background image

• Ariterm B 20

ARITERM-VTT-S-07229-11.1

INSTALLATION AND OPERATING 
INSTRUCTIONS

Summary of Contents for Biomatic+ 20

Page 1: ... Ariterm Biomatic 20 ARITERM VTT S 07229 11 1 INSTALLATION AND OPERATING INSTRUCTIONS ...

Page 2: ...oden frame The base is a platform from which the boiler can be safely lifted The package should be unwrapped as close to the installation site as possible The factory has insured the boiler against damage during transport from the factory to the first intermediate storage site It is important for the person who receives the boiler to verify the state of the boiler before its acceptance In case of ...

Page 3: ...m Electrical values burner side Power supply Supply cable Fuse size Power in operation Power in connection 400 V 3 phase 50 Hz 9 kW resistance MMJ 5x2 5s 9 kW resistance 3x16 A Burner ignition 500 W Burner normal 40 W 9 kW resistance about 10 kW depending on equipment TECHNICAL DATA ARITERM BIOMATIC Standard delivery Four way mixing valve ESBE TM 20 Sweeping gear Dirt trap Brick support Flue duct ...

Page 4: ...ed from the ash box located in the lower part of the boiler Ash can also be removed into a special ash pan by means of an ash trap or a common vacuum cleaner However the ash may still be hot Therefore the ash trap must be heat resistant Standard equipment includes an automatic heat regulation system that adjusts the sup ply water temperature according to the tem perature outside For safety reasons...

Page 5: ...tance BURNER OPERATING PRINCIPLE Green The burner is on Red Alarm the burner is off Blinking light Warning light do not turn the burner off Arrow keys browsing menus changing setting C button exiting menus acknowledging warnings ac knowledgement of setting Enter button selecting settings go to sub menu 1 Inner circulation pump switch 2 Inner circulation pump fuse 3 Display 4 Over heating sensor 5 ...

Page 6: ...nal circulation pump through the venting screw located in the pump head the flue damper if any is open the circulation damper located in the convection part of the boiler is in place the circulation pump is running the network valves are open the ventilation air intake is open the safety valve is in working order and there are no obstacles between it and the boiler BOILER INSTALLATIONS Flue pipe c...

Page 7: ...4 WAY VALVE FLOOR HEATING RADIATOR HEATING 3 CONNECTION SET OF THE ADDITIONAL HEATING CIRCUIT RADIATOR HEATING 4 HEAT PIPE PUMP FLOOR HEATING 5 HEAT PIPE PUMP RADIATOR HEATING 6 FLOOR HEATING NETWORK MANIFOLDS 7 RADIATOR HEATING NETWORK 8 EXPANSION VESSEL 9 SERVICE SHUT OFF VALVE 10 SAFETY VALVE 11 FILLING VALVE 12 FEED MIXING VALVE 13 DOMESTIC WATER CIRCULATION PUMP PIPE INSTALLATIONS VW CW DW ...

Page 8: ...ARITERM SWEDEN AB ARITERM OY Asennus ja käyttöohje Installation och driftanvisning Installation and operating instruction UK 25 05 2012 8 32 ARITERM VTT S 07229 11 1 WIRING DIAGRAM ...

Page 9: ...urner head The success of the cold start can be ensured by sufficiently increasing the set boiler water temperature and by changing it back to the desired value after ignition Hot start The burner performs a hot start when the boiler water temperature is within 8 C of the set temperature for example after a short power failure During a hot start the burner uses the embers in the burner head for ig...

Page 10: ...rner and control the external storage auger When the pellet surface drops below the level switches the external auger activates factory setting 30 s The operating time of the external auger should be long enough for the pellet surface to rise to the level of the burner up per connection Time can be adjusted from Auger External in the Power menu If the time is too long the pellets rise to the drop ...

Page 11: ...High auger Low auger High fan Low fan Min auger Power settings Cleaning fan Min fan Holding time Coldstart amount Warmstart amount Coldstart settings Auger external Manual Start backup El El step Level monitor Test outputs Optical monitor English Default settings Adjustment Diff temperature Accessories Flow water min Heating Curve Flow water max Curve comp 0 Curve comp 5 Curve comp 5 Circ pump sto...

Page 12: ...enu Adjust 0 20 C Fine adjustment of heating circuit 1 visible if activated from the Accessories menu and if the internal sensor is not connected Menues Accessing submenus Burner Adjustments Ope rating Time Pellet Store Power Heat Regulati on Service Main menu Menu Setting Description El step 0 3 Activation of electrical resistances 0 not in use 1 3 kW 2 6 kW 3 9 kW Start backup El 10 40 C Activat...

Page 13: ...wer mode the blower goes to 100 power and keeps the air vents clean Holding time 60 min No 0 120 min Time between ember maintenance cycles The auger burner carries out a 1 minute feeding cycle while the burner is in Maintain mode No The burner does not maintain the embers In this case the burner always performs a cold start when starting up To be used for example with an accumulator Auger external...

Page 14: ...efficient can be used to determine the supply water correction coefficient in order for the indoor temperature to reach the set value The factory setting is 2 ºC In other words if the indoor temperature is 19 20 ºC the supply water temperature increases by 2 ºC in order for the set indoor temperature to be achieved The room coefficient depends on insulation level and heating system Residual oxygen...

Page 15: ... heating circuits Heat circuit menu The graph curves more quickly when the outdoor temperature is above 16 ºC The Flow Water Max and Min settings can be used to cut the top and bottom of the graph The angular coefficient of the graph slightly increases when the Curve setting is increased Temperature graph compensation The graph can be compensated when the outdoor temperature is 5 ºC 0 ºC and 5 ºC ...

Page 16: ...indicative and fine adjustment might be required Floor heating system A thermostat is installed in the circulation pump control of the heating circuit The thermostat switches the pump control off if the supply water temperature rises above 45 ºC If the supply water temperature is too high this may damage parquet floor Control If when the outdoor temperature is below 0 ºC the room temperature is to...

Page 17: ... connection Control module Power source 230 VAC 12 VDC Heated oxygen sensor The Pellet boiler Ariterm Biomatic can be equipped with a heated oxygen sensor that facilitates control of the burner and which if necessary can regulate the combustion air fan output if the combustion is poor Residual value is displayed on the display The heated oxygen sensor can be easily connected to the boiler at a lat...

Page 18: ... cleanliness of the fla me detection sensor 2 Ember maintenance time Power menu 1 Check the flame detection system as specified above 2 Check the embers while being in Maintain mode Excessive draught may burn the embers completely In this case reduce the draught and the time of the Ember Maintenance setting If the alarm has been given af ter cleaning the burner head increase the set temperature of...

Page 19: ...switches must be cleaned all the time they may be defective and the instal ler should have a look at them A possible foreign object in the pellet fuel must be removed if it gets stuck in the blocking feeder or in one of the feeding augers Remove the upper connection and take out the possible fo reign object from the feeding auger or blocking feeder ALARMS AND TROUBLESHOOTING Alarm message Cause Ch...

Page 20: ...PS 25 40 pump 1544 Boiler temperature sensor 5358 Flue gas temperature sensor 5022 BeQuem 20 inner cage 1692 Display card BM BQ 5820 ESBE ARA661 shunt motor 5062 Sweeping motor SPG TS09 0175 1691 Controller card Biomatic 5291 Outdoor temperature sensor 5292 Indoor temperature sensor 5718 Supply water sensor 5346 Chain wheel Z 12 5023 Hub chain wheel Z 15 5831 Hub chain wheel Z 24 5885 47 link chai...

Page 21: ...ed with the boiler see the next page Finally empty the ash box The ash from the ash box can be used to deter mine whether combustion has been good The ash should be powdery The interval for ash removal and boiler cleaning can be specified in the Service menu on the basis of experience The boiler should be cleaned when the temperature of flue gases rises by 20ºC with respect to the temperature they...

Page 22: ...n power before maintenance work Other boiler cleaning operations Ash box emptying Flue duct cleaning Convection channel cleaning 2 times a year Combustion chamber cleaning as needed Convector cleanout hatch Clean the flame detector of impurities NOTE If the protective glass of the flame detector breaks or detaches the flame detector can no longer be used and must be replaced with a new one Remove ...

Page 23: ... convection channel 3 Lift the rocker switch to the side 6 Lift off the holder and the springs from the convec tion 7 Sweep the convection pipe surface with a brush remove any ash Push the brush up and down again 8 Reinstall all the springs and lifting levers illustrated 9 Install the convection channel hatch and the rocker switch 5 Lift off the second hatch of the convection channel 10 Install th...

Page 24: ...rities sand These materials cannot be detected before burning NOTE If the ash is sin tered all sintered material must be continuously removed from the burner head Fuel storage Thanks to the feeding system it is possible to build the pellet store for so called bulk deliveries The store can be placed either inside or in a separate building outside the house The shorter the transport distance from th...

Page 25: ... silo is 300 litres and its filling is facilitated by the intermediate grid in the silo Contrary to the figure the silo is delivered with a lid NOTE More information on the installation of PS300 Feedo can be found in separate manuals Depo Feed chute Depo is a patented pellet transfer system that effectively reliably and quietly feeds pellets from the silo via the feeding system to the burner Feedo...

Page 26: ...fuels or exempt appliances for use in smoke control areas in England In Scotland and Wales this power rests with Ministers in the devolved administrations for those countries Separate legislation the Clean Air Northern Ireland Order 1981 applies in Northern Ireland Therefore it is a requirement that fuels burnt or obtained for use in smoke control areas have been authorised in Regulations and that...

Page 27: ...Flue gas temperature Max CO O2 CO2 Combustion efficiency Draught mm Blower Auger Flue gas temperature Mean CO O2 CO2 Combustion efficiency Draught mm Blower Auger Flue gas temperature Min CO O2 CO2 Combustion efficiency Draught mm Blower Auger Dealer Installer Installer Date After installation the burner must be adjusted using a flue gas analyser INSTALLATION REPORT ...

Page 28: ...ARITERM SWEDEN AB ARITERM OY Asennus ja käyttöohje Installation och driftanvisning Installation and operating instruction UK 25 05 2012 28 32 ARITERM VTT S 07229 11 1 NOTES ...

Page 29: ...NOTES ...

Page 30: ...ARITERM SWEDEN AB ARITERM OY Asennus ja käyttöohje Installation och driftanvisning Installation and operating instruction UK 25 05 2012 30 32 ARITERM VTT S 07229 11 1 NOTES ...

Page 31: ...ARITERM SWEDEN AB ARITERM OY Asennus ja käyttöohje Installation och driftanvisning Installation and operating instruction UK 25 05 2012 31 32 ARITERM VTT S 07229 11 1 NOTES ...

Page 32: ...ORGANISATION CERTIFIED BY ARITERM VTT S 07229 11 1 ARITERM SWEDEN AB Flottiljvägen 15 39241 Kalmar www ariterm se 0771 442850 ...

Reviews: