Thankyou  for  selecting  the  Duomo  CellAir

TM

  CO

2

 

monitor.  It  is  designed  to  detect  the  presence  of 
carbon dioxide in the ambient air to protect people 
in  confined  spaces.  High  concentrations  of  CO

2

  in 

confined  spaces  are  dangerous,  and  may  lead  to 
health  problems  ranging  from  headaches  and 
fatigue  to  asphyxiation  and  death.  CellAir

TM

  has  an 

audible  alarm  and  visual  indication  which  will 
activate when CO

2

 concentration reaches a pre-set 

level.  Detection  of  high  levels  of  CO

2

  will  also 

activate  a  relay  that  could  be  used  for  a  fan  to 
ventilate  the  confined  space  and  reduce  CO

2

 

concentration  in  the  area.  CellAir

TM

  can  be  widely 

used  in  CO

2

  storage  areas,  breweries,  wineries, 

cellars,  beverage  dispensing  areas  and  fast  food 
outlets.

CO

2

 Specification

Measurement range - 0 - 50,000ppm
Accuracy - ±100ppm or ±5% of reading
Temperature Specification
Measurement range - 0

o

C - 50

o

C (32

o

F - 122

o

F)

Alarm Levels
Alarm 1 - 0.5 / 1 / 1.5 / 2%
Alarm 2 - 1.5 / 2 / 2.5 / 3 / 3.5 / 4%
Operating Conditions
Operating temperature - 0

o

C - 40

o

C (32

o

F - 104

o

F)

Humidity range - 0 ~ 95%RH
Storage Conditions
Storage temperature - -20

o

C - 60

o

C (-4

o

F - 140

o

F)

Power Supply & Relay Output
AC adapter - 110/220 VAC
AC input - 100 ~ 240 VAC, 50/60Hz
AC output - 6 VDC, 1.8 W
Relay output - 30 VDC or 250 VAC, max. 2A, SPST,  NO
Accuracy
Annual drift < 20ppm / year @ 400ppm
Calibration
User calibration via onboard menu system
Recommended calibration interval - 2 years

NDIR (Non-Dispersive Infrared) sensor
Measures up to 50,000ppm
Can handle up to 3 remote display units;
1 up to 25m away, 3 up to 8m apart
Large LCD display indicates ambient
CO

2

 concentration and temperature

Relay output to automatically control
a fan to ventilate confined spaces
Audible and visual alarm indications
IP54 water proof protection

Application

Specifications

Package Contents

SEU (Sensor Unit), RDU (Remote Display Unit), panel 
holders,  network  cable  connector,  communication 
cable (8m length), fixtures and fittings, user manual.

CellAir

TM

 CO

2

 Detector

w: www.duomo.co.uk 

-

e: [email protected]

-

t: 01905 797989

-

f: 01905 774296

 |   © Duomo (UK) Ltd. 20

16

Summary of Contents for CellAir

Page 1: ...1 5 2 Alarm 2 1 5 2 2 5 3 3 5 4 Operating Conditions Operating temperature 0o C 40o C 32o F 104o F Humidity range 0 95 RH Storage Conditions Storage temperature 20o C 60o C 4o F 140o F Power Supply Relay Output AC adapter 110 220 VAC AC input 100 240 VAC 50 60Hz AC output 6 VDC 1 8 W Relay output 30 VDC or 250 VAC max 2A SPST NO Accuracy Annual drift 20ppm year 400ppm Calibration User calibration ...

Page 2: ... stop sounding When concentrations exceed the second alarm level both AL1 and AL2 LED s will flash and the alarm will sound more quickly The alarm will remain in this state until the button has been pressed In the case of very high concentrations ESC will appear on the screen of the unit It is imperative that the area be completely ventilated and that no one enters the area until concentrations ha...

Page 3: ...flashes Fault LED flashes Alarm sounds Power the unit down then back up If Er5 Er6 still appears please return the unit to the dealer Internal data transmission error Er7 flashes Fault LED flashes Alarm sounds Er7 flashes Fault LED flashes Alarm sounds Power the unit down then back up Check the communication cable between the SEU and RDU Er5 Er6 Er7 Er8 CO2 concentration ppm Ambient CO2 concentrat...

Page 4: ...Settings w www duomo co uk e sales duomo co uk t 01905 797989 f 01905 774296 Duomo UK Ltd 2007 1 Press the button until DIAG flashes 2 Press the four LED s on the SEU will flash and its alarm will sound 3 The four LED s on the RDU will flash and its alarm will sound 1 Press button until AL1 flashes 2 Press the AL1 icon shown on the LCD 3 Press to go through the parameters 4 Press again to save the...

Page 5: ...Fault indication C AL1 LED Alarm 1 D AL2 LED Alarm 2 E OK LED Power indication F Reset button G Mode button H Enter button I Communication cable to RDU J Relay output K Power supply L Rubber cap M Gas entry O OK LED Power indication P AL1 LED Alarm 1 Q AL2 LED Alarm 2 R FLT LED Fault indication S LCD display T Enter button U Mode button V RJ45 plug for SEU Input W RJ45 plug for next RDU Output A B...

Reviews: