Metering PDU 

 

 

 

Manual

 

DN-95601 • DN-95602 

Summary of Contents for DN-95601

Page 1: ...Metering PDU Manual DN 95601 DN 95602 ...

Page 2: ...ing material is NOT a toy Plastics has to be stored out of range of children Please recycle the packaging materials In case of further questions about installation operation or usage of the device which are not clear after reading the manual please do not hesitate to ask our support team Description The DIGITUS Metering PDU DN 95601 is a multiple socket outlet with CEE 7 4 sockets DN 95601 or IEC ...

Page 3: ...twork to the Ethernet port of the DIGITUS Metering PDU DN 95601 3 Attach up to seven loads to the CEE 7 4 sockets or IEC sockets for DN 95602 of the DIGITUS Metering PDU DN 95601 Usage and Display Status LED The status LED shows directly the state of the device Red The device is not connected to the Ethernet Orange The device is connected to the Ethernet TCP IP settings are not defined Green Your ...

Page 4: ... the top line the period of time over the power was measured The values are stored in an EEPROM every 5 minutes and therefore preserved during a power outage VRMS 225 3V IRMS 0 000A Here voltage and current are shown Active 0W Reactive 0VAR Active power and reactive power are shown Apparent 0VA Phase 83 5deg The measured values of apparent power and the phase angle of the power Freq 50 02Hz Powerf...

Page 5: ...nf exe The program will look automatically for connected devices and will display their network configuration If the displayed IP address accords with the factory settings 192 168 0 2 there is either no DHCP server available in the network or no free IP address could be allocated Enter a free IP address and the according netmask in the entry mask then save these changes by clicking on Program Devi...

Page 6: ...ges to get valid a restart of the firmware is required Das Bild kann nicht angezeigt werden Dieser Computer verfügt möglicherweise über zu wenig Arbeitsspeicher um das Bild zu öffnen oder das Bild ist beschädigt Starten Sie den Computer neu und öffnen Sie dann erneut die Datei Wenn weiterhin das rote x angezeigt wird müssen Sie das Bild möglicherweise löschen und dann erneut einfügen Das Bild kann...

Page 7: ...r Wether it is active hosts and subnets only can contact the unit if their IP addresses are stated in this IP ACL e g http 192 168 0 1 or http 192 168 0 1 24 If you locked yourself out by mistake please activate the bootloader mode start Gbl_Conf exe and deactivate IP ACL Here you can set if the device shall react on pings Enable IP Filter Here you can activate the IP Access Control List IP ACL If...

Page 8: ...admin is admin Users are authorized to login but are not allowed to modify the settings The username of the user is user If you have forgotten your password activate the bootloader mode start GBL Conf exe and deactivate the password request For the changes to get valid a restart of the firmware is required Check Password on start page If activated the user has to enter his password before logging ...

Page 9: ...rm threshold 1 If the value of 11 C is reached the alarm is reset Without the threshold would be for small fluctuations of 0 1 C respectively a new alarm is issued or initiate a command Limit 10 Action trigger alarm threshold 0 Temperature 10 C Alarm is triggered Temperature 10 1 C Alarm is reset 9 9 C temperature alarm is triggered etc Das Bild kann nicht angezeigt werden Dieser Computer verfügt ...

Page 10: ... DMZ or IP ACL MIB All information that can be requested or changed the so called Managed Objects are described in Management Information Bases MIBs There are three MIBs which can be requested from the unit system interface system and interface are standardized MIBs MIB II At least there are so called Object Identifiers OID subordinated to those three structures An OID describes the location of an...

Page 11: ... simple text messages transmitted to a syslog server using UDP Linux OS regularly have a syslog daemon installed e g syslog ng For Windows there are some freeware tools available On following events a syslog message will be send Booting up Activation deactivation of syslog sensor alarm Enable Syslog Here you can activate Syslog Syslog Server IP If syslog is active enter here the IP address of you ...

Page 12: ... use when sending e mails Recipient address Enter the e mail address of the recipient Enable Authentifiaction If your e mail server needs an authentification you can enter it here Username Enter the username the device should use to log on your e mail server Set new password If your server needs a password for sending e mails you can enter it here Repeat password Repeat the password to enable it ...

Page 13: ...ick on Program Device Firmware Update and determine the location of the new firmware Please note The up to date firmware and GBL_Conf exe can be found at www assmann com free to download Technical information Connections 1 x CEE 7 4 Plug 230 VAC max 16A 1 x Ethernet jack RJ45 Power outlets 7x CEE 7 4 max 16A DN 95601 8x IEC C13 max 10A DN 95602 Network 10 100 MBit s 10baseT Ethernet Protocols TCP ...

Page 14: ...cts Product name DIGITUS Metering PDU DN 95601 DIGITUS Metering PDU DN 95602 Telecontrol System are in accordance with the following european directives Reference no Title 89 336 EWG 89 336 EEC Electromagnetic Compatibility 2006 95 EWG 2006 95 EEC Low Voltage Electrical Equipment 93 68 EWG 93 68 EEC CE marking And comply with the following European standards Standard Title EN 55022 2006 A1 A2 Info...