MODEL 10-2614 APAK

®

 ALARM SYSTEMS WITH AUXILLIARY CONTACTS 

WIRING INSTRUCTIONS

 

ELECTRICAL SHOCK HAZARD - Disconnect all 

power sources before servicing. Failure to do so could result 

in serious injury or death.

1)  Remove the three screws from the back of the enclosure as shown in 

Fig. A.

2)  Remove the back of the enclosure. Note the position of the power 

cord in the enclosure. The cord will need to be located in the same 

manner when the enclosure back is replaced.

3)  Determine the location where the auxiliary contact wires will 

enter the housing. See Fig. B for recommended location. Before 

drilling the hole, loosen the circuit board mounting screw and 

remove the circuit board. See Fig. C.

4)  At the selected location, drill a hole in the enclosure suitable for 

the strain relief that will be used (strain relief not included).

5)  Install strain relief and reinstall the circuit board. Connect wires 

to the terminal block shown in Fig. C.

6)  Markings on the circuit board show positions for Common (C), 

Normally Open (NO), and Normally Closed (NC).

7)  Position the power cord into place as it was prior to removing the 

enclosure back as shown in Fig. C.

8)  Reinstall the enclosure back and three screws.

 

CAUTION

 Do not over torque screws. Screw bosses may 

become stripped.

9)  Note that while testing the installed product, the auxiliary alarm 

wired to the auxiliary contacts should activate in an alarm 

condition. The auxiliary alarm should also remain in alarm condition 
when the silence button is pushed.

Auxiliary Contacts Specifications

 

 

 

Voltage: 

120 VAC

 

  

Current: 

5 amps max. N/O

 

  

   

3 amps max. N/C

NOTE:

 This unit includes auxiliary contact option. Due to increased 

power consumption, if an alarm condition occurs while on battery 

backup power, this option will reduce the life of the battery.

SK2775

Figure A

Figure B

Figure C

   All electrical systems must be installed by a qualified licensed electrician according to the  National 

Electrical Code and all other applicable codes.