- INSTRUCTIONS -

The NDR-nRS Lamp Memory System is designed for use with the NE-NVP-RA  Rescue Assistance sub stations.
The NE-NVP-RA provides communication and call status indication for applications with ADA requirements for
Areas of Rescue Assistance.  The NE-NVP-RA features Braille signage, a large red call button, and "call placed"
and "help coming" LED indicators. The sub station flush mounts into a 3-gang masonry-type box, or surface
mounts in the SBX-NVP.  Tamper proof screws are provided, along with a wrench for installation. Remote lamps
can be added for better visibility of a station's status.  The NDR-nRS master station is equipped with a door
release button and a reset button to reset calls at the master station. The NDR-nRS has outputs to activate an
external device, such as a CCTV camera when the associated sub station is selected, or selectively controlling
the corresponding door strike or maglock.

WIRING DIAGRAM:     SYSTEM USED FOR CCTV CAMERA CALL-UP

NDR-RS

NDR Lamp Memory Master Station with External Control Capability for Rescue Assitance

NDR-10RS

NDR-20RS

NDR-30RS

NDR-40RS

NDR-10ARS NDR-20ARS NDR-30ARS NDR-40ARS

Individual Components for System:

NDR-

nRS     

Master station with selective contact output capability (10, 20, 30, 40)

NDR-

nARS  

Master station w/hndst andcontact output capability (10, 20, 30, 40)

ND-20AS

20-call Add-on Selector with selective output capability (Require PS-2410A)

ND-40AS

40-call Add-on Selector with selective output capability (Requires PS-24E)

RY-PA

Relay for selective output (1 per station requiring external contact)

PS-2410A24V DC, 1A Power Supply for 10-20 station systems
PS-24E

24V DC, 2A Power Supply for 30-40 station systems

NE-NVP-RA

Vandal proof sub station with call status indicators and braille signage

IMPORTANT:

1. RY-PA must be used for each additional contact

to isolate AC voltage from the intercom circuit.

2. Extra contact connections and L are on separate

terminal block.  NDR-30/40RS have two terminal blocks.

Special
Order
Products

NDR-20RS

+

-

PS-2410A

Pg. 1

1

          L

2

RY-PA

#1

BLK

H

RY-PA

#2

NDR-RS Master

RY-PA

#1

RY-PA

#2

BLK

BLK

BLK

YEL

Momentary closure #1

YEL

Constant closure #1

YEL

Momentary
closure #2

YEL

Constant
closure #2

Equipment for each station that requires
both a constant closure and momentary
closure when a channel is selected:
2 RY-PA relays
1 Diode (1N4001)

DUAL FUNCTIONS FROM EACH CHANNEL:

Terminal Block

NDR-RS TERMINAL DEFINITIONS:

+

Positive 24V DC

-

Negative

1~40

Station number

E

Common communication

S

Sends "call placed" tone to sub

H

Resets call signals at sub when RESET
button is pressed.

1

2

3
~
20       L

BLK

YEL

External

Terminal Block

Normally Open contacts remain
closed as long as master has sub
station selected.

Closure for Station #2

Closure for Station #3

BLK

YEL

BLK

YEL

Closure for Station #1

RY-PA

#3

RY-PA

#2

RY-PA

#1

NE-NVP-RA

Red

Blu

Pur

Blk
Yel

Org

Green

jumper

NE-NVP-RA

Red

Blu

Pur

Blk
Yel

Org

Green

jumper

NE-NVP-RA

Red

Blu

Pur

Blk
Yel

Org

Green

jumper

Leave green

jumper intact

1
2
3
~

20

E
S
H

+

-