background image

  

1

 Probe tip (Voltage sensor)      

2

 Probe body      

3

 Battery cap

SymbolS

Caution! Risk of electric 
shock.

Caution! Refer to the 
explanation in this 
instruction sheet.

Double insulated 

Battery

Canadian Standards
Association (NRTL/C)

 

Conforms to relevant
Australian standards

Complies with
European Directives.

Do not dispose of this 
product as unsorted 
municipal waste. Contact a 
qualified recycler.

CAT IV

Equipment is for measurements performed at the source of a low 
voltage installation. (i.e. electrical meters and measurements on 
primary over current protection devices and ripple control units.)

For Use by Competent Persons

Anyone using this instrument should be knowledgeable and trained about 
the risks involved with measuring voltage, especially in an industrial setting, 
and the importance of taking safety precautions and of testing the instrument 
before and after using it to ensure that it is in good working condition.

SaFety InFormatIon



WarnInG!

to avoid possible electric shock or personal injury:

•  If the Tester is used in a manner not specified by the manufacturer, 

protection provided by the Tester may be affected.

•  Test on a known live source within the rated ac voltage range of the 

product, both before and after use to ensure unit is in good working 
condition.

•  When using the Tester, if tip does not glow, voltage could still be present. 

The Tester indicates active voltage in the presence of electrostatic fields of 
sufficient strength generated from the source voltage. If the field strength 
is low, the Tester may not provide indication of live voltage. Lack of an 
indication occurs if the Tester is unable to sense the presence of voltage 
which may be influenced by several factors including, but not limited to:

 

  - Shielded wire/cables

 

  - Thickness and type of insulation

 

  - Distance from the voltage source

 

  - Fully-isolated users that prevent an effective ground

 

  - Receptacles in recessed sockets/ differences in socket design

 

  - Condition of the Tester and batteries

•  Do not use if the Tester appears damaged or if the Tester is not operating 

properly. Specifically examine the probe tip for cracks or breakage before 
use. If in doubt, have the Tester serviced.

•  Do not apply more than the rated voltage as marked on the Tester.
•  Use caution with voltages above 30 V ac as a shock hazard may exist.
•  Comply with local and national safety requirements.
•  Use proper protective equipment as required by local or national 

authorities.

oPeratInG InStrUCtIonS

The product is always on and ready to use, subject to battery and Tester 
condition.

Checking for the Presence of aC Voltage

Placing the tip of the Tester near an ac voltage (within the specified range of 
the Tester) produces flashing illumination at the tip.

Testing receptacle: 

Testing wires:

LINE contact

     

LINE

VP-1000:

 Illuminates when ac voltage is detected.

battery rePlaCement

CleanInG

The Tester can be cleaned with a mild solution of water. Apply sparingly with 
a soft cloth and allow to dry completely before using. Do not use aromatic 
hydrocarbons, gasoline or chlorinated solvents for cleaning. 

DetaIleD SPeCIFICatIonS 

operating Voltage range:

 90 Vac to 1000 Vac, 50 / 60 Hz

Deteccion VP-1000:

 Illuminates at approximately 10 mm (0.39 in) distance from 

a wire carrying 120 Vac. 

operating temperatures:

 0°C to +50°C (32°F to 122°F), 

95% RH

Storage Conditions:

 -10°C to +50°C (14°F to 122°F), 

95% RH

operating altitude:

 

 2000 meters (CAT IV 1000 V)

Power Supply:

 Two 1.5V AAA batteries

Dimensions (l x W x H):

 155 x 24.5 x 21.5 mm (6.10 x 0.96 x 0.85 in)

Weight:

 Approximately 50 g (0.11 lb) with batteries installed

Safety Compliance:

 IEC 61010-1 3rd Ed., UL61010-1 2nd Ed. and CAN/CSA C22.2 

No. 61010.1-0.92 to CAT IV 1000 V, Pollution degree 2, IP40

emC Compliance:

 IEC 61326-1

limited Warranty and limitation of liability

Your Amprobe product will be free from defects in material and workmanship 
for one year from the date of purchase, unless local laws require otherwise. This 
warranty does not cover fuses, disposable batteries or damage from accident, 
neglect, misuse, alteration, contamination, or abnormal conditions of operation 
or handling. Resellers are not authorized to extend any other warranty on 
the behalf of Amprobe. To obtain service during the warranty period, return 
the product with proof of purchase to an authorized Amprobe Service Center 
or to an Amprobe dealer or distributor. See Repair Section for details. THIS 
WARRANTY IS YOUR ONLY REMEDY. ALL OTHER WARRANTIES - WHETHER 
EXPRESS, IMPLIED OR STAUTORY - INCLUDING IMPLIED WARRANTIES OF FITNESS 
FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, ARE HEREBY DISCLAIMED. 
MANUFACTURER SHALL NOT BE LIABLE FOR ANY SPECIAL, INDIRECT, INCIDENTAL 
OR CONSEQUENTIAL DAMAGES OR LOSSES, ARISING FROM ANY CAUSE OR 
THEORY. Since some states or countries do not allow the exclusion or limitation of 
an implied warranty or of incidental or consequential damages, this limitation of 
liability may not apply to you.

repair

All test tools returned for warranty or non-warranty repair or for calibration 
should be accompanied by the following: your name, company’s name, 
address, telephone number, and proof of purchase. Additionally, please 
include a brief description of the problem or the service requested and include 
the test leads with the meter. Non-warranty repair or replacement charges 
should be remitted in the form of a check, a money order, credit card with 
expiration date, or a purchase order made payable to Amprobe®.

In-Warranty repairs and replacement – all Countries

Please read the warranty statement and check your battery before requesting 
repair. During the warranty period any defective test tool can be returned 
to your Amprobe® distributor for an exchange for the same or like product. 
Please check the “Where to Buy” section on www.amprobe.com for a list 
of distributors near you. Additionally, in the United States and Canada in-
warranty repair and replacement units can also be sent to a Amprobe® Service 
Center.

non-Warranty repairs and replacement – US and Canada

Non-warranty repairs in the United States and Canada should be sent to a 
Amprobe® Service Center. Call Amprobe® or inquire at your point of purchase 
for current repair and replacement rates.

In USA  

In Canada

Amprobe  

Amprobe

Everett, WA 98203  

Mississauga, ON L4Z 1X9

Tel: 877-AMPROBE (267-7623)  

Tel: 905-890-7600

non-Warranty repairs and replacement – europe

European non-warranty units can be replaced by your Amprobe® distributor 
for a nominal charge. Please check the “Where to Buy” section on www.
amprobe.com for a list of distributors near you.

European Correspondence Address*

Amprobe® Europe
Beha-Amprobe GmbH
In den Engematten 14
79286 Glottertal, Germany
Tel.: +49 (0) 7684 8009 - 0
www.amprobe.eu

*(Correspondence only – no repair or replacement available from this address. 
European customers please contact your distributor.)

VP-1000

Non-Contact Voltage Detector

6/2014, Rev.03 ©2014 Amprobe.

All rights reserved. Printed in China

Non-Contact Voltage Probe
Sensitivity range: 90 - 1000 Vac

CAT IV 1000V

VP-1000

1

2

3

Please Recycle 

v