Model TAAB
Notice to Installer: Instructions must remain with installation.
Product information presented
here reflects conditions at time
of publication. Consult factory
regarding discrepancies or
inconsistencies.
MAIL TO
: P.O. BOX 16347 • Louisville, KY 40256-0347
SHIP TO
: 3649 Cane Run Road • Louisville, KY 40211-1961
TEL
: (502) 778-2731 • 1 (800) 928-PUMP •
FAX
: (502) 774-3624
Visit our website:
zoellerpumps.com
MODEL 10-2614 APAK
®
ALARM SYSTEMS WITH AUXILLIARY CONTACTS
WIRING INSTRUCTIONS
ELECTRICAL SHOCK HAZARD - Disconnect all
power sources before servicing. Failure to do so could result
in serious injury or death.
1) Remove the three screws from the back of the enclosure as shown in
Fig. A.
2) Remove the back of the enclosure. Note the position of the power
cord in the enclosure. The cord will need to be located in the same
manner when the enclosure back is replaced.
3) Determine the location where the auxiliary contact wires will
enter the housing. See Fig. B for recommended location. Before
drilling the hole, loosen the circuit board mounting screw and
remove the circuit board. See Fig. C.
4) At the selected location, drill a hole in the enclosure suitable for
the strain relief that will be used (strain relief not included).
5) Install strain relief and reinstall the circuit board. Connect wires
to the terminal block shown in Fig. C.
6) Markings on the circuit board show positions for Common (C),
Normally Open (NO), and Normally Closed (NC).
7) Position the power cord into place as it was prior to removing the
enclosure back as shown in Fig. C.
8) Reinstall the enclosure back and three screws.
CAUTION
Do not over torque screws. Screw bosses may
become stripped.
9) Note that while testing the installed product, the auxiliary alarm
wired to the auxiliary contacts should activate in an alarm
condition. The auxiliary alarm should also remain in alarm condition
when the silence button is pushed.
Auxiliary Contacts Specifications
Voltage:
120 VAC
Current:
5 amps max. N/O
3 amps max. N/C
NOTE:
This unit includes auxiliary contact option. Due to increased
power consumption, if an alarm condition occurs while on battery
backup power, this option will reduce the life of the battery.
SK2775
Figure A
Figure B
Figure C
All electrical systems must be installed by a qualified licensed electrician according to the National
Electrical Code and all other applicable codes.