background image

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 1

DUCT HUMIDITY SERIES

Installation & Operation Instructions

Version 6.0

I0000546

GENERAL INFORMATION

The A/RH Duct Series Sensor is a Relative Humidity 
transmitter that can be powered with either an AC or 
DC supply voltage. The RH Duct transmitter is field 
selectable with a 4-20 mA, 0-5 VDC, or 0-10 VDC output 
signal that is equivalent to 0 to 100% RH. This sensor is 
designed for use with electronic controllers in commer-
cial heating and cooling building management 
systems. All units are shipped from the factory set up 
for a 4-20 mA output. The transmitter can also include 
an optional temperature sensor for monitoring the 
space temperature.

For optimal readings, follow these tips:  

The sensor should be mounted in the middle of the duct 

where air circulation is well mixed (no stratification), and 
not blocked by obstructions. Stratification and 
obstructions can cause sensing errors. An example is 
downstream from a heating or cooling coil.

Duct probe should be placed (3) to (4) duct 

segments down from any bend or obstructions and 
away from 90° bends. 

Mount the sensor on the top or sides of duct work; 

mounting on the bottom risks damage due to moisture.

MOUNTING INSTRUCTIONS

The Euro enclosure (-EH) requires a 0.875” (22.23 mm) 
hole in the duct, and the Nema 4X enclosure (-4X) 
requires a 1.25” (31.75 mm) hole - see 

FIGURE 1

. After 

drilling, insert the probe through the hole until the 
foam pad is tight to the duct. Drill pilot holes for the 
mounting screws. Use the enclosure as a guide, or use 
the dimensions listed on the right to measure out.

Now fasten and insert mounting screws through the 
mounting holes and tighten until the unit is held firmly 
to the duct. Refer to 

Wiring Instructions 

(p. 2-4) to 

make necessary connections.

FIGURE 1: 

ENCLOSURE DIMENSIONS

EURO (-EH)

NEMA (-4X)

2.55"

(64.77 mm)

1.96"

(49.78 mm)

1.90"

(48.28 mm)

4.30"

(109.22 mm)

3.80"

(96.56 mm)

6.96"

(176.66 mm)

2.21"

(56.07 mm)

2.12"

(53.72 mm)

ø

: 0.75"

(19.05 mm)

ø

: 1.08"

(27.50 mm)

0.98"

(24.89 mm)

3.11"

(78.99 mm)

1.56"

(39.50 mm)

3.70"

(93.98 mm)

7.94"

(201.60 mm)

Phone:

 1-888-967-5224

Website:

 workaci.com

Summary of Contents for DUCT HUMIDITY SERIES

Page 1: ...ns can cause sensing errors An example is downstream from a heating or cooling coil Duct probe should be placed 3 to 4 duct segments down from any bend or obstructions and away from 90 bends Mount the sensor on the top or sides of duct work mountingonthebottomrisksdamageduetomoisture MOUNTING INSTRUCTIONS The Euro enclosure EH requires a 0 875 22 23 mm hole in the duct and the Nema 4X enclosure 4X...

Page 2: ...ransorbordiode connectstothepositiveside of the power supply Without these snubbers coils produce very large voltage spikes when de energizing that can cause malfunction or destruction of electronic circuits RELATIVE HUMIDITY WIRING INSTRUCTIONS Open the cover of the enclosure ACI recommends 16 to 26 AWG twisted pair wires or shielded cable for all transmitters Twisted pairmaybeusedfor2 wirecurren...

Page 3: ...TROLLER ANALOG INPUT WIRING FROM CONTROLLER ANALOG INPUT FIGURE 6 TEMPERATURE WIRING 3 WIRE RTD WIRING 2 WIRE THERMISTOR or RTD WIRING FIGURE 5 OUTPUT SIGNALS OPTIONAL TEMP SENSOR CONNECT TO THE 2 or 3 22 AWG FLYING LEADS OPTIONAL TEMP SENSOR 4 20mA SUPPLY GROUND SIGNAL COMMON DC SUPPLY VOLTAGE 4 20 mA OUTPUT TB1 COM VIN VOUT OPTIONAL TEMP SENSOR VOLTAGE OUTPUT SIGNAL 3 WIRE CURRENT OUTPUT SIGNAL ...

Page 4: ... 4 are ON When all calibration is completed remember to place the switches back into the positions that correspond to the output needed as shown in FIGURE 7 HUMIDITY REVERSE ACTING OUTPUT The output is direct acting and can be changed to reverse acting mode The output range stays the same but the corresponding RH value is opposite Example Direct Acting DA 0 10 V output mode 0 V 0 RH and 10 V 100 R...

Page 5: ... The decrease goes into effect each time switch 6 is set to ON Reset RH Output This will reset the RH output back to the original calibration Switch 4 must be set to ON first After switch 4 is on toggle switches 5 and 6 ON then OFF After 5 and 6 are OFF slide switch 4 OFF When all calibration is completed remember to place the switches back into the positions that correspond to the output needed a...

Page 6: ... C 0 36 F A 1K 1 KΩ nominal 60 C 140 F 0 27 C 0 49 F 21 1 C 70 F 0 17 C 0 34 F 54 4 C 130 F 0 56 C 1 00 F SENSOR SPECIFIC RH Supply Voltage Reverse Polarity Protected RH Supply Current VA RH Output Load Resistance RH Output Signal RH Accuracy 77 F 25 C RH Measurement Range Operating RH Range Operating Temperature Range Storage Temperature Range RH Stability Repeatability Sensitivity RH Response Ti...

Page 7: ...dings SOLUTION S Checkthatyouhavethecorrectsupplyvoltageatthepowerterminalblocks Check that wiring configurations and all DIP switch settings are as in FIGURE 5 and 7 Verify that the terminal screws are all connected tightly and that all of the wires are firmly in place Verify that all of the wires are terminated properly Make sure that there is no condensation on the board Check that the input po...

Reviews:

Related manuals for DUCT HUMIDITY SERIES