background image

deutsch

IO-Link-Konfiguration

english

IO-Link Configuration

BIS U-4A7-082-01C-07-S4
BIS U-4A7-082-11C-07-S4
BIS U-4A7-082-21C-07-S4

Summary of Contents for BIS U-4A7-082-01C-07-S4

Page 1: ...deutsch IO Link Konfiguration english IO Link Configuration BIS U 4A7 082 01C 07 S4 BIS U 4A7 082 11C 07 S4 BIS U 4A7 082 21C 07 S4...

Page 2: ...www balluff com...

Page 3: ...BIS U 4A7 082 01C 07 S4 BIS U 4A7 082 11C 07 S4 BIS U 4A7 082 21C 07 S4 IO Link Konfiguration deutsch...

Page 4: ...www balluff com...

Page 5: ...ionsparameter 18 5 Prim re Ger tefunktionen 19 5 1 Identifikation Identification 19 5 2 Ger teerkennung Device Discovery 20 5 3 Prozessdaten Process Data 21 5 4 RFID Parameter RFID Parameters 22 5 5 S...

Page 6: ...ands 56 7 4 Variantenkonfiguration Variant Configuration 57 7 5 Pinzuweisung Pin Assignment 59 7 6 Bedeutung der LED Zust nde und Konfiguration LED Meaning and Configuration 61 7 7 Prozessdateninforma...

Page 7: ...rrechtlich gesch tzt Alle Rechte einschlie lich der Vervielf ltigung Ver ffentlichung Bear beitung und bersetzung bleiben vorbehalten 1 2 Verwendete Symbole und Konventionen Einzelne Handlungsanweisun...

Page 8: ...er und Device aufbauen zu k nnen fragt der Master zu Beginn der Kommunikation einige wichtige Kommunika tionsparameter des Ger ts ab Durch die Parameter werden Einstellungen f r die Kommunikation in d...

Page 9: ...wenn sich Daten gewollt ver ndern oder Down loads wenn z B ein falsch parametriertes Ger t ange schlossen wird Das System aus Master und Device stellt so einen Ger teaustausch ohne die Notwendigkeit e...

Page 10: ...ehe Seite 57 Pinzuweisung Pin Assignment siehe Seite 59 Bedeutung der LED Zust nde und Konfiguration LED Meaning and Configuration siehe Seite 61 Prozessdateninformation und konfiguration Process Data...

Page 11: ...TRING n a z B BIS U 4A7 082 01C 07 S4 Product Text 0x0014 20 0 R 59 Byte STRING n a RFID UHF read write head IO Link stainless steel M30 Condition monitoring Serial Number 0x0015 21 0 R 16 Byte STRING...

Page 12: ...Byte UINT8 Ja 16 Max Lesel nge 14 R W 1 Byte UINT8 Ja 16 Automatisches Scan nen 15 R W 1 Byte UINT8 Ja 0 off Auto Scan Aufl sung 16 R W 1 Byte UINT8 Ja 50 SafeMode aktivieren 17 R W 1 Byte UINT8 Ja 1...

Page 13: ...te FLOAT32 n a Maximum 2 R 4 Byte FLOAT32 n a Average 3 R 4 Byte FLOAT32 n a Moving Average 4 R 4 Byte FLOAT32 n a Number Of Samples 5 R 4 Byte UINT32 n a Status 6 R 1 Byte UINT8 n a Betriebsstundenz...

Page 14: ...tate 1 R 1 Byte UINT8 ENUM n a Time 2 R 4 Byte UINT32 n a Interne Temperatur Device Temperature 0x0052 82 0 R 10 Byte n a Device Temperature 1 R 2 Byte INT16 n a Minimum Device Temperature Since Reset...

Page 15: ...e FLOAT32 n a Y Reference Value 2 R 4 Byte FLOAT32 n a Z Reference Value 3 R 4 Byte FLOAT32 n a Inclination Deviation Value 0x2154 8532 0 R 1 Byte UINT8 n a Vibrationsdetektion Vibration Level 0x210E...

Page 16: ...e UINT16 n a Resetbefehle System Commands 0x0002 2 0 W 1 Byte UINT8 n a Variantenkonfiguration Device Variant 0x0055 85 0 R W 2 Byte UINT16 ENUM Nein 0x01 Standard Pinzuweisung Pin 2 Function 0x0093 1...

Page 17: ...tialisierungen neu durchgef hrt ohne dass eine nderung der Parameterwerte erfolgt siehe Kapitel 7 3 auf Seite 56 0x81 129 Application Reset siehe Kapitel 7 3 auf Seite 56 0x82 130 Reset Factory Settin...

Page 18: ...ce is operating properly 0x8CFF 36095 Warnung Niedriges Signalqualit tsniveau 0 Device is operating properly 0x8D07 36103 Warnung Die Berechnung der Grundstatistik wurde automa tisch gestoppt um einen...

Page 19: ...d 0x8D24 36132 Warnung Parameterschreibfehler dient nur zur Information 0 Device is operating properly 0x8D25 36133 Fehler Parameter nicht konsistent Grundeinstellungen werden verwendet Service ist er...

Page 20: ...060301 Tab 4 1 Kommunikationsparameter Um die grundlegenden Kommunikationsparameter flexibel an die Anwendung anzupassen k nnen auch andere Ger tevarianten eingestellt werden siehe Tab 4 2 auf Seite 1...

Page 21: ...n Tag 0x0019 25 0 R W 32 Byte STRING Ja Location Tag 0x001A 26 0 R W 32 Byte STRING Ja Product Type Code 0x0700 1792 0 R 64 Byte STRING n a z B BIS U 4A7 082 01C 07 S4 Product Order Code 0x0701 1793 0...

Page 22: ...ung ISDU Device Discovery Timeout Der Parameter Device Discovery Timout stellt die Zeitdauer des Device Discovery Signals ein das ber LEDs ange zeigt wird Der Wert wird in Minuten angegeben Es ist der...

Page 23: ...Ger tefunktionen Fortsetzung 5 3 Prozessdaten Process Data 5 3 1 Beschreibung In den Prozessdaten wird ein Protokoll bertragen Funktionsweise und verf gbare Befehle siehe Betriebsan leitung BIS U 4A7...

Page 24: ...der Sen deleistung beim Schreiben 9 R W 1 Byte UINT8 Ja 8 Anzahl Wiederholungen 10 R W 1 Byte UINT8 Ja 5 Aktive Kan le 11 R W 4 Byte UINT32 Ja 0x0000000F BlockWrite aktivieren 12 R W 1 Byte UINT8 Ja 0...

Page 25: ...chen Ausfalls Diese Reaktion wird ausgel st wenn die Signalqualit t unter einen einstellbaren Schwellenwert f llt und gibt Entwar nung wenn wieder ein zufriedenstellendes Niveau der Signalqualit t err...

Page 26: ...Der Schwellenwert f r niedrige Signalqualit t kann einge stellt werden um die aktuelle Signalqualit t zu berwa chen Er wird als Wert zwischen 0 und 100 in Prozent angezeigt Wenn der aktuelle Signalqu...

Page 27: ...eshold auf Default 0 zur ck Dadurch ist das Feature deaktiviert und die Evaluation auf dem Index 0xCF Subindex 2 ergibt immer FALSE Tab 5 7 Signalqualit t System Commands F r eine bersicht aller Syste...

Page 28: ...Eingang Maximum Minimum Berechnung von Minimum Maximum und Durchschnitt Wie in Bild 6 1 dargestellt wird die Berechnung durch den Startbefehl eingeleitet und durch den Stoppbefehl gestoppt Die Werte...

Page 29: ...n Fensters Bild 6 3 Gleitender Durchschnitt Fensterbreite 9 Wert periodisches Fenster Periodischer Fensteransatz Beispiel 6 1 3 Process Data Object ID Name Beschreibung Richtung 0x0053 83 Minimum Mini...

Page 30: ...M Nein Sekunden Time Period Value 3 R W 2 Byte UINT16 Nein 1 Moving Average Window Unit 4 R W 1 Byte UINT8 ENUM Nein Messwerte Moving Average Window Value 5 R W 2 Byte UINT16 Nein 100 Statistics Data...

Page 31: ...den Durchschnitt f r jeweils 100 Messwerte zu berechnen kann als Einheit Messwerte samples gew hlt werden Wert Bedeutung Beschreibung 0x01 1 Seconds Sekunden 0x02 2 Minutes Minuten 0x03 3 Hours Stunde...

Page 32: ...tem Commands Command Wert Ger teaktion 0xA7 167 Statistics Reset Setzt alle Aus gangsparameter auf 0 und alle Benutzereinstellungen auf die Defaultwerte zur ck 0xA8 168 Statistics Start Min Max Avg St...

Page 33: ...ent meldet die Zeit berschreitung der Minimalwert Maximalwert Durch schnitt Berechnung Es meldet keine Zeit berschreitung f r die Berechnung des gleitenden Durchschnitts da sich der Zeitablauf des gle...

Page 34: ...hoher Gesamtbetriebs stundenwert auf eine intensive Nutzung eines Ger ts und eine m gliche Verschlechterung der Leistung hin Einem Ausfall kann pr ventiv durch einen Austausch entgegenge wirkt werden...

Page 35: ...rameter speichert den Wert der Betriebsstunden seit der letzten Inbetriebnahme in Sekunden Total Operating Hours Dieser Parameter speichert den Wert der Betriebsstunden seit der ersten Inbetriebnahme...

Page 36: ...etzt Custom Operating Hours und Operating Hours Saving Mode auf den Defaultwert zur ck 0xA5 165 Maintenance Reset Setzt Custom Operating Hours auf den Defaultwert zur ck Tab 6 13 Betriebsstundenz hler...

Page 37: ...te UINT32 n a Custom Boot Cycle Counter 2 R 4 Byte UINT32 n a Tab 6 15 Betriebsstartz hler ISDU Der maximal speicherbare Z hlerwert betr gt 1 000 000 und bedeutet bei einer An und Abschaltung alle 12...

Page 38: ...4 TRUE berlast oder Kurzschluss an Pin 4 erkannt Eingang 0x0016 22 Overload short circuit pin 2 TRUE berlast oder Kurzschluss an Pin 2 erkannt Eingang 0x0017 23 Undervoltage TRUE das Spannungsniveau...

Page 39: ...ung pr fen 2 Out of Specification 0x5111 20753 Warnung Unterschreitung der prim ren Versorgungsspannung Abweichungen in der Versorgung pr fen 2 Out of Specification 0x8D0B 36107 Warnung berlast oder K...

Page 40: ...gung w hrend einer Extrembedingung unterbrochen kann der Zeitz hler einen Fehler von maximal 180 Sekunden haben 6 5 3 Process Data Object ID Name Beschreibung Richtung 0x0041 65 Lifetime Extreme Eine...

Page 41: ...t in Sekunden in der sich das Ger t in einer Extrembedingung befunden hat ausgelesen werden 6 5 5 Events Event Code Event Typ Event Beschrei bung Abhilfe Device Status 0x8D13 36115 Warnung Eine oder m...

Page 42: ...ie eingestellten Kun denlimits Index 0x0053 Gesetzt wenn au erhalb der Limits Eingang 0x004F 79 Temperature Status Device Limits Temperaturstatus Warnung bezogen auf die Ger telimits Gesetzt wenn au e...

Page 43: ...ger tespezifischen Temperaturgrenzen betrie ben Gefahr von Ger tesch den 4 Failure 0x4210 16912 Warnung Device Temperature Overrun Clear Heat Of Source Gefahr von Ger teschaden Das Ger t ist zu hei Hi...

Page 44: ...nt werden ob das Ger t seine urspr ngliche Einbauposition ge ndert hat und so z B eine m gliche Dejustage und daraus resultierende Fehlfunktionen fr hzeitig entdeckt werden Die Konfiguration kann ber...

Page 45: ...ion und Einstellhilfe Process Data 6 7 4 ISDU Name Index Sub index Zugriff L nge Datentyp Data Storage Default Inclination Alarm Configuration 0x2151 8529 0 R W 2 Byte Ja Inclination Alarm Enable 1 R...

Page 46: ...erst berechnen wenn die Referenzposition eingelernt ist 6 Sekund re Ger tefunktionen Fortsetzung Alarm Inclination Status Bit Description 0 Device ist in seiner eingelernten Position Orientie rung 1...

Page 47: ...Dieses Event zeigt dass das Ger t seine urspr ngliche Position Schwellenwert ber cksichtigen verloren hat Die Befestigung des Ger ts sollte berpr ft werden Das Device ist noch funktionsf hig aber die...

Page 48: ...ereich der Schwingungs beschleunigung 0 16 g Messfehler 10 1 Der Schwinggeschwindigkeitsbereich ist frequenzabh ngig Der angegebene Wert ist das theoretische Maximum innerhalb dieses Frequenzbereichs...

Page 49: ...llst n dige berwachungsfunktionalit t bietet wobei die Zustands berwachung die prim re Funktion des Sensors ist und dieser am Objekt oder an der Maschine montiert wird Bild 6 6 Trendanalyse 6 8 3 Proc...

Page 50: ...ert Ziel Entprellung und Vermeidung von Sto werten Einheit mm s Minimalwert 0 0 Maximalwert 1770 0 Vibration Alarm Status Das Status Flag ist TRUE wenn die Vibration den Alarm schwellenwert berschreit...

Page 51: ...rocess Data Siehe auch Kapitel Prozessdatenprofile auf Seite 8 6 9 3 ISDU Name Index Subindex Zugriff L nge Datentyp Data Storage Default Humidity 0x005C 92 0 R 9 Byte n a Humidity Bad 1 R 1 Byte BOOL...

Page 52: ...vent Beschreibung Abhilfe Device Status 0x8D12 36114 Warnung berschreitung der festgelegten Schwelle der ger teinternen Feuchtigkeit Installation und Umgebungsbedingungen pr fen 1 Maintenance Required...

Page 53: ...her begrenzt ist wird die Anzahl in jedem Abschnitt mit einem Z hler berwacht Alle Datenabschnitte sind mit einer CRC32 Pr fsumme gesch tzt 6 10 2 Events Event Code Event Typ Event Beschreibung Abhilf...

Page 54: ...UE wenn ein Fehler im Ger t vorliegt Diese Information ist gekoppelt mit dem Device Status 4 Failure der durch verschiedene Ger tefunktionen bzw Diagnose meldungen ausgel st werden kann Sobald der Feh...

Page 55: ...en Eine Neukonfiguration Zur cksetzen auf Werkseinstellungen kann weiterhelfen Sonst muss der Balluff Service kontaktiert oder das Ger t ausge tauscht werden Tab 7 3 Device Status 7 1 5 Detailed Devic...

Page 56: ...yte UINT16 Nein 0 Event Code Suppression Teach in 0x0072 114 0 W 2 Byte UINT16 n a Event Code Suppression Delete 0x0073 115 0 W 2 Byte UINT16 n a Tab 7 5 Diagnoseunterdr ckung ISDU 7 2 3 Diagnosis Lev...

Page 57: ...r Defaultwert und wird als FREE interpretiert Jede Event Meldung ist wie folgt aufgebaut Byte1 MSB Byte0 LSB Event Code High Byte Event Code Low Byte Tab 7 7 Diagnoseunterdr ckung Event Message Suppre...

Page 58: ...1 2 durchgef hrt R cksetzen aller Parameter und Ger teeinstellungen auf Standardwerte mit Ausnahme der Identifikations und Tagging Parameter Keine R cksetzung der Konfiguration der Ger tevariante DS...

Page 59: ...Parameter wird durch einen Reset nicht ver ndert Nach einer Variantenumstellung kann es zu einer inkonsistenten Konfiguration kommen da es keine automatische Umstellung von Parametern gibt Daher wird...

Page 60: ...yte UINT16 ENUM Nein 0x01 Standard Tab 7 10 Variantenkonfiguration ISDU Device Variant Folgende Ger tevarianten sind vef gbar Wert Bedeutung Beschreibung 0x0001 1 Standard 32 Byte Prozessdaten RFID 0x...

Page 61: ...men nur zur Anwendung wenn der Pin als Digitalausgang oder Digitaleingang konfiguriert wurde Tab 7 12 Pinzuweisung ISDU Behavior IO Link Mit Behavior IO Link kann das Verhalten des Pins w hrend einer...

Page 62: ...idity Bad aktiv ist siehe Kapitel 6 9 auf Seite 49 0x0037 55 Inclination Alarm Status Schaltet wenn Neigungsalarm ausgel st wird bzw Inclination Alarm Status aktiv ist siehe Kapitel 6 7 auf Seite 42 0...

Page 63: ...uired Blau statisch Es muss eine Wartung durchgef hrt werden Overload Orange blinkend 3 Hz berlast an Pin 2 Pin 4 ist erkannt worden Bad Signal Quality Orange blinkend 1 Hz Schlechte Signalqualit t di...

Page 64: ...Das Objekt wurde erfasst Schaltpunkt ist aktiv Communication Gr n wechselnd mit LED aus im Verh ltnis 10 1 1 s Periode IO Link Kommunikation ist aktiv Das Ger t ist bereit Ready Diagnosis On Gr n stat...

Page 65: ...lerhaften Daten werden die Daten nicht ung ltig gekennzeichnet sondern durch Substitutionswerte bzw Fehlercodes ersetzt Dies ist bei der Auswertung zu ber cksichtigen Ung ltige Ausgangsdaten vom Maste...

Page 66: ...rved Byte 2 TypeLength 0 255 Bit Byte 3 Bit offset 0 255 Bit Tab 7 24 Prozessdateninformation und konfiguration PD Description 7 Systemfunktionen Fortsetzung Last Valid Process Data Dieser Parameter z...

Page 67: ...r Device Status siehe Kapitel 7 1 auf Seite 52 des Ger ts Failure ist In allen anderen Zust nden werden Ersatzwerte f r die Daten ausgegeben deren Inhalt nicht korrekt ausgegeben werden kann PDOutputs...

Page 68: ...Der Parameter kann ber Subindex 0 gelesen werden und besteht aus mehreren Profil Indizes und Funktionsklassen jeweils 16 Bit Werte Ist eine Profil ID angegeben bedeutet das dass alle enthaltenen Funkt...

Page 69: ...h tzt Im Falle eines besch digten Speichers gibt der Parameterma nager das Event Parameters not consistent aus 7 9 2 Events Event Code Event Typ Event Beschreibung Abhilfe Device Status 0x8D24 36132 W...

Page 70: ......

Page 71: ...BIS U 4A7 082 01C 07 S4 BIS U 4A7 082 11C 07 S4 BIS U 4A7 082 21C 07 S4 IO Link Configuration english...

Page 72: ...www balluff com...

Page 73: ...the included Functions 8 3 2 Device Variants 8 3 3 Process Data Profiles 8 3 4 ISDU Identification Data 9 3 5 System Commands 15 3 6 Events 16 4 Communication parameters 18 5 Primary Device Functions...

Page 74: ...2 Diagnosis Suppression 54 7 3 Reset Commands 56 7 4 Variant Configuration 57 7 5 Pin Assignment 59 7 6 LED Meaning and Configuration 61 7 7 Process Data Info and Configuration 63 7 8 Profile Characte...

Page 75: ...2 Balluff GmbH All content is protected by copyright All rights reserved including the right to reproduce publish edit and translate this document 1 2 Symbols and conventions Individual action instruc...

Page 76: ...nnection between master and device the master requests some important communication parameters from the device at the start of communication Settings for communication in Preoperate and Operate modes...

Page 77: ...erization data of a device on the master The master controls the process between uploads if data is intentionally changed or downloads if e g an incorrectly parameterized device is connected The syste...

Page 78: ...66 Parameter Manager see page 67 3 Overview of IO Link Data and Functions 3 2 Device Variants The following variants are available Standard Comprehensive Condition Monitoring CCM The variants differ...

Page 79: ...a e g BIS U 4A7 082 01C 07 S4 Product Text 0x0014 20 0 R 59 bytes STRING n a RFID UHF read write head IO Link stainless steel M30 Condition monitoring Serial Number 0x0015 21 0 R 16 bytes STRING n a H...

Page 80: ...gth 13 R W 1 byte UINT8 Yes 16 Max read length 14 R W 1 byte UINT8 Yes 16 Automatic scanning 15 R W 1 byte UINT8 Yes 0 off Auto Scan resolution 16 R W 1 byte UINT8 Yes 50 Activate SafeMode 17 R W 1 by...

Page 81: ...T32 n a Maximum 2 R 4 bytes FLOAT32 n a Average 3 R 4 bytes FLOAT32 n a Moving Average 4 R 4 bytes FLOAT32 n a Number Of Samples 5 R 4 bytes UINT32 n a Status 6 R 1 byte UINT8 n a Operating Hours Coun...

Page 82: ...1 R 1 byte UINT8 ENUM n a Time 2 R 4 bytes UINT32 n a Internal Temperature Device Temperature 0x0052 82 0 R 10 bytes n a Device Temperature 1 R 2 bytes INT16 n a Minimum Device Temperature Since Reset...

Page 83: ...es FLOAT32 n a Y Reference Value 2 R 4 bytes FLOAT32 n a Z Reference Value 3 R 4 bytes FLOAT32 n a Inclination Deviation Value 0x2154 8532 0 R 1 byte UINT8 n a Vibration Detection Vibration Level 0x21...

Page 84: ...0 W 2 bytes UINT16 n a Reset Commands System Commands 0x0002 2 0 W 1 byte UINT8 n a Variant Configuration Device Variant 0x0055 85 0 R W 2 bytes UINT16 ENUM No 0x01 Standard Pin Assignment Pin 2 Func...

Page 85: ...are restarted and all initializations performed again without any change made to the parameter values see chapter 7 3 on page 56 0x81 129 Application Reset see chapter 7 3 on page 56 0x82 130 Reset Fa...

Page 86: ...arm Check machine 0 Device is operating properly 0x8CFF 36095 Warning Low signal quality level 0 Device is operating properly 0x8D07 36103 Warning The calculation of the basic statistics was stopped a...

Page 87: ...Required 0x8D24 36132 Warning Parameter write error for information purposes only 0 Device is operating properly 0x8D25 36133 Error Parameters not consistent basic settings are used service required P...

Page 88: ...e ID 0x060301 Tab 4 1 Communication parameters In order to flexibly adapt the basic communication parameters to the application other device variants can also be adjusted see Tab 4 2 on page 18 The fo...

Page 89: ...s STRING Yes Function Tag 0x0019 25 0 R W 32 bytes STRING Yes Location Tag 0x001A 26 0 R W 32 bytes STRING Yes Product Type Code 0x0700 1792 0 R 64 bytes STRING n a e g BIS U 4A7 082 01C 07 S4 Product...

Page 90: ...ice detection ISDU Device Discovery Timeout The Device Discovery Timeout parameter sets the duration of the Device Discovery signal that is displayed via LEDs The value is specified minutes The value...

Page 91: ...evice Functions continued 5 3 Process Data 5 3 1 Description A protocol is transferred in the process data For information on the mode of operation and available commands see the user s guide BIS U 4A...

Page 92: ...se of transmitting power on write 9 R W 1 byte UINT8 Yes 8 Number of repetitions 10 R W 1 byte UINT8 Yes 5 Active channels 11 R W 4 bytes UINT32 Yes 0x0000000F Activate BlockWrite 12 R W 1 byte UINT8...

Page 93: ...l failure This reaction is triggered if the signal quality drops below the adjustable threshold value and gives the all clear if a satisfactory signal quality level is once again achieved The signal s...

Page 94: ...w Signal Quality Threshold The threshold value for low signal quality can be set in order to monitor the current signal quality It is displayed as a value between 0 and 100 in percent If the current s...

Page 95: ...nal Quality Threshold to default 0 The feature is thereby deactivated and the evaluation of index 0xCF subindex 2 always results in FALSE Tab 5 7 Signal quality System Commands For an overview of all...

Page 96: ...Fig 6 1 Average Input Maximum Minimum Calculation of minimum maximum and average As shown in Fig 6 1 the calculation is initiated by the start command and stopped by the stop command The values are k...

Page 97: ...odic window Fig 6 3 Moving average window width 9 Value Periodic window Periodic window approach example 6 1 3 Process Data Object ID Name Description Direction 0x0053 83 Minimum Minimum value Input 0...

Page 98: ...conds Time Period Value 3 R W 2 bytes UINT16 No 1 Moving Average Window Unit 4 R W 1 byte UINT8 ENUM No Measurement values Moving Average Window Value 5 R W 2 bytes UINT16 No 100 Statistics Data Outpu...

Page 99: ...100 measurement values measurement values samples can be selected as the unit Value Meaning Description 0x01 1 Seconds Seconds 0x02 2 Minutes Minutes 0x03 3 Hours Hours 0x04 4 Samples Measurement valu...

Page 100: ...6 1 5 System Commands Command Value Device Action 0xA7 167 Statistics Reset Resets all output parameters to 0 and all user settings to the default values 0xA8 168 Statistics Start Min Max Avg Starts t...

Page 101: ...e time has elapsed This event reports the timeout of the minimum value maximum value average calculation It does not report a timeout for the calculation of the moving average because the timer repeat...

Page 102: ...of the total operating hours is indicative of intensive use of a device and possible deterioration of the performance The risk of failure can be countered preventatively through replacement 6 2 2 Algo...

Page 103: ...on the application Current Operating Hours This parameter saves the value of the operating hours since the last startup in seconds Total Operating Hours This parameter saves the value of the operatin...

Page 104: ...ings Resets Custom Operating Hours and Operating Hours Saving Mode to the default value 0xA5 165 Maintenance Reset Resets Custom Operating Hours to the default value Tab 6 13 Operating hours counter S...

Page 105: ...Custom Boot Cycle Counter 2 R 4 bytes UINT32 n a Tab 6 15 Boot cycle counter ISDU The maximum counter value that can be saved is 1 000 000 and with a switch on and switch off every 12 minutes this mea...

Page 106: ...circuit detected at pin 4 Input 0x0016 22 Overload short circuit pin 2 TRUE overload or short circuit detected at pin 2 Input 0x0017 23 Undervoltage TRUE the voltage level is below the threshold valu...

Page 107: ...he supply 2 Out of Specification 0x5111 20753 Warning Primary supply voltage below minimum value Check for deviations in the supply 2 Out of Specification 0x8D0B 36107 Warning Overload or short circui...

Page 108: ...time the time counter can have an error of maximum 180 seconds 6 5 3 Process Data Object ID Name Description Direction 0x0041 65 Lifetime Extreme One or more extreme conditions present Input 0x0042 6...

Page 109: ...summed time in seconds in which the device was exposed to an extreme condition can be read out 6 5 5 Events Event Code Event Type Event Description Remedy Device Status 0x8D13 36115 Warning One or mo...

Page 110: ...configured customer limits Index 0x0053 Set when out of limits Input 0x004F 79 Temperature Status Device Limits Temperature status Warning related to the device limits Set when out of limits Input 0x0...

Page 111: ...the device specific temperature limits Risk of device damage 4 Failure 0x4210 16912 Warning Device Temperature Overrun Clear Heat Of Source Risk of device damage The device is too hot Remove heat sou...

Page 112: ...e device has changed its original installation position and therefore a possible misalignment and resulting malfunctions can be detected at an early stage The configuration can be performed via ISDU p...

Page 113: ...nstallation aid Process data 6 7 4 ISDU Name Index Sub index Access Length Data Type Data Storage Default Inclination Alarm Configuration 0x2151 8529 0 R W 2 bytes Yes Inclination Alarm Enable 1 R W 1...

Page 114: ...il the reference position has been taught in 6 Secondary Device Functions continued Alarm Inclination Status Bit Description 0 Device is in its taught in position orientation 1 Device is incorrectly o...

Page 115: ...ts This event shows that the device has lost its original position taking the threshold value into account The mounting of the device should be checked The device is still functional but the measured...

Page 116: ...mm s Detectable range of the vibration acceleration 0 16 g Measurement error 10 1 The vibration velocity range is frequency dependent The specified value is the theoretical maximum within this freque...

Page 117: ...ers complete monitoring functionality whereby the status monitoring is the primary function of the sensor and it is mounted on the object or on the machine Fig 6 6 Trend analysis 6 8 3 Process Data Ob...

Page 118: ...ive debouncing and avoidance of shock values Unit mm s Minimum value 0 0 Maximum value 1770 0 Vibration Alarm Status The status flag is TRUE if the vibration exceeds the alarm threshold value 0 no ala...

Page 119: ...ion Process Data Profiles on page 8 6 9 3 ISDU Name Index Subindex Access Length Data Type Data Storage Default Humidity 0x005C 92 0 R 9 Byte n a Humidity Bad 1 R 1 byte BOOL n a Operating Hours At Ex...

Page 120: ...Type Event Description Remedy Device Status 0x8D12 36114 Warning The defined threshold of the device internal humidity was exceeded Check installation and ambient conditions 1 Maintenance Required Ta...

Page 121: ...n each segment is monitored by a counter All data segments are protected with a CRC32 checksum 6 10 2 Events Event Code Event Type Event Description Remedy Device Status 0x8D22 36130 Warning Warning l...

Page 122: ...here is an error in the device This information is linked to the device status 4 Failure which can be triggered by different device functions or diagnostic messages The bit is reset as soon as the err...

Page 123: ...tting to factory settings can help Otherwise Balluff service must be contacted or the device replaced Tab 7 3 Device Status 7 1 5 Detailed Device Status Detailed Device Status indicates the currently...

Page 124: ...6 No 0 Event Code Suppression Teach in 0x0072 114 0 W 2 bytes UINT16 n a Event Code Suppression Delete 0x0073 115 0 W 2 bytes UINT16 n a Tab 7 5 Diagnosis suppression ISDU 7 2 3 Diagnosis Level Config...

Page 125: ...e and is interpreted as FREE Each event message is structured as follows Byte1 MSB Byte0 LSB Event Code High Byte Event Code Low Byte Tab 7 7 Diagnosis suppression Event Message Suppression Event Code...

Page 126: ...formed using IO Link specification V1 1 2 Resets all parameters and device settings to default values with the exception of the identification and tagging parameters No reset of the configuration of t...

Page 127: ...his parameter is not changed by a reset After a variant changeover an inconsistent configuration may occur because there is no automatic changeover of parameters It is therefore recommended that the s...

Page 128: ...s UINT16 ENUM No 0x01 Standard Tab 7 10 Variant Configuration ISDU Device Variant The following device variants are available Value Meaning Description 0x0001 1 Standard 32 bytes RFID process data 0x0...

Page 129: ...on are only used if the pin was configured as a digital output or digital input Tab 7 12 Pin assignment ISDU Behavior IO Link With Behavior IO Link the behavior of the pins during active IO Link commu...

Page 130: ...dity Bad is active see section 6 9 on page 49 0x0037 55 Inclination Alarm Status Switches when inclination alarm is triggered or Inclination Alarm Status is active see section 6 7 on page 42 0x0041 65...

Page 131: ...ntenance must be performed Overload Orange flashing 3 Hz Overload on pin 2 pin 4 has been detected Bad Signal Quality Orange flashing 1 Hz Poor signal quality the signal quality is below the configure...

Page 132: ...splay Yellow static The object was detected Switching point is active Communication Green alternating with LED off at ratio of 10 1 1 s period IO Link communication is active The device is ready Ready...

Page 133: ...data is not marked as invalid but is instead replaced by substitution values or error codes This is to be taken into account during the evaluation Invalid output data from the master to the device is...

Page 134: ...ed Byte 2 TypeLength 0 255 bits Byte 3 Bit offset 0 255 bits Tab 7 24 Process data info and configuration PD Description 7 System Functions continued Last Valid Process Data This parameter indicates t...

Page 135: ...s invalid if the device status see section 7 1 on page 52 of the device is Failure In all other states replacement values for the data are output for which the content cannot be output correctly PD Ou...

Page 136: ...parameter can be read via subindex 0 and consists of multiple profile indices and function classes each 16 bit values If a profile ID is specified this means that all included function classes are su...

Page 137: ...t of damaged memory the parameter manager outputs the Parameters not consistent event 7 9 2 Events Event Code Event Type Event Description Remedy Device Status 0x8D24 36132 Warning Parameter write err...

Page 138: ...hengshan Rd 8F Building A Yunding International Commercial Plaza 200125 Pudong Shanghai Phone 86 400 820 0016 Fax 86 400 920 2622 service cn balluff com cn DACH Service Center Germany Balluff GmbH Sch...

Reviews: