HEATER

 

CONTROLLER

Code

Function

Setting

Default

TS1

Temperature  

Set Value

-50° to 37.7°C 

/ -58° to 99.9°F

25°C / 77°F

DS1

Heating  

Differential Value

0.3° to 15°C 

/ 0.3° to 15°F

2°C / 2°F

CA

Temperature  

Calibration

-15° to 15°C 

/ -15° to 15°F

0°C / 0°F

CF

Display in  

°F or °C

°C / °F

°C

MENU KEY

When TR=0 (default)

SETTINGS

Temperature Control Range Setting (TS1, DS1)

When the controller is working normally, the 

PV

  

window displays current measured temperature, 

while the 

SV

 window displays set temperature.

When 

PV

 (measured temperature) ≤ 

TS1

 (set  

temperature)

-DS1

 (temperature differential value),  

system will enter heating status, the 

Heater  

Indicator Lamp

 will turn on, and heating relay  

will start working; when 

PV

 ≥ 

TS1

, the 

Heater  

Indicator Lamp

 will turn off, and heating relay 

will stop working. 
For example, if 

TS1 

= 78.5°F, 

DS1

 = 0.5°F, when 

measured temperature is lower than or equal to 

78.0°F 

(TS1-DS1)

, heater turns on; when the  

temperature reaches 78.5°F, heater turns off.

Temperature Calibration (CA)

When there is deviation between measured  

temperature and actual temperature, use  

temperature calibration function to align the  

measured temperature and actual temperature.  

The corrected temperature is equal to temperature 

before calibration plus corrected value (corrected 

value could be positive value, zero, or negative value).

Display in Fahrenheit or Celsius unit (CF)

Temperature can be set to display in Fahrenheit or 

Celsius according to preference. Default setting is to 

display in Celsius. To display in Fahrenheit, set 

CF

 

value to F.

Attention:

 when 

CF

 value is changed, all other  

settings will be reset to factory settings.

ERROR DESCRIPTION

Sensor fault alarm

 

If the controller detects a fault in the temperature 

sensor, either due to a short circuit or open loop,  

the controller will initiate sensor fault mode, and 

cancel all the actions. An alarm will sound, and LED 

will display “ER”. Buzzer alarm can be dismissed by 

pressing any key. After fault is solved, the system will 

return to normal operation. 

Over-temperature alarm

If the measured temperature exceeds the set point 

(TS) by more than 3°F, the controller will initiate 

over-temperature alarm mode, and cancel all actions. 

An alarm will sound and LED will display “HL”.  

Buzzer alarm can be dismissed by pressing any key. 

When the measured temperature returns to within 

3°F of the set point, the system will resume normal 

operation.