background image

 

 
 
 
 

PWR-240/PWR-480 

 
 

INSTALLATION MANUAL 

 
 
 
 

 

 

Summary of Contents for PWR-240

Page 1: ...PWR 240 PWR 480 INSTALLATION MANUAL ...

Page 2: ...le for technical or editorial errors or omissions contained herein nor for incidental or consequential damages resulting from the use of this material Product names mentioned herein are for identification purposes only and may be trademarks and or registered trademarks of their respective companies Datalogic is a registered trademark of Datalogic S p A in many countries and the Datalogic logo is a...

Page 3: ...IEW v GUIDE TO INSTALLATION vi 1 INSTALLATION 1 1 1 PWR 240 PWR 480 Electrical Diagram 1 1 2 Electrical Connections 2 1 2 1 Input Line Voltage 3 1 2 2 Supply Capacity When Wiring Directly to Scanners 4 1 2 3 Supply Capacity When Wiring to SC8000 5 2 TECHNICAL FEATURES 6 ...

Page 4: ...l appears as follows The internal AC plug must only be used temporarily during system installation or maintenance Maximum available power 500 W Figure 1 AC Plug Label SERVICES AND SUPPORT Datalogic provides several services as well as technical support through its website Log on to www automation datalogic com and click on the links indicated for further information including PRODUCTS Search throu...

Page 5: ...1 2 3 Main Switch Key Locks Glands Figure 3 PWR 240 PWR 480 open view 1 2 4 Monophase Switching Power Supply Cooling Fan AC Plug for temporary use only 3 24 Vdc Terminal Block 5 AC Line Input Terminal Block 6 Main Switch 7 Safety Fuse 1 3 2 2 1 3 5 6 7 4 ...

Page 6: ...AC Terminal Block see par 1 2 1 4 System Wiring Directly to Scanners Provide correct and complete system cabling to the PWR according to the signals necessary for the layout of your application See par 1 2 2 and your scanner manual for details All system cables must pass through the glands With SC8000 Connect the SC8000 Controller to the PWR by means of the appropriate cables see par 1 2 3 and the...

Page 7: ...onents are electrically connected as displayed in the following diagram Figure 4 PWR 240 PWR 480 Electrical Diagram CAUTION The AC plug must only be used temporarily during system installation or maintenance The maximum power is 500 W N L Three Pole Power Switch Two Pole Fused Disconnecting Switch 10 A Monophase Switching Power Supply AC DC PE AC Plug Fused AC Line and Neutral 4 A Fan N L 24V 0V ...

Page 8: ...s provided The terminal block also allows various system wiring terminals so that all system wiring i e host communication P S Encoder etc can be provided through a single cable when connecting directly to the scanners For connection to the SC8000 Controller only the 24 V DC low voltage output is necessary Figure 5 PWR 240 PWR 480 Terminal Block AC Plug AC Line 4 A Fused ...

Page 9: ... have to be inserted into the dedicated terminal blocks on the DIN rail see diagram which are marked Line L neutral N and Protection Earth PE The terminal block marked with the ground symbol is a special block which allows direct connection of the Protection Earth with the enclosure of the PWR 240 PWR 480 The AC input cable must be inserted through one of the Glands and the individual wires instal...

Page 10: ... W PWR 480 The maximum peak power propagated is 24 V x 26 A 624 W while the steady state normal power is 24 V x 20 A 480 W Due to these limits the maximum number of scanners to be supplied for direct wiring is Maximum Number of Scanners Power Supply Unit DS6000 DX6000 DS8100A DX8200A DS8100 DX8200 PWR 240 12 10 8 6 4 3 PWR 480 24 20 16 12 8 6 DS8100 and DX8200 scanners have peak power startup cons...

Page 11: ... maximum peak power propagated is 24 V x 26 A 624 W while the steady state normal power is 24 V x 20 A 480 W Due to these limits the maximum number of scanners to be supplied when using the SC8000 Contoller is Maximum Number of Scanners SC8000 Power Supply Unit DS8100 DX8200 PWR 240 6 5 PWR 480 14 12 DS8100 and DX8200 scanners have peak power startup consumption of 60W The power supply unit is con...

Page 12: ...ut Voltage 24 VDC 1 Output Noise Suppression Radiated EMI values below EN50081 1 even when using long unscreened output cables ENVIRONMENTAL FEATURES Operating temperature 25 to 50 C 13 to 122 F Storage temperature 40 to 85 C 40 to 185 F Humidity 90 non condensing Protection Class IP65 PHYSICAL FEATURES Mechanical Dimensions 500 x 300 x 210 mm 19 7 x 11 8 x 8 3 in Weight about 14 6 kg 32 lbs about...

Page 13: ...dsstaaten in bezug auf elektromagnetische Verträglichkeit und Produktsicherheit entsprechen Basado en la aproximación de las leyes de los Países Miembros respecto a la compatibilidad electromagnética y las Medidas de seguridad relativas al producto Questa dichiarazione è basata sulla conformità dei prodotti alle norme seguenti This declaration is based upon compliance of the products to the follow...

Reviews: