CLT- & CLX-1MC4

 

Functional Summary 

NOTE:  

Modules and terminal blocks must be 

installed into the lowest available spaces and 
continue toward the top of the enclosure. 

The Crestron

®

 1-Feed, 4-Motor Terminal Block and 

Module (CLT-1MC4 and CLX-1MC4, respectively), are 
considered a single entity and must be used together. 
They ship separately to permit termination of the field 
wiring to the CLT-1MC4 prior to installation of the CLX-
1MC4, as described in this guide. They can be mounted in 
any Crestron Automation Enclosure (CAEN-Series 
Enclosures). The terminal block is designed to terminate 
the circuit feed (HOT and NEUTRAL) and distribute the 
controlled circuits (LOAD) to the motors. The module 
connects to the terminal block and performs control of 
four bi-directional motors. The maximum load is 10 amps 
(1/2 HP) for any controlled circuit, limited to 16 amps 
total per module. The unit requires 120VAC 50/60 Hz, 1 
phase input voltage. An oversize heat sink dissipates heat 
efficiently. There are LEDs on the module to indicate 
communication to a Cresnet

®

 network, input power to the 

module, and output power to the load. 

Terminal Block & Module Locations (Single-wide Enclosure) 

MODULE

TERMINAL

BLOCK

GROUNDING

TERMINAL

BLOCK

 

 

Industry Compliance 

This product is Listed to applicable UL Standards and 
requirements by Underwriters Laboratories Inc.  

     

(E103692)

 

Terminal Block & Module Locations (Double-wide Enclosure) 

Installation 

GROUNDING TERMINAL BLOCKS

MODULE

TERMINAL BLOCK

(LEFT)

TERMINAL BLOCK

(RIGHT)

 

Terminal block and module must be mounted into a 
Crestron Automation Enclosure by a licensed electrician, 
in accordance with all national and local codes.  

CAUTION:  

This equipment is for indoor use only and 

needs to be air-cooled. Mount in a well-ventilated area. 
The ambient temperature must be 32

°

F to 104

°

F (0

°

C to 

40

°

C). The relative humidity must be 0% to 90% (non-

condensing).  

Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and 
right sides) of double-wide enclosures. Modules are 
installed along the right side of single-wide enclosures 
and side-by-side in the center of double-wide enclosures. 
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so 
that they can be properly wired. Refer to the illustrations 
shown in the next column when considering the location 
of terminal blocks and modules within an enclosure.  

Crestron Electronics, Inc.

 

Installation Guide – DOC. 5991B

 

15 Volvo Drive   Rockleigh, NJ 07647

 

(2002073)

 

Tel: 888.CRESTRON

 

01.06

   

Fax: 201.767.7576

  

Specifications subject to 

 

www.crestron.com

 

change without notice.

 

Summary of Contents for CLT-1MC4

Page 1: ...Industry Compliance This product is Listed to applicable UL Standards and requirements by Underwriters Laboratories Inc E103692 Terminal Block Module Locations Double wide Enclosure Installation GROUNDING TERMINAL BLOCKS MODULE TERMINAL BLOCK LEFT TERMINAL BLOCK RIGHT Terminal block and module must be mounted into a Crestron Automation Enclosure by a licensed electrician in accordance with all nat...

Page 2: ... since the modules and terminal blocks along the right side must be inverted when mounting CAUTION The jumper on the white section of the terminal block ties all neutrals together Do not remove the jumper Wiring Diagram of the Terminal Block to the Feed and Load s Right Side Double wide Enclosures NOTE Use copper conductors only rated 75 C NEUTRAL AREA FOR MODULE LOCATION LABEL JUMPER TERMINAL BLO...

Page 3: ...th and is the same color as the terminal to which it should be connected Wires are pre stripped to inch Tighten to 9 in lbs 3 If the module is being installed above another module within the enclosure attach the supplied module interconnect cable between the two modules The illustration below depicts the area within a double wide enclosure where the corners of four modules meet NOTE One wire on th...

Page 4: ...rials and workmanship under normal use for a period of three 3 years from the date of purchase from CRESTRON with the following exceptions disk drives and any other moving or rotating mechanical parts pan tilt heads and power supplies are covered for a period of one 1 year touchscreen display and overlay components are covered for 90 days batteries and incandescent lamps are not covered This warra...

Reviews: