background image

Configurable temperature Node with RTD inputs (powered by external battery module only)

The SureCross

®

 wireless system is a radio frequency network with integrated I/O that can operate

in most environments and eliminate the need for wiring runs. DX99 wireless networks are formed
around a Gateway, which acts as the wireless network master device, and one or more Intrinsical-
ly Safe Nodes.

• Wireless industrial I/O device with up to four 3-wire Pt100 RTDs; other types are available with

configuration

• FlexPower

®

 power input requires power from the DX81H Battery Supply Module

• DIP switches for user configuration
• Frequency Hopping Spread Spectrum (FHSS) technology and Time Division Multiple Access

(TDMA) control architecture ensure reliable data delivery within the unlicensed Industrial, Sci-
entific, and Medical (ISM) band

• Transceivers provide bidirectional communication between the Gateway and Node, including

fully acknowledged data transmission

• Lost RF links are detected and relevant outputs set to user-defined conditions
• DX99 Polycarbonate housings are certified for use in Class I, Division 1, Groups A, B, C, D;

and Zone 0 (Category 1G) when properly installed in accordance with the National Electrical
Code, the Canadian Electrical Code, or applicable local codes/regulations

For additional information, updated documentation, and accessories, refer to Banner Engineering's website, 

www.bannerengineer-

ing.com/surecross

.

Model

Frequency

I/O

DX99N9X2S0N0R4X0A0

900 MHz ISM Band

Inputs: Four 3-wire RTD

DX99N2X2S0N0R4X0A0

2.4 GHz ISM Band

Internal antenna models are also available. For more information, contact your local Banner Engineering Corp. representative.

WARNING: Not To Be Used for Personnel Protection
Never use this device as a sensing device for personnel protection. Doing so could lead to serious
injury or death.
 This device does not include the self-checking redundant circuitry necessary to allow its
use in personnel safety applications. A sensor failure or malfunction can cause either an energized or de-
energized sensor output condition.

SureCross User Configuration Tool

The User Configuration Tool (UCT) offers an easy way to link I/O points in your wire-
less network, view I/O register values graphically, and set system communication pa-
rameters when a host system is not part of the wireless network.
The UCT requires a special USB to RS-485 (model number BWA-UCT-900 for 1 Watt
radios, BWA-HW-006 can be used for all other radios) converter cable to pass infor-
mation between your computer and the Gateway. Download the most recent revi-
sions of the UCT software from Banner Engineering's website: 

http://www.banneren-

gineering.com/wireless

.

Setting Up Your Wireless Network

To set up and install your wireless network, follow these steps.

Disconnect the power from your SureCross devices.

1. Configure the DIP switches of all devices.
2. Connect the sensors to the SureCross devices.

SureCross DX99 FlexPower RTD Node (Polycarbonate

Housing)

 

 

P/N 142499 Rev. E

6/24/2013

0 142499

7

Summary of Contents for SureCross DX99 FlexPower DX99N9X2S0N0R4X0A0

Page 1: ...ineer ing com surecross Model Frequency I O DX99N9X2S0N0R4X0A0 900 MHz ISM Band Inputs Four 3 wire RTD DX99N2X2S0N0R4X0A0 2 4 GHz ISM Band Internal antenna models are also available For more informati...

Page 2: ...sing the Internal DIP Switches To access the internal DIP switches follow these steps 1 Unscrew the four screws that mount the cover to the bottom housing 2 Remove the cover from the housing without d...

Page 3: ...ge C Pt100 DIN 0 00385 328 to 900 F 200 to 482 C Cu 10 Ohm alpha 0 00427 328 to 500 F 200 to 260 C For the copper RTD the best accuracy is when measuring between 50 to 150 C 58 to 302 F Below this ran...

Page 4: ...TD 3 F C 1638 3 1638 4 32768 32767 A3 A3 DI1 6 6 6 Node 16 RTD 4 F C 1638 3 1638 4 32768 32767 A4 A4 DI2 7 7 7 Node 16 Reserved 8 8 8 Node 16 Device Message 15 15 15 Node 16 Control Message 16 16 16 N...

Page 5: ...ate 16 seconds Accuracy 0 1 of full scale Resolution 0 1 C 15 bit Refer to the SureCross DX80 Wireless I O Network Product Man ual p n 132607 for installation and waterproofing instructions Op erating...

Page 6: ...point ground system to ensure no ground loops are created No surge suppressor can absorb all lightning strikes do not touch the SureCross device or any equipment connected to the SureCross device duri...

Page 7: ...ICULAR PURPOSE AND WHETHER ARISING UNDER COURSE OF PERFORMANCE COURSE OF DEALING OR TRADE USAGE This Warranty is exclusive and limited to repair or at the discretion of Banner Engineering Corp replace...