background image

 

Page 

1 of 2

FUSION-TEC

TM

/LV1000 Free Cooling Unit System

Quick Start Guide

The LV1000 controller and TEC-EYE

TM

 hand-held diagnostic tool will both be used to set up the Bard Free Cooling Unit 

system. The TEC-EYE diagnostic tool is shipped inside the controller. Use password 1313. See FUSION-TEC/LV1000 
System Installation Instructions 2100-674, FUSION-TEC Service Instructions 2100-670 or LV1000 Service Instructions 
2100-673 if more information is needed.

SYSTEM SET-UP

Set up and configuration must be done to each wall-
mount unit using the TEC-EYE hand-held diagnostic tool. 
Use the LV1000 controller for the remaining steps.

IMPORTANT:

 

When working with circuit board 

components, Bard recommends the use of 

an anti-static wrist strap to prevent static 

electricity shorts to electronic controls.

Address wall unit and select unit of measure (UOM) and 

economizer control type (TEC-EYE)

The address of the unit being looked at will be listed in 
the upper right hand corner on the status screen. The 
available addresses are 1-4.
1.  Connect TEC-EYE

TM

 to wall-mount unit.

2.  Press MENU key to access the Main Menu screen. 
3.  Press UP or DOWN keys and ENTER key to enter 

password 1313.

4.  Press UP or DOWN keys to scroll to 

Sys Config

; press 

ENTER key.

5.  Press UP or DOWN keys to scroll to 

Unit Setup (A1)

 

screen.

6.  Press UP or DOWN keys to change address to value 

between 1 and 4.

 

NOTE:

 Each unit must have a unique address for the 

communication to work properly. Bard also 

recommends labeling each unit for ease in 

identification.

7.  Press ENTER key to save and scroll to 

UOM

8.  If desired, press UP or DOWN keys to change the 

value from 

USA

 to 

SI

NC

,

 LON

CAN

 or 

UK

. Units 

are preconfigured for each selection.

9.  Press ENTER key to save and move the cursor back 

to the top left position.  

10. Press DOWN key to navigate to 

Economizer Setup 

(A2)

 screen.

11. Press ENTER key to scroll to 

Type

12. Press UP or DOWN keys to change economizer type 

to 

None

Drybulb

Temperature and Humidity

 or 

Enthalpy

.

13. Press ENTER key to save and move the cursor back 

to the top left position. 

Execute a run test on each unit to verify the equipment is 

functioning correctly (TEC-EYE)

1.  Use UP or DOWN keys to scroll to 

Run Test (A10)

 

screen.

2.  Press ENTER key to scroll to 

Run Test Enable

 

parameter.

3.  Use UP or DOWN key to change value to 

ON

. The run 

test will begin.

Run Test Approximate Timings (in Minutes)

0:00  •  Blower starts.
 

•  Damper begins to open to damper test volts 

parameter. To verify damper operation, open unit 
side door. Inspect upper and lower blades.

2:30  •  Damper closes. Compressor Stage 1 turns on. 

Condenser fan may also turn on depending on 
ambient conditions.

3:00  •  Compressor Stage 2 turns on.
3:30  •  Compressor turns off. Condenser fan turns off (if 

applicable). 

 

•  Heat turns on.

4:30  •  Heat turns off.
5:30  •  Blower turns off.

Clear unit alarm logs

To clear the wall-mount unit alarm logs:
1.  Press MENU key to go to the Main Menu screen.
2.  Use UP or DOWN keys and ENTER key to enter 

password 1313.

3.  Press UP or DOWN keys to scroll to 

Settings

; press 

ENTER key.

4.  Press UP or DOWN keys to scroll to 

Initialization

press ENTER key.

5.  Press ENTER key to scroll to 

Delete Alarm Logs?

6.  Press UP or DOWN key to value to 

YES

; press ENTER 

key.

7.  Press ESCAPE key several times to return to Main 

Menu screen.

After first unit has been set up and configured, follow the 
above steps to set up and configure the remaining units.

Set LV Controller Timezone and Date/Time  

(LV Controller)

1.  Press MENU key to access the Main Menu screen.

Manual 2100-675 

Date 6-2-17

Reviews:

Related manuals for Fusion-Tec