ENGINEERING SPECIFICATION:

  ZURN Z1300 Encased Ecolotrol “anti-siphon” automatic 

draining wall hydrant for flush installation. Complete with non-freeze type integral 

backflow preventer, bronze casing, all bronze interior parts, non-turning operating rod 

with free-floating compression closure valve, replaceable bronze seat and seat washer, 

and combination 3/4” [19 mm] female or 1” [25 mm] male straight IP inlet. Nickel 

bronze box and hinged cover with operating key lock and “WATER” cast on cover.

Z1300 ECOLOTROL WALL HYDRANT – 

Encased, Non-Freeze, Anti-Siphon, Automatic Draining

SUFFIXES

–CL

 

Cylinder Lock

–PB

 

Polished Bronze Face

–RA2 

12” [305 mm] Replacement Rod Assembly with Repair Kit (-RK)

–RA4 

24” [610 mm] Replacement Rod Assembly with Repair Kit (-RK)

–RK 

Hydrant Parts Repair Kit

–SB

 

Statuary Bronze Face

 

(Specify light, medium, or dark finish.)

–SS

 

Stainless Steel Box and Cover

–WC

  Wall Clamp

–34FS 

3/4” [19 mm] Solder Female Inlet Adapter

–34UN 

3/4” [19 mm] IP 90° Inlet Elbow with Union Nut

Z1300 Ecolotrol Wall Hydrant

The Z1300 Ecolotrol is an encased, automatic draining, non-freeze, anti-

siphon wall hydrant designed for commercial applications such as office 

buildings, institutions, hospitals, malls and retail outlets, and schools.

Hydrant Features

• 

 

Certification 

– IAPMO

®

 and City of L.A. listed. 

Approved under ASSE standard 1019-A.

• 

 

Integral Anti-Siphon Vacuum Breaker/Backflow Preventer –

 Unique 

design utilizes an internal Equa-Balance

®

 seal to prevent contam ina-

tion of the potable water supply through back siphonage. The use of an 

additional hose-connection vacuum breaker with ASSE 1011 approval 

is not necessary.

•  

Valve Seat –

 Removable bronze valve seat with circular seating surface.

•  

Valve –

 One-piece assembly, replaceable, free-floating compression 

closure valve plunger operates the water flow and drainage with a maxi-

mum of two and one-half (2-1/2) turns. No adjustments are necessary.

•  

Casing –

 Threaded brass pipe nipple.

•  

Operating Screw –

 Chrome-plated brass.

• 

 Operating Rod –

 3/8” [10 mm] solid brass.

• 

 Faceplate  –

 Constructed of type 304 stainless steel with brush finish.

• 

 Box and Cover –

 Cast nickel bronze box and hinged cover with “WATER” 

stamping.

• 

 Drainage  –

 Through circular drain ports of the nozzle.

•  

Operating Pressures – 

Minimum running pressure 8 psi. Maximum static 

pressure 125 psi.

• 

 Water Temperature Range –

 Minimum 33°F. Maximum 130°F.

®

OPTIONS

Inlet Descriptions

  Wall Thickness

  6”  8”  10” 12” 14” 16” 18” 20” 22” 24” 

 

 

Inches [mm]

 

[152] [203] [254] [305] [356] [406] [457] [508] [559] [610]

  Overall Length*

 8

3

4

” 10

3

4

” 12

3

4

” 14

3

4

” 16

3

4

” 18

3

4

” 20

3

4

” 22

3

4

” 24

3

4

” 26

3

4

” 

 

Inches [mm]

 

[222] [273] [324] [375] [425] [476] [527] [578] [629] [679]

  Approx. Weight

 9  9  12 12 12 15 15 18 18 18 

 

Lbs. [Kg]

 

[4] [4] [5] [5] [5] [7] [7] [8] [8] [8]

*3/4” [19 mm] female and 1” [25 mm] male IPS connections.

Standard

-34FS

-34UN

Summary of Contents for Z1300 Ecolotrol

Page 1: ... malls and retail outlets and schools Hydrant Features Certification IAPMO and City of L A listed Approved under ASSE standard 1019 A Integral Anti Siphon Vacuum Breaker Backflow Preventer Unique design utilizes an internal Equa Balance seal to prevent contam ina tion of the potable water supply through back siphonage The use of an additional hose connection vacuum breaker with ASSE 1011 approval ...

Page 2: ...853 042 13 Key 1 59546 001 16 Removable Seat 1 25262 001 17 Wall Clamp Optional 1 50268 001 18 Wall Clamp Screw Optional 1 26050 004 19A 3 4 Nozzle 1 50799 005 19B 1 Nozzle 1 50799 006 20 Faceplate 1 56115 005 21 Disc O Ring 1 23750 204 22 Disc 1 50819 001 23 Equa Balance Seal 1 50785 001 24 Faceplate Screw 5 22698 047 25 Ball O Ring 1 23750 232 26 Ball 1 51458 001 27 Hydrant Body 1 56068 002 28 H...

Page 3: ...zzle when Equa Balance seal is damaged Follow steps 1 3 and 9 10 of the Service Guide hydrant is on Hydrant will not self drain when it is shut off Screw nozzle is closed Open screw nozzle so hose will drain some hose and nozzle are attached relieving pressure Gun nozzle is closed Squeeze gun nozzle trigger so hose will drain some relieving pressure Water does not shut off completely when Debris b...

Page 4: ...g coupling 7 by turning clockwise and slip the old O Ring 6 off and replace with new O Ring 6 Reinstall operating screw 5 into operating coupling 7 by turning counter clockwise Note Lubricate the operating screw 5 threads and the O Ring 6 with Lubriplate FGL 2 if needed If the operating screw assembly was not the reason for service skip to step 7 Step 6 Checking Operating Screw Assembly Remove the...