL 9002 13 280 093 001 HA011410 Intrinsically safe supply unit 1 channel STAHL 9160 13 11 11 HA011405 Intri...

Page 6: ...47 T7 Remote probe with cut in fitting pressure tight 0 1 20 bar 1 5 300 psi 40 180 C 40 356 F 12 mm 0 47 T9 Remote probe with cut in fitting pressure tight 0 01 300 bar 0 15 4 351 psi 40 180 C 40 356...

Page 7: ...us label for EE300Ex without display USA product label Example E E Elektronik A 4209 Engerwitzdorf FM17US0302X CL I II III DIV 1 GP ABCDEFG T4 CL I II III DIV 2 GP ABCDEFG T4 CL I ZN 0 AEx ia IIC T4 G...

Page 8: ...re probe INTERNATIONAL Applied Standard for IECEx IEC 60079 0 2011 IEC 60079 11 2011 The Certificate of Conformity has been carried out by FM Approvals Certificate No IECEx FMG 14 0017 X Entity parame...

Page 9: ...G T4 Ta 40 C to 60 C Entity M1_139080 IP65 Class I II III Division 2 Groups ABCDEFG T4 Ta 40 C to 60 C Sensor with display Class I Division 1 Groups CD T4 Ta 40 C to 60 C Entity M1_139080 Class I Divi...

Page 10: ...sed on 70 C 94 F Ta 60 C 140 F T5 temperature class based on 70 C 94 F Ta 75 C 167 F T4 temperature class based on 70 C 94 F Ta 110 C 230 F T3 temperature class based on 70 C 94 F Ta 175 C 347 F T2 te...

Page 11: ...Ga Entity M1_139080 IP65 Zone 20 Ex ia IIIC T131 C Ta 40 C to 60 C Da Entity M1_139080 IP65 Sensor with display Zone 0 Ex ia IIB T4 Ta 40 C to 60 C Ga Entity M1_139080 Zone 1 Ex ia IIC T4 Ta 40 C to 6...

Page 12: ...94 F Ta 75 C 167 F T4 temperature class based on 70 C 94 F Ta 110 C 230 F T3 temperature class based on 70 C 94 F Ta 175 C 347 F T2 temperature class based on 70 C 94 F Ta 200 C 392 F T1 temperature...

Page 13: ...300 bar 4351 psi with weld or cut in fitting Types T1 T7 T9 T10 T22 Enclosure 179 7 60 2 4 151 5 9 adjustable min 23 0 9 max 164 6 5 364 14 3 G1 2 ISO or 1 2 NPT G1 2 ISO or 1 2 NPT 98 3 9 53 2 1 13...

Page 14: ...or wiring intrinsically safe electrical circuits according to EN 60079 14 EN 60079 25 IEC 60079 14 IEC 60079 25 proof of intrinsic safety in the system description as well as all applicable national r...

Page 15: ...charge with the blind front cover HA011401 see accessories Unused cable glands shall be closed with appropriate sealing plugs see accessories 3 3 Assembly in Category 1 Zone 0 20 Division 1 Only intr...

Page 16: ...ea EPL Ga for Group IIC or Class I Division 1 group A B and in the dust hazard area for groups IIIA IIIB and IIIC or Class II III The probe for wall mount is not permitted to be used for Zone or Divis...

Page 17: ...ion 3 4 Assembly in Categories 2 and 3 Zone 1 2 21 22 Division 2 Only intrinsically safe power supply devices and protective barriers are approved to supply EE300Ex in category 2 and 3 or Division 2 N...

Page 18: ...cated at the most representative location for the RH and T of the process to be monitored For accurate measurement it is of paramount importance to avoid temperature gradients along the probe Whenever...

Page 19: ...ion bushing For this the tightness of its mounting into the Zone separation wall must correspond to IP67 Once mounted the cut in fitting creates a permanent clamping ring onto the probe Safety instruc...

Page 20: ...4 F The maximum permitted process pressure during mounting is 10 bar 145 psi Mount the probe onto the ball valve with the ball valve closed Open the ball valve Slide the probe through the ball valve i...

Page 21: ...action tool must be strictly observed The probe of the EE300EX model T22 can be installed into a pressurized environment up to 250 bar using the sensor retraction tools ZM WA 025 040 EST or BG WA 103...

Page 22: ...all be performed according to NEC or CEC and to the Control Drawing M1_1309080 page 51 The installation in an explosion hazard area shall comply with EN 60079 14 EN 60079 25 or IEC 60079 14 IEC 60079...

Page 23: ...conductor or the potential equalization connection must have a cross section of 4 mm 0 06 in for the external grounding Stranded wires shall be fitted with suitable wire end sleeves The resistance of...

Page 24: ...079 14 and EN60079 25 Maximum cross section 1 5 mm 0 02 in Single stranded wire diameter 0 1mm 0 004 Test voltage wire wire 500 V AC eff Test voltage wire shield if a cable with shield is used 500 V A...

Page 25: ...ce with EN 60079 14 2008 12 2 5 2 EN 60079 25 2010 13 1 CH1 and CH2 are galvanically isolated The proof of intrinsic safety shall be performed with appropriate equipment Example Installation in Zone 0...

Page 26: ...A Li negligibly small no reduced C0 and L0 values are required 4 7 Configuration Adapter The on board service interface is dedicated for the EE300EX configuration and for the RH and T adjust ment Thi...

Page 27: ...II III For EX6 TIIS no display in Ga The display shows the measured parameter on the outputs CH1 top row and CH2 bottom row according the ordering code The top key change the visualization of the calc...

Page 28: ...If needed the sensing head of the probe can be cleaned For cleaning instructions please see www epluse com ee300ex When replacing a filter cap ensure that the sensor is NOT touching the filter cap 6 3...

Page 29: ...rotection class of housing IP65 NEMA 4 Cable gland M16 for cable diameter 5 10 mm 0 2 0 4 M20 for cable diameter 10 14 mm 0 4 0 6 Electrical connection Screw terminals max 1 5 mm AWG 16 Working temper...

Page 30: ...suring range Electronics 40 60 C 40 140 F Electronics with display 20 60 C 4 140 F Storage temperature range Electronics and probe 20 60 C 22 140 F Material Enclosure stainless steel 1 4404 Probe cabl...

Page 31: ...31 User Manual EE300Ex Humidity Temperature Sensor 8 ATEX Certificate...

Page 32: ...32 User Manual EE300Ex Humidity Temperature Sensor...

Page 33: ...33 User Manual EE300Ex Humidity Temperature Sensor...

Page 34: ...34 User Manual EE300Ex Humidity Temperature Sensor...

Page 35: ...35 User Manual EE300Ex Humidity Temperature Sensor 9 EU Declaration of Conformity...

Page 36: ...36 User Manual EE300Ex Humidity Temperature Sensor 10 IECEX Certification of Conformity COC for more information see http www iecex com or our website http www epluse com ee300ex...

Page 37: ...15 FM Class 3611 2016 FM Class 3810 2005 ANSI ISA 61010 1 2012 ANSI ISA 60079 0 2013 ANSI ISA 60079 11 2014 ANSI IEC 60529 2004 8 If the sign X is placed after the certificate number it indicates that...

Page 38: ...one 20 AEx ia IIIC T80 C Da Entity M1_1309080 IP65 Equipment Group II EE300Ex with display Class I Division 1 Groups C and D T4 Ta 40 C to 60 C Entity M1_1309080 Class I Division 2 Groups A B C and D...

Page 39: ...2 or F13 c Sensor Protection C0 or C1 d Software Code 22 to 44 Digits Not Safety Relevant Entity parameters Terminals Vmax or Ui Imax or Ii Pi Li Ci CH 1 and 6 4Vdc Ui 28Vdc 100mA 0 7W 0mH 2 2nF CH 2...

Page 40: ...ection E2 E13 E15 E17 E18 E19 E20 E21 E22 or E32 c Probe Cable Length K0 2 K0 5 K1 K2 K3 K5 or K10 d Probe length L150 e Zone Feedthrough probe fitting PA0 PA26 or PA27 f Software Code 7 to 10 Digits...

Page 41: ...e Zone Feedthrough probe fitting PA0 PA20 PA21 PA22 PA28 PA23 or PA25 f Filter F2 F4 F5 F9 F10 F11 F12 or F13 g Sensor Protection C0 or C1 h Software Code 22 to 44 Digits Not Safety Relevant Entity pa...

Page 42: ...Code T Code Ambient Temperature T6 70 C Ta 60 C T5 70 C Ta 75 C T4 70 C Ta 110 C T3 70 C Ta 175 C T2 70 C Ta 200 C T1 70 C Ta 200 C 13 Specific Conditions of Use Equipment Group I EE300Ex without dis...

Page 43: ...nts to this certificate are described below Date Description 2nd October 2017 Original Issue 30th November 2017 Supplement 2 Report Reference RR211141 dated 30th November 2017 Description of the Chang...

Page 44: ...M91 R2006 CSA C22 2 No 142 M1987 R2004 CSA C22 2 No 157 92 2016 CSA C22 2 No 213 2015 CSA C22 2 No 60529 R2010 CAN CSA C22 2 No 60079 0 2015 CAN CSA C22 2 No 60079 11 2014 CAN CSA C22 2 No 61010 1 201...

Page 45: ...C T6 T1 Ga Entity M1_1309080 IP65 Zone 20 Ex ia IIIC T80 C Da Entity M1_1309080 IP65 Equipment Group II EE300Ex with display Class I Division 1 Groups C and D T4 Ta 40 C to 60 C Entity M1_1309080 Clas...

Page 46: ...F12 or F13 c Sensor Protection C0 or C1 d Software Code 22 to 44 Digits Not Safety Relevant Entity parameters Terminals Vmax or Ui Imax or Ii Pi Li Ci CH 1 and 6 4Vdc Ui 28Vdc 100mA 0 7W 0mH 2 2nF CH...

Page 47: ...n E2 E13 E15 E17 E18 E19 E20 E21 E22 or E32 c Probe Cable Length K0 2 K0 5 K1 K2 K3 K5 or K10 d Probe length L150 e Zone Feedthrough probe fitting PA0 PA26 or PA27 f Software Code 7 to 10 Digits Not S...

Page 48: ...00 e Zone Feedthrough probe fitting PA0 PA20 PA21 PA22 PA28 PA23 or PA25 f Filter F2 F4 F5 F9 F10 F11 F12 or F13 g Sensor Protection C0 or C1 h Software Code 22 to 44 Digits Not Safety Relevant Entity...

Page 49: ...ure Code T Code Ambient Temperature T6 70 C Ta 60 C T5 70 C Ta 75 C T4 70 C Ta 110 C T3 70 C Ta 175 C T2 70 C Ta 200 C T1 70 C Ta 200 C 13 Specific Conditions of Use Equipment Group I EE300Ex without...

Page 50: ...ements to this certificate are described below Date Description 2nd October 2017 Original Issue 30th November 2017 Supplement 2 Report Reference RR211141 dayed 30th November 2017 Description of the Ch...

Page 51: ...51 User Manual EE300Ex Humidity Temperature Sensor 13 Control Drawing M1_1309080...

Page 52: ...52 User Manual EE300Ex Humidity Temperature Sensor...

Page 53: ...53 User Manual EE300Ex Humidity Temperature Sensor...

Page 54: ...54 User Manual EE300Ex Humidity Temperature Sensor 14 Certificates Korea and Japan For more information please contact the E E sales support...

Page 55: ...55 User Manual EE300Ex Humidity Temperature Sensor...

Page 56: ...lin 69130 Ecully Tel 33 4 74 72 35 82 E mail info epluse fr E E Elektronik Germany Sch ne Aussicht 8 C 61348 Bad Homburg Tel 49 6172 13881 0 E mail info epluse de E E Elektronik Italy Via Alghero 17 1...

Reviews: