TROUBLE SHOOTING GUIDE

Problem
No lights are visible in
the sensor eye.
Valve does not flush.

Light flashes randomly in
sensor eye and valve
does not flush
Lights follow normal
sequence, valve does
not flush.

Valve flushes but does
not shut off.

Leaks

Possible Cause
Electronics fault.

Valve could be sensing a
close by surface or reflections
from some opposite surface.

Lens could be dirty or dam-
aged.
Electrical leads disconnected
or broken wire.
Electrical corrosion has
caused loss of contact.

Sensor not detecting user.

Electronics fault

Water not turned on.

Plugged filter.

Stop valve closed.
Wiring fault.

Solenoid malfunction.

Diaphragm damage or plugged
diaphragm orifice.
Solenoid malfunction

Incorrectly installed.

Damaged O-ring on inlet tube.

Diagnosis
Run through reset procedure
below.
Hold a flat object at an acute
angle to the valve and see if it
flushes ( three ring binder
works well)
Visual inspection of batteries
and battery case.
Check plug insertion and wire
continuity.
Visual inspection

Hold hand at different ranges
in front of valve to see if it can
be detected.
Run through reset procedure
below

Close stop, disconnect valve,
crack stop to check for water.
Close stop, remove and
inspect filter.
Check stop screw.
Check solenoid leads and and
insertion of solenoid plug.

Visual inspection.

Check for leak location.

Check for cuts.

Solution

Reduce sensing range
Eliminate reflective
object.

Replace if obstructed or
damaged
Reinsert plug or repair
leads
Replace

Reset sensor range
(Appendix A)

Find source valve and
turn on.
Clean and reinstall filter

Open stop valve
Reinsert plug or repair
wiring
Clean P6900-SRK
components.  See parts
list
Replace diaphragm

Clean P6900-SRK
components.  See parts
list
Remove and reinstall.
Pay close attention to
alignment of inlet tube
and outlet boss with
mating pieces.
Replace O-ring

Electronics Reset Procedure: Remove valve cover.  Disconnect solenoid wires ((J) Figure 9).  Disconnect one wire nut
connection to disrupt power to the valve.  Place magic magnet on top cover as if changing activation distance (See Appendix A).
Reconnect solenoid wire connector.  Place valve cover back on valve housing, carefully tuck wires into housing.  Secure cover
with two screws provided.  Reconnect power and check for sensor function.

Soft RESET for Electronics:
1. Remove the battery cover from the battery box.
2. Wait for two minutes.
3. Reassemble.
4. Hold target in front of sensor eye (light should blink once followed by a double blink over a 5 second period).
5. Solenoid will activate when target leaves view.

Summary of Contents for AquaSense EV ZEG Series

Page 1: ...be responsible for any labor charges or any loss injury or damages whatsoever including incidental or consequential damages The sole and exclusive remedy shall be limited to the replacement of the defective goods Before installation and use the purchasershalldeterminethesuitabilityoftheproductforhisintendeduseandthepurchaserassumesallriskandliability whateverinconnectiontherewith Where permitted b...

Page 2: ...uld be used on male NPT threads only Figure 2 A Before the supply water is turned on be sure all stop valves are closed off tight The stop valves can be opened and closed by using the adjusting screw S located at the center of the stop valve cap T Stop valve adjustments can only be made by using the adjusting screw S It is not necessary to remove the stop valve cap T when making adjustments If for...

Page 3: ...s installed open each stop fully for a brief time and catch the water in a two gallon or larger bucket Figure 3 For multiple installations start with the stop valve closest to the water supply and work toward the most remote valve B Due to the small passages and orifices it is not possible to flush the piping through the low volume valve C Once the lines are flushed the valve can be installed A 4 ...

Page 4: ...ll activate This six second sensing cycle will prevent the valve from flushing needlessly when someone walks by If special circumstances require adjustment of the sensing distance see Appendix A Changing Activation Distance L D H G 9 Wiring installation see fig 8 A Remove the two cover retaining screw and lift the flushometer top cover B Run fish tape through the valve cover tube and wall to the p...

Page 5: ...as follows 1 Place the Zurn Magic Magnet N on the left hand side of the flat top surface of the valve and move around until the LED comes on 2 The LED will blink 10 times to indicate magnet is in the proper position Hold magnet in place until 10 flashing lights occur and the red light turns solid The solid red light indi cates the electronics are in calibration mode 3 Remove the magnet and stand i...

Page 6: ...or water Close stop remove and inspect filter Check stop screw Check solenoid leads and and insertion of solenoid plug Visual inspection Check for leak location Check for cuts Solution Reduce sensing range Eliminate reflective object Replace if obstructed or damaged Reinsert plug or repair leads Replace Reset sensor range AppendixA Find source valve and turn on Clean and reinstall filter Open stop...

Page 7: ...ng Screw 31 Guide Holder 32 Piston Guide 33 Guide O Ring 34 Piston 35 Piston Seal 36 Stop Body 37 Sweat Solder Adapter 38 Supply Cover Tube 39 Setscrew for Cast Wall Escutcheon 40 Cast Wall Escutcheon 41 Hex Wrench 42 Cover O ring Control Stop Repair Kit and Parts Product No Control Stop Repair Kit for 3 4 PEG6003 D SD Includes Items 30 35 3 4 Control Stop Replacement Includes PEG6003 C SD Items 2...

Reviews: