background image

External Power

Internal Power

T1K-08ND3    $77.00

8-point 12/24VDC  

input module

The 8-point DC module uses a 

 

T1K-08B or T1K-08B-1 base, which is 
purchased separately.

DC Input Modules

Note:

 When using external power, the module can be wired to either sink current or source current regard-

less of the module’s sink/source jumper position. When using internal power, the sink/source jumpers 
determine the module’s configuration.

Module Specifications

T1K-08ND3

Inputs Per Module

8 (sink/source)

Commons, Non-isolated

Ext. power: 2, isolated (4 pts. /com) 

Int. power: 2, all 8 pts. internally connected

Operating Voltage Range

12–24 VDC 

Input Voltage Range

10.8-26.4 VDC min./max.

Peak Range

30VDC

Input Current (Typical)

4mA @ 12VDC,  8.5 mA @ 24VDC

Input Impedance

2.8 k

q

ON Voltage Level

> 10.0  VDC

OFF Voltage Level

<  2.0  VDC

Min. ON Current

4mA 

Max. OFF Current

0.5 mA

OFF to ON Response

2–8 ms,   Typ: 4ms

ON to OFF Response

2–8ms,   Typ: 4ms

Base Power Required

35mA @ 5VDC

Status Indicators

Logic side

Weight 

70g 

w w w . a u t o m a t i o n d i r e c t . c o m

Universal Field I/O

tFED-71

For the latest prices, please check AutomationDirect.com.

1 - 8 0 0 - 6 3 3 - 0 4 0 5

Summary of Contents for T1K-08ND3

Page 1: ...r Module 8 sink source Commons Non isolated Ext power 2 isolated 4 pts com Int power 2 all 8 pts internally connected Operating Voltage Range 12 24 VDC Input Voltage Range 10 8 26 4 VDC min max Peak Range 30VDC Input Current Typical 4mA 12VDC 8 5 mA 24VDC Input Impedance 2 8 kq ON Voltage Level 10 0 VDC OFF Voltage Level 2 0 VDC Min ON Current 4mA Max OFF Current 0 5 mA OFF to ON Response 2 8 ms T...

Page 2: ... Per Module 16 sink source Commons Non isolated Ext power 4 isolated 4 pts com Int power 4 all 16 pts internally connected Operating Voltage Range 12 24 VDC Input Voltage Range 10 8 26 4 VDC Peak Range 30VDC Input Current Typical 4 mA 12VDC 8 5 mA 24VDC Input Impedance 2 8 Kq ON Voltage Level 10 0 VDC OFF Voltage Level 2 0 VDC Min ON Current 4 mA Max OFF Current 0 5 mA OFF to ON Response 2 8 ms Ty...

Page 3: ... isolated Input Voltage Range 80 132 VAC 47 63 Hz Operating Voltage Range 90 120 VAC 47 63 Hz Input Current 8mA 100VAC 50Hz 10mA 100VAC 60Hz 12mA 132VAC 50Hz 15mA 132VAC 60Hz 8mA 100VAC 50Hz 10mA 100VAC 60Hz 12mA 132VAC 50Hz 15mA 132VAC 60Hz Input Impedance 14kq 50Hz 12kq 60Hz ON Current Voltage 6mA 75VAC OFF Current Voltage 2mA 20VAC OFF to ON Response 40ms ON to OFF Response 40ms Base Power Requ...

Page 4: ...access and cable clearance However your distance may be greater or less Also check the installation guidelines for the recom mended cabinet clearances 48mm 1 89in 80mm 3 15in 80mm 3 15in 48mm 1 89in 80mm 3 15in 48mm 1 89in 89mm 3 5in 80mm 3 15in 83 3mm 3 28in Power Supply Network Interface Module Half size I O Module with Base System Depth Full size I O Module with Base Dimensions and Installation...

Page 5: ...parate terminal bases for easy installation To install I O modules 1 Slide the module into its terminal base until it clicks into position 2 Hook upper DIN rail tabs over the top of DIN rail and press the assembly firmly onto the DIN rail 3 Slide the module along the DIN rail until it engages with the adjacent module DN ASB 1 angled mounting bracket Optional angled support bracket raises and tilts...

Page 6: ... MVSTBW 2 5 6 ST 5 08 BK Note 500mA 24VDC can be achieved by lowering the 5VDC from 2000mA to 1500mA Power Budget Example Module 5VDC 24VDC T1K 01AC 2000mA 300mA T1H EBC100 300mA 0mA T1K 16ND3 70mA 0mA T1K 16TD2 200mA 0mA T1F 08AD 1 75mA 50mA Remaining 1355mA 250mA Module 5VDC 24VDC Analog Input Modules T1F 08AD 1 75 50 T1F 08AD 2 75 50 T1F 16AD 1 75 50 T1F 16AD 2 75 50 T1F 16RTD 150 0 T1F 16TMST ...

Page 7: ...s pass 24VDC through on an isolated wire All cables pass the 5VDC base power Any local expansion DC input module configured for internal power current sourcing must either have a power supply preceding it on the same base or have a 1 version cable pass 24VDC from a power supply on the preceding base In the system below power supplies can be used anywhere T1K 10CBL 1 I O Addressing T1K 10CBL 1 Cabl...

Page 8: ...ean wiring with only one wire per termination External user supplied 24VDC power or auxil iary 24VDC terminals from T1K 01AC can be easily applied directly to one end of the terminal rows and jumpered across each base in the system This is a convenient solution for powering analog I O and discrete DC output devices whose modules do not have direct access to the internal bussed 24VDC If current con...