2

Install rigid 1-1/4 in. discharge pipe (not included) according to 

local, regional, and state codes. Attach the switch securely to 

the discharge pipe so that incoming water does not interfere 

with switch movement. The best place for the ‘off’ point is 

above the motor housing and 180° from the inlet. Never put 

the ‘off’ point below the pump discharge.

3

Drill a 3/16 in. hole in the discharge pipe above the pump 

discharge to prevent air lock. Water stream will be visible from 

this hole when the pump is running. The hole must be cleaned 

periodically. 

4

Install a union, check valve, gate or ball valve as required by 

local, regional or state codes. Connect remaining discharge 

pipe into main waste line.

5

Secure power cord to discharge pipe and plug into a GFCI-

protected outlet. Fill the basin with water to check operation.
Add water to basin to test operation. 

6

Seal basin with lid and install vent pipe per codes.

SW1221 A

Zoeller

®

 is a registered trademark of Zoeller Co.  

All Rights Reserved.

QUICK REFERENCE GUIDE.  

SEE INSTRUCTION MANUAL FOR 

COMPLETE DETAILS.

GRINDER PUMP 

MODEL #2701-0005

1

Place pump securely in 

minimum 18 in. x 30 in. 

basin on a solid surface 

such as a cement block.

Discharge

pipe

Switch

Incoming

water

3/16 in.

hole

Discharge

pipe

Union

Check

valve

Gate or 

ball valve

Main waste 

line

GFCI

outlet

Vent 

pipe

Basin

cover

FIRE/EXPLOSION HAZARD.

 

Do not pump flammable or explosive fluids such as gasoline, fuel oil, kerosene, etc. Do not use in a flammable 

and/or explosive atmosphere. Failure to follow these warnings could result in death or serious injury and/or 

property damage.