background image

1

Sales 800-633-0405

www.productivity1000.com

24V

I2+
I3+
I4+

0V

I1+
I2+

COM
COM

I1+

P1-4ADL2DAL-1

0-20mA IN

4-20mA OUT

INPUTS

1000

P1-4ADL2DAL-1 Analog Input/

Output

The P1-4ADL2DAL-1 Current Analog Input/Output 

Module provides four 13 bit input channels at 0-20 

mA and two 12 bit output channels at 4-20 mA for 

use with the Productivity1000 system.

General Specifications  . . . . . . . . . . . . . . . . . . . . . .  1

Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . .  2

Output Specifications  . . . . . . . . . . . . . . . . . . . . . . .  2

Wiring Diagram and Schematic . . . . . . . . . . . . . . . .  3

Module Installation Procedure . . . . . . . . . . . . . . . . .  4

QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4

Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5

Module Configuration  . . . . . . . . . . . . . . . . . . . . . . .  5

Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  6

Non-Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . .  6

Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

Removable Terminal Block Specifications. . . . . . . .  8

Warranty: Thirty-day money-back guarantee. Two-year limited 

replacement. (See www.productivity1000.com for details).

Terminal Block sold separately, (see wiring options on page 5).

General Specifications

Operating Temperature

0º to 60ºC (32º to 140ºF)

Storage Temperature

-20º to 70ºC (-4º to 158ºF)

Humidity

5 to 95% (non-condensing)

Environmental Air

No corrosive gases permitted

Vibration

IEC60068-2-6 (Test Fc)

Shock

IEC60068-2-27 (Test Ea)

Field to Logic Side 

Isolation

1800VAC applied for 1 second

Insulation Resistance

> 10M

 @ 500VDC

Heat Dissipation

2470mW

Enclosure Type

Open Equipment

Module Location

Any I/O position in a Productivity1000 System

Field Wiring

Removable terminal block (sold separately). Use 

ZIP

Link 

Wiring System optional See “Wiring Options” on page 5.

EU Directive

See the “EU Directive” topic in the Productivity Suite Help 

File. Information can also be obtained at:

www.productivity1000.com

Terminal Type 

(sold separately) 

10-position Removable Terminal Block

Weight

60g (2.1 oz)

Agency Approvals

UL61010-2-201 file E139594, Canada & USA
CE (EN61131-2 EMC and EN61010-2-201 Safety)*

*See CE Declaration of Conformance for details.

Summary of Contents for Productivity 1000 P1-4ADL2DAL-1

Page 1: ...wiring options on page 5 General Specifications Operating Temperature 0º to 60ºC 32º to 140ºF Storage Temperature 20º to 70ºC 4º to 158ºF Humidity 5 to 95 non condensing Environmental Air No corrosive gases permitted Vibration IEC60068 2 6 Test Fc Shock IEC60068 2 27 Test Ea Field to Logic Side Isolation 1800VAC applied for 1 second Insulation Resistance 10M 500VDC Heat Dissipation 2470mW Enclosur...

Page 2: ...ontinuous Overload Outputs open circuit protected Type of Output Protection Electronically current limited to 20mA or less Output Signal at Power Up and Power Down 4mA Input Specifications Inputs per Module 4 Module Signal Input Range 0 20 mA Signal Resolution 13 bit Resolution Value of LSB least significant bit 0 20 mA 2 44 µA per count 1LSB 1 count Data Range 0 8191 counts Input Type Sinking Sin...

Page 3: ...CUIT POWER P1 4ADL2DAL 1 Wiring Diagram Current Input Circuits Current Output Circuits COM 3 Wire Current Transmitter 032A 2 Wire 4 20 mA Transmitter fuse 2 Wire Transmitter 3 Wire Transmitter 24VDC User Supplied Power 032A fuse Note Do not connect both ends of shield 4 Wire 4 20 mA Transmitter 4 Wire Transmitter User Supplied Transmitter Power AC or DC 4 20mA Load Note Shield is connected to comm...

Page 4: ...cked position and then pull modules apart Step Two Attach field wiring using the removable terminal block or ZIPLink wiring system LOCK UNLOCK WIRE STRIP LENGTH MIN MAX P1 08TD1 Check all latches are secure after modules are connected QR Code Use any QR Code reader application to display the module s product insert P1 08TD1 P1 08TD1 1 2 3 4 5 6 7 8 9 10 L L L L L L L L 24V 1 2 3 4 0V 5 6 7 8 12 24...

Page 5: ...nly P1 10RTB Quantity 1 4 Spring Clamp Terminal Block only P1 10RTB 1 Quantity 1 5 Accessories ZL RTB COM TW SD SL 1 TW SD MSL 2 ZL RTB20 ZL RTB20 1 2 1 Cable ZIPLink Module Complete System 2 ZL RTB COM provides a common connection point for power or ground Complete System ti i t f Module Configuration Using the Hardware Configuration tool in the Productivity Suite programming software drag and dr...

Page 6: ... raw input signals to engineering units for use in the program or convert engineering units to output signals for control purposes max min min max 1045 0 8191 220 Level Transmitter Tank Level Non Linear Scaling Non Linear Scalin 0 5 1 1 55 2 25 3 4 55 6 75 7 0 0 0 0 0 0 0 0 1 2 3 4 5 6 6 5 7 0 0 0 0 0 0 0 Level Transmitter Tank Level 7 0 0 0 0 0 0 0 Select the minimum and maximum values of the raw...

Page 7: ...7 Sales 800 633 0405 www productivity1000 com ...

Page 8: ... determine which codes should be followed and to verify that the equipment installation and operation are in compliance with the latest revision of these codes Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and standards We do not guarantee the products described in this publication are suitable for your particular application nor do we a...