VPLC710 Motion Controller Hardware Manual V1.0
1.6.
Interface Definition
1.6.1.
Standard Interface
The USB3.0 interface, VGA interface, HDMI interface, LAN interface, audio interface,
and EtherCAT interface are all standard interfaces, which can be connected and used
through standard wiring cables.
1.6.2.
RS485/RS232
VPLC710 series support RS485 protocol local IO communication and RS232 protocol
local debug.
Before use, it needs to configure the number of "com num" and related parameters
on the "Config Window" of the MotionRT software.
By default, the MODBUS_RTU standard protocol is adopted, and at the same time, it
supports configuration as no-protocol mode, and adopts custom communication.
Both support configuration as master or slave.
PIN
Name
Description
2
RS232-RXD
RS232, receive data
3
RS232-TXD
RS232, send data
4
RS485A
RS485 + communication
5
GND
Power ground
7
RS485B
RS485 - communication
9
DC5V
5V power output
1, 6, 8
NC
Spare