Smart Backflow Wireless Monitor

Note: This product to be installed in an indoor, dry or damp location only.

Single Water Shutdown

A single ZW206 Solenoid Control Valve 

to shutdown the water supply to the 

backflow preventer and system is our 

standard installation. This will prevent the 

discharge of water through a fouled first 

check.

Double Water Shutdown

Two ZW206 Solenoid Control Valves to 

isolate the Reduced Pressure Backflow 

Assembly on both the inlet and outlet. A 

second ZW206C installed downstream 

will prevent water discharge due to a 

fouled second check

Typical Installation

PLACING THE DEVICE IN SERVICE

1. Plug unit into a 120 VAC grounded outlet and wait 60 seconds for the electronics to 

initialize before moving to step 2. GREEN LED on enclosure will turn on.
2. Toggle the switch position to the ZERO position and hold for three seconds, this will 

set the closed position of the backflow relief valve position monitor.

ALTERNATE MOUNTING INSTRUCTIONS

1.  Remove electronics enclosure from Unistrut or brackets on left ACV.
2.  Locate mount hardware shipped with the electronics enclosure (taped to the side 

of the enclosure)

3.  Install the wall mount brackets onto the electronics enclosure using the self-tap-

ping pan-head screws provided (see picture on the right)

4. 

Position the enclosure on a wall 3’ from the floor to the bottom of the enclosure 

ina secure area. The position of the enclosure must be within 4’ of the backflow 

preventer valve and sensors

5.  Mount the enclosure to the wall with appropriate fasteners to meet the mounting 

application.

6.  Refer to the “Placing the device in service” above

Backflow Preventer with Wireless Monitoring – Model List *Sizes (2 1/2" - 10") 

375ASTW1, 375AW1, 375W1

A

G

B

E

F

WILKINS

C515

WILKINS

C515

XL

VENT

EXTERNAL CABLES FOR THE 

WALL MOUNT CONFIGURATION 

ARE 6 FEET LONG

Model 375ASTW1 with NRS option

1

ZURN WILKINS

1747 Commerce Way, Paso Robles, CA 93446 Phone:

855-663-9876

 Fax:805-238-5766

ISW1  (REV. B  7/20)

www.zurn.com

On/Off Zero/-/Test

ZERO

SWITCH

POWER

XL

VENT

12"  MIN.

30"  MAX.

12"  MIN.
30"  MAX.

XL

VENT

12"  MIN.
30"  MAX.

XL

VENT

Installation

 

Instructions

CAUTION: 

Do not power unit until backflow preventer valve has been installed, pressurized and stable.

1. Install backflow preventer valve per Zurn Wlkins backflow preventer valve installation guide.

STANDARD MOUNTING

Electronics enclosure and electronics/sensors are pre-installed on the standard backflow preventer valve.

On model FCIS, once the ZW206 and backflow preventer have been installed, plug the pressure sensor cable from the enclosure 

into the pressure transducer on the backflow preventer cover.  Route the black position sensor housing to the relief valve cover 

under the backflow preventer and attach with the two screws and 5/32" allen wrench.

   