background image

 

 
 

 

 

 

 

3211 Fruitland Ave 

Los Angeles, CA  90058 

UM-200 

 

2-Channel Monitor 

 

Version 2

 

 

Installation and Operation Manual 

 

 

 

Rev. D 

 

P/N145F-13019 

 
 

(c) Copyright 2013, Dynalco Controls 

 

All Rights Reserved 

 

Published: December 3, 2013 

Summary of Contents for UM-200

Page 1: ...eles CA 90058 UM 200 2 Channel Monitor Version 2 Installation and Operation Manual Rev D P N145F 13019 c Copyright 2013 Dynalco Controls All Rights Reserved Published December 3 2013 DVNALCO Alarm D Inlet Tern1 erature CH2 982F ...

Page 2: ... to this instrument and warranty invalidation For clarification of instructions in this manual or assistance with your application contact Dynalco at 800 368 6666 or 954 739 4300 or send email to customerservice dynalco com Additional manuals and CSA certificates are available at Follow all warnings cautions and instructions marked on and supplied with the product Use only qualified personnel to i...

Page 3: ...anels with 3 3 8 inch 86 mm opening Specifications Input Types J or K type thermocouple ungrounded accurate to 0 2 4 20 mA 0 1 VDC 0 5 VDC 0 10 VDC Digital Input Closure to ground indicates run condition or use pulsed input Pulsed Input Magnetic pickup input for RPM display to indicate run condition Relay Output Digital Output rated 0 15 A 48 VDC Input Power 10 36 VDC Display Backlit Graphic Displ...

Page 4: ...3 Installation The UM 200 is designed to be panel mounted The dimensions are shown below The UM 200 has a bracket for securing into the panel t 3 35 3 89 u 1 2 01 2 94 ...

Page 5: ...on the back of the unit Terminal screws to be tightened to 8 inch pounds torque See page 10 for complete wiring information SIGNAL TERMINAi NEG DC VOLTS 1 POS DC VOLTS 2 NEG Al CHNL 1 3 POS AI CHNL 1 4 NEG Al CHNL 2 5 POS AI CHNU 6 RPM SIGNAL IN A ALARM OUTPUT B ...

Page 6: ...ed through the front keypad Below is a brief description of each key Press to enter or exit the configuration screens Press to enter or accept values Select up Select down Go back one screen Select and advance to next screen DI DI DYNALOO Alim Cl L M 200 ...

Page 7: ... 200 must first be programmed prior to operation When first powering up the unit the display will first indicate the firmware version and then go to the operational mode To configure each input first go to the main programming screen by pressing the Menu Escape key The main configuration screen shows the following icons Run Signal defines run status input type Channel enables each channel defines ...

Page 8: ... to be at normal levels If no delay is required set to 0 seconds The magnetic pickup should be connected to input terminals A and 1 See page 4 for connections If Digital is selected you will only need to set the startup delay if applicable In this mode a run signal will be sensed with a contact closure or short between terminals A and 1 Pressing at any time during configuration will prompt you to ...

Page 9: ...d to channel 2 The output of the oxygen sensor is 0 1 VDC 0 1000 mV The Cal Zero and Cal Span values would be defined as Cal Zero 0 Cal Span 1000 Note that the Engineering Units would be input as mV in Channel configuration above Configuration of Alarm Settings Using the arrows on the keypad select the Alarm Settings icon Next select the channel number to configure by pressing the up down arrows a...

Page 10: ...nputs and will initiate alarms based on over under threshold values configured for each channel It is not necessary to define alarm threshold values for both channels as they may be for monitoring only Alarm Shutdown Output The UM 200 will alarm when either channel value or differential value is above or below limits as specified Alarms can be configured as either latching or non latching If an al...

Page 11: ...13 K type thermocouple displays in DegF TID110 14 K type thermocouple displays in DegC STM110 11 J type thermocouple displays in DegF STM110 12 J type thermocouple displays in DegC STM110 13 K type thermocouple displays in DegF STM110 14 K type thermocouple displays in DegC Please see the programming steps in this manual for configuring the proper thermocouple type and display in either DegF or De...

Page 12: ...ckups haw bee n must be approved for use in Class I Division 2 Groups A B C D areas approved to be conn ected to the RPM Input the pickup must be connected with Any ungrounded thermocoup le may be conneet ed to the UM 200 Monitor as shle lded cable with th e shle ld conne cted to te rmlnal 2 assh 1Nn Asan alternative the thermocouple in p ut circuit has been evaluated as non incendive a contact cl...

Reviews: