The EBDHS-DD-LT30 PIR (passive infrared) presence 

detector provides automatic control of lighting loads with 

optional manual control. The EBDHS-DD-LT30  is a high 

sensitivity PIR detector suitable for high bay applications, 

such as warehouses and factories, and where high 

detection sensitivity is needed 
Output Channel 1 comprises a mains voltage relay capable 

of simple on/off switching, while Output Channel 2 provides 

dimmable control of either DALI or DSI type ballasts. 
Functioning as a presence detector, the unit can turn lights 

on when a room is occupied and off when the room is 

empty. Optional settings allow lights to be turned off in 

response to ambient daylight, or to implement a maintained 

illuminance (daylight harvesting) system. 
The flexibility of having two channels and two switch inputs 

allows the following example scenarios: 

 

Dim an outside row of luminaires whilst internal fittings 

are switched 

 

Provide absence detection for two separate channels 

 

Maintained illuminance system with manual up/down 

controls 

All functionality is fully programmable using an IR handset. 

Features 

Front features 

Back features 

Ceiling PIR HS presence detector – DALI / DSI, low temperature 

EBDHS-DD-LT30 

Product Guide 

Mounting Bezel 

Sensor Lens 

which covers... 

 

PIR Sensor 

IR Receiver 

Light Level Sensor 

Status LEDs 

Retaining Spring 

Retaining Spring 

Power Input 
& Switched 
Output Connector 

(Channel 1) 

Dimmable 

Control Output 

Connector 

(Channel 2) 

Switch Input 

Connector 

PIR Sensor 

Detects movement within the unit’s detection range, 
allowing load control in response to changes in occupancy. 

IR Receiver 

Receives control and programming commands from an  
IR (infrared) handset. 

Light Level Sensor 

Measures the overall light level in the detection area  

Status LEDs 

The LED flashes 

R

ed to indicate the following: 

Power Input & Switched Output Connector 

(Channel 1)

 

Used to connect mains power to the unit and to connect a 
switched load. 

Dimmable Control Output Connector 

(Channel 2)

 

Used to connect DSI/DALI controllable ballasts and 
transformers for dimmable loads. 

Switch Input Connector 

Two input terminals can be used to manually override the 
dimming levels and override the lights on or off. 

Walk Test LED active 

        

when movement is detected

 

Valid setting received 

 

Summary of Contents for EBDHS-DD-LT30

Page 1: ...n controls All functionality is fully programmable using an IR handset Features Front features Back features Ceiling PIR HS presence detector DALI DSI low temperature EBDHS DD LT30 Product Guide Mounting Bezel Sensor Lens which covers PIR Sensor IR Receiver Light Level Sensor Status LEDs Retaining Spring Retaining Spring Power Input Switched Output Connector Channel 1 Dimmable Control Output Conne...

Page 2: ...15m 30m 10m 20m 6m 12m 3m 8m Height Range Diameter 15m 40m 10m 26m 6m 16m 3m 9m Alignment marks The sensor head has 4 alignment marks These correspond to the 4 outer passive infrared sensors under the lens Use these marks to align with aisles and corridors to ensure the best detection characteristics See example overleaf ...

Page 3: ...attern for narrowing the detection diameter Lateral tear pattern for making a slot style detection shape Applications Aisles Masking shields trimmed for aisle shaped detection Narrow detection Masking shields trimmed for a narrow beam of detection 1 2 3 4 4 3 2 1 Slot number Masking shield coverage 1 45 2 32 3 22 4 11 Slot number 2 3 4 Diameter number Masking shield coverage 1 89 2 63 3 45 4 32 5 ...

Page 4: ... ambient light level using the Lux On Level and Lux Off Level parameters Maintained Illuminance The detector measures the overall light level in the detection area and calculates the correct output for the luminaires to achieve a preset lux level maintained illuminance Sensor functionality The UNLCDHS has the ability to read back the settings stored in a device To read back individual parameters N...

Page 5: ...n in The EBDHS DD LT30 is designed to be mounted using either Flush fixing or Surface fixing using the optional Surface Mounting Box part no DBB Both methods are illustrated below Use the supplied gasket to ensure IP rating not compatible with Surface Mounting Box part no DBB Assembly Remove connector cover 1 2 Push in sensor head connector to mating socket on power supply unit Locate sensor head ...

Page 6: ...tch to turn back on Press and hold up switch to dim up press and hold down switch to dim down Turns off after occupancy Configured to absence detection Press and release up switch to turn on Maintains illuminance Press and release down switch to turn off Press and hold up switch to dim up press and hold down switch to dim down Turns off after occupancy Channel mode Set to Switch and dim together S...

Page 7: ...Set to 1 position switch separate Functions Switches both channels with occupancy Maintains illuminance dims and switches the dimming channel using optional centre biased retractive switch Configured to presence detection Turns on automatically with occupancy Maintains illuminance dimming channel only Press and release down switch to turn off Press and release up switch to turn back on Press and h...

Page 8: ...ger than the Time Out Period Ensure that the sensor is not adjacent to circulating air heaters or lamps Fault finding Functions Switches channel 1 only with occupancy optional override switch No dimming output Configured to presence detection Turns on automatically with occupancy Press and release down switch to turn off Press and release up switch to turn back on Turns off after occupancy Configu...

Page 9: ...n Sets the ballast control protocol to be used by the output channel Sensitivity 9 1 5 9 3 6 8 Sensitivity level for detecting movement 1 low sensitivity 9 high sensitivity Defaults D Returns the unit to the default settings Burn in 0 0 50 100 Determines how long the output will be at 100 so that lamps burn in The burn in time is not affected by power supply interruptions Presence Absence Presence...

Page 10: ...e or presence mode if the lights were out because of the lux level they will be immediately turned on again for at least the Lux Time Power Up State On On or Off Select No for a 30 second delay on start up If Yes is selected there will be no delay on start up and the detector will always power up detecting Disable Detector N Y or N Disables detection leaving the relay output permanently off with t...

Page 11: ...ights from being turned on by movement Light Level maintained illuminance 600 1 to 998 999 disabled Sets a target light level to be maintained by the lighting system Load Type DALI DSI DALI DALI On Sets the ballast control protocol to DSI Sets the ballast control protocol to DALI DALI On provides a permanent voltage to DALI ballasts when DALI has not been implemented correctly in the ballast Maxim...

Page 12: ...as if mains potential Use mains rated wiring Terminal Capacity 2 5mm2 Temperature 30ºC to 35ºC Humidity 5 to 95 non condensing Material casing Flame retardant ABS and PC ABS Type Class 2 IP rating 40 without gasket 65 with gasket Compliance EMC 2004 108 EC LVD 2006 95 EC Technical data Part numbers C P Electronics Ltd Brent Crescent London NW10 7XR United Kingdom Tel 44 0 333 900 0671 Fax 44 0 333...