DESCRIPTION

SPECIFICATIONS

Component

Description

Motor

Rear access - Nema 56J face

Bearings

Ball-ball, permanently lubricated

Impellers

GFN2

Diffuser

GTX 820

Pump shaft

316 Stainless steel

Pump shaft coupling

316 Stainless steel

Pump housing

Powder-coated cast iron

O-Rings

Viton

Seal composition

Carbon-ceramic, stainless steel spring and Viton

Chart C: Material Construction

Chart B: 115V, 60 Hz Motor Data & Minimum Wire Size (Gauge)

†Thermal overload protector - automatic reset.

Motor HP

Service Factor

Motor Amps

Phase†

Distance In Feet From Motor To Service Panel

Breaker Size 

(Amps)

0-50

50-100

100-150

150-200

200-300

Wire Size

1/2

8.6

1

14

14

14

12

12

15

3/4

13.0

1

12

12

12

12

10

20

Pressure booster pumps increase water pressure from city mains 

or private water systems. This system is powered by a 1/2 or 

3/4 HP single phase, capacitor start motor with thermal overload 
protection. The bladder tank is pressurized with air to 48 PSI.

NOTE:

  Use pump with clear water only.

Figure 1

Gallons per Minute

20

18

15

14

12

10

8

6

4

3

Max.

Press.

PSI

Suction

Pipe Tap 

NPT

Disch.

Pipe Tap 

NPT

Cast Iron Pump w/

S.S. Tank

Cast Iron Pump w/

Painted Tank

HP

Discharge PSI

350-0006

350-0005

1/2

29

31

35

46

57

61

66

68

77

3/4"

3/4"

351-0006

351-0005

3/4

36

42

47

49

55

59

61

64

67

68

73

1"

1"

Chart A:  Performance Specifications based on 20 PSI flooded suction  

To keep pump and seal lubricated, a minimum flow of 1.5 GPM must always be maintained through the pump.

Motor voltage: Single phase 1/2 - 3/4 HP - 115/230V, 60 Hz.

IL0530

Gallons per minute

20

18

15

14

12

10

8

6

4

3

Max 

Press.

PSI

Suction 

Pipe Tap

NPT

Disch.

Pipe Tap

NPT

Cast Iron Pump w/

S.S. Tank

HP

Discharge PSI

350-0006

1/2

29

31

35

46

57

61

66

68

77

3/4”

3/4”

351-0006

3/4

36

42

47

49

55

59

61

64

67

68

73

1”

1”

To keep pump and seal lubricated, a minimum flow of 1.4 GPM must always be maintained through the pump.

Motor voltage: Single Phase 1/2 - 3/4 HP - 115/230V, 60 Hz

Summary of Contents for 350

Page 1: ...u o d r a z a H Release all pressure on system before working on any component 16 According to the state of California Prop 65 this product contains chemicals known to the state of California to caus...

Page 2: ...hts which vary from state to state LIMITED WARRANTY Symptom Possible Cause s Corrective Action Pump won t start or run at full speed 1 Blown fuse or open circuit breaker 1 Replace fuse or close circui...

Page 3: ...3 4 HP single phase capacitor start motor with thermal overload protection The bladder tank is pressurized with air to 48 PSI NOTE Use pump with clear water only Figure 1 Gallons per Minute 20 18 15 1...

Page 4: ...t finger or any object into pump or motor openings LOCATION 1 Locate pump as close to the fluid source as possible keeping the inlet pipe short as possible 2 Place unit where the pump and piping are p...

Page 5: ...he two black and orange wires on the flow sensor 5 Specific Wiring Procedure Refer to Figure 5 and Minimum Wire Size Chart B a The 1 2 and 3 4 HP single phase pumps are factory connected for 115V at t...

Page 6: ...crewdriver slot at the impeller eye 4 The rotary seal will come loose at this time Use a screwdriver or similar instrument to pry the ceramic seal and rubber gasket from the recess of the mounting bra...

Page 7: ...ghts reserved 7 MAINTENANCE continued 3 4 Pipe Press Carefully IL0169 Cardboard Washer Protects Seal Face Seal Seal Cavity Figure 10 If necessary press with cardboard and pipe IL0173 Figure 8 Remove m...

Page 8: ...3 8 x 3 4 1 4 021642 021642 4 5 6 7 8 9 Ring Square Cut Seal Rotary w Spring Impeller Diffuser Rubber Diffuser Pump Body 1 1 1 1 1 1 132583 131100 139348 132424 132428 021640 132583 131100 139349 132...