NetNumen™ U31 R06 Hardware Installation Guide
Figure 5-36 Connecting Neighboring Cabinets
1.
Junction kit
2.
M4×12 combination
screw
13. Verify that the horizontal and vertical deviations of cabinets in a row are in an
acceptable range.
The deviation should be less than 3 mm. If it does not meet the requirement, adjust
cabinets.
14. (Optional) Install a shockproof assembly on the cabinet if necessary.
l
For the shockproof assembly installation when all the installation holes are under
the cable ladder in the equipment room, see
5-28