HOW TO MAKE REPAIRS:

(Shut off service before starting disassembly)

Model BR4EC

Pressure Reducing Valve with Integral By-pass

and Pressure Relief Valve

(1/2", 3/4", 1 1/4", 1 1/2" & 2")

q

 Installation 

q

 Maintenance Instructions

      company

REPAIR KIT INSTRUCTIONS

BODY

UNION NUT

UNION TAILPIECE

*LOWER O-RING

UPPER O-RING*

*CARTRIDGE

*SPRING

*FRICTION RING

BELL HOUSING

ADJUSTMENT BOLT

SPRING*
DISC

INNER LOCKNUT

OUTER LOCKNUT

*UNION GASKET

RETAINING*
BOLT

FRICTION RING DETAIL

P1520

*INDICATES PARTS SUPPLIED IN REPAIR KITS

SEALED CAGE 
WASHER

1.

Note distance that adjustment bolt protrudes from bell housing.

Loosen locknut on adjustment bolt, then turn adjustment bolt out

of bell housing until free of spring tension.

2.

Unscrew bell housing counterclockwise and remove spring, spring

disc and friction ring.

3.

Remove cartridge from regulator by gripping retaining bolt with

pliers  and  pulling  outwards  away  from  body.

TO REASSEMBLE:

INSTALLATION INSTRUCTIONS

CAUTION: Anytime a reducing valve is adjusted, a pressure

gauge must be used downstream to verify correct pressure

setting. Do not bottom out adjustment bolt on bell housing.

Valve may be installed in any position.

1.

Open shut-off valve slowly and flush body and line of any debris.

2.

Replace old cartridge assembly with new cartridge assembly. Prior

to installation, apply a small amount of lubricant to cartridge o-rings.

The cartridge is pushed into bore on body and seals against o-rings.

3.

Install new spring, spring disc and friction ring. Make sure friction

ring is installed with raised edge facing up (friction ring detail).

4.

Replace bell housing by tightening clockwise (Be sure not to over-

tighten.). Turn adjustment bolt clockwise until adjustment bolt touches

spring disc.

5.

Turn adjustment bolt into bell housing to old setting.

6.

Enter dwelling and turn on several faucets.

7.

Turn on water service. Let water run for several seconds then turn

off faucets in dwelling.

8.

Adjust regulator to desired pressure by turning adjustment bolt clock-

wise (into bell housing) to raise pressure or counterclockwise (out

of bell housing) to lower pressure. 

It is recommended a pressure

gauge be installed downstream of the regulator to ensure pres-

sure is reduced below 75 psi.

 NOTE: When reducing pressure,

open a down stream faucet to relieve pressure.

9.

Tighten locknut when desired pressure is achieved.

Install valve in line with arrow on valve body pointing in direction

of flow. Before installing reducing valve, flush out line to remove

loose dirt and scale which might damage seal ring and seat. All

valves will be furnished with stock settings to reduce to 50 psi.

To readjust reduced pressure, loosen outer locknut and turn ad-

justment bolt clockwise(into bell housing) to raise reduced pres-

sure, or counterclockwise(out of bell housing) to lower reduced

pressure.

WARNING: Attach drain line to relief valve and plumb to a

safe location. The drain line should terminate at a location

where discharge of water will not cause damage or general

discomfort.

DIRECTION OF FLOW

MODEL BR4EC

DRAIN

P1520 PRESSURE RELIEF VALVE

TYPICAL INSTALLATION

WARRANTY:

 WILKINS Valves are guaranteed against defects of material or workmanship when used for the services recom-

mended. If in any recommended service, a defect develops due to material or workmanship, and the device is returned, freight

prepaid, to WILKINS within 12 months from date of purchase, it will be repaired or replaced free of charge. WILKINS' liability shall

be limited to our agreement to repair or replace the valve only.

NOTICE: Annual inspection and maintenance is required of

all plumbing system components. To ensure proper perfor-

mance and maximum life, this product must be subject to

regular inspection, testing and cleaning.

Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer or birth defects or

other reproductive harm.

Regulators in series: Where the desired pressure reduction

is more than a 4 to 1 ratio (i.e. 200psi to 50psi), multiple regu-

lators in series should be installed.

SEALED CAGE WARNING: Loosen lock washer at adjustment

bolt slowly. Look for any trapped water pressure under the

sealed cage washer. Relieve pressure before removing bell.