background image

1

We reserve the right to make changes without notice

T 334 - GSM 622  C1  Eng.  

04.02.10 LB  

REV. 0

2

REMOTE GSM DUAL-BAND MODEM

GSM 622 

C1  Eng.

• Uses digital GSM 900/1800 MHz digital telecommunications

• Communicates with modems :

– MCV 711 (discontinued) 

– MCV 712 (in replacement of MCV 711)

– GSM 714 (to be used only in non-central, provisional stations, with laptop PCs)

• Supplied with RF Dual Band antenna

• C-Bus communication speed adjustable from 1200 to 9600 baud (factory setting: 1200)

• Power supply 230 V~; DIN rail mounting

1. APPLICATION

GSM 622 modem is suitable for “TELECOSTER” telemanagement systems, installed in a remote position (e.g. 

central heating site) for data communication to and from the central sites.

2. FUNCTIONS

GSM 622 modem is an E-GSM dual-band modem (900/1800 MHz) with a transmission speed configurable from 

2400 to 14400 bps in non-transparent mode (with error correction).

It cannot communicate with modems having a transmission speed below 2400 bps (e.g. MCT 710).

It supports AT+ controls in conformity with standard ETSI GSM 07.05 & 07.07 & V.25ter.

The digital interface conforms to the ITU-T.V24 and V.28 recommendations.

It incorporates autodiagnosis that indicate the presence of the GSM signal.

Every six hours resets itself automatically.

It is possible to reset manually by connecting a push-button switch to terminals E-D.

3. REFERENCE STANDARDS

The protocol details are based on the following standards:

•1999 /5/CE of March 9 1999, R & TTE, as having been designed in conformity with the requirements of following 

Reference Standards : EN 60950, EN 301 489-1, EN 301 489-7, EN 301-419-1, EN 301-511 

4. ACCESSORIES

 

Code 

Description 

Data sheet

 

APA 812

 

5 meter cable for extending antenna for GSM 622 

 

APA 812 C1

 

4 meter cable for extending antenna for GSM 622 C1 

 

ACS 232

 

RS 232 cable with male DB 9. 

 

ALM 688

 

Backup battery 

T 350 

 

TCB 908

 

Tester for connections and telephone calls  

5. TECHNICAL DATA

• Electrical & mechanical: 

Power supply 

 230 V ~ ± 10 % 

Frequency 

50…60 Hz

Consumption 

11 VA

Electrical protection 

IP 40

Construction standard 

Italian Electrotech. Committee (CEI)

Ambient temperature: 

operating 

0…+ 45 °C

storage 

– 25…+ 60 °C

Dimensions 

105 x 115 x 71.5 mm (L x W x H)

Weight 

0.7 kg 

• Transmission data: 

Data format 

asynchronous start-stop

Character data 

 8 bits data, 1 bit stop  

 

none

Transmission speed 

 1,400...14,400 bps

RF antenna  

 SMA connector

• C-Bus communication: 

Speed adjustable  

from 1.200 to 9.600 baud

via SWC 701 Remote Management software

C-Bus line with 1.5 mm

cable 

max. 2000 metres

Max. number of slaves  

100

T 334

04.02.10  LB

REV. 02

Summary of Contents for GSM 622

Page 1: ...ate the presence of the GSM signal Every six hours resets itself automatically It is possible to reset manually by connecting a push button switch to terminals E D 3 REFERENCE STANDARDS The protocol details are based on the following standards 1999 5 CE of March 9 1999 R TTE as having been designed in conformity with the requirements of following Reference Standards EN 60950 EN 301 489 1 EN 301 48...

Page 2: ...ended RS232 By inverting Tx and Rx it is possible to connect Coster devices DIN format provided with a serial input C BUS Parallel output for connecting to Coster devices fitted with C BUS parallel input 1 2 3 4 5 6 7 1 Power 2 Presence signal 3 Reset modem 4 Connection 5 Data transmission 6 Data reception 7 Socket for TCB 908 tester 1 Protective cover for electronic components 2 Base with transfor...

Page 3: ...be used connected to a PC The desired speed can be selected via the SWC 701 Remote Management software The C Bus line can be up to 2000 metres long with 100 slave units at the most regardless of transmission speed 12 SIM CARDS 12 1 Purchase of SIM CARD You are advised to purchase the SIM card from your chosen GSM network service provider for business networks When purchasing it is essential to req...

Page 4: ...ENSIONS Update diagram Overall dimensions 02 03 09 AM 01 3 11 3 0 GSM network signal strength indicator Aggiornati dati del segnale di campo 04 02 10 AM 02 1 and 3 5 and 11 C Bus transmission speed updated COSTER TECNOLOGIE ELETTRONICHE S p A Sede Legale 20132 Milano Via San G B De La Salle 4 a E mail info coster info Web www coster eu COSTER CONTROLLI TEMPERATURA ENERGIA Head Office Sales Via San ...