14
MANUAL SHUT-OFF VALVE
• This valve is not shipped with the appliance and must be provided by the installer.
• The valve must be installed in the gas service line between the gas hook-up on the wall
and the appliance inlet, in a position where it can be reached quickly in the event of
an emergency.
•
In Massachusetts:
A T-handle type manual gas shut-off valve must be installed in the gas
supply line to this appliance.
FLEXIBLE CONNECTIONS
• In case of installation with flexible couplings and/or quick-disconnect fittings, the installer
must use a heavy duty, AGA design-certified commercial flexible connector of at least
1/2" (13 mm) NPT with a suitable strain relief in compliance with ANSI Z21.41 and
Z21.69 standards.
•
In Massachusetts:
The unit must be installed with a 36" (914 mm) flexible gas connector.
•
In Canada:
Use CAN 1-6, 10-88 metal connectors for gas appliances and CAN 1-6.9,
M79 quick disconnect devices for use with gas fuel.
PRESSURE TEST POINT STOPPER VALVE
When attaching the regulator, please use the blue gasket located within the liquid propane gas
orifice box. This will need to be placed at the top inside of the threads of the regulator valve,
where it connects to the gas rail manifold. If this is not installed properly, gas leaks may occur.
Gasket
Gasket
Gas pipe
Pressure test-point stopper
Gas connection adaptor 1/2" NPT with
pressure test point 1/8" NPT (to be fixed
toward external side of the appliance)
Scan to follow along
with a video.
INSTALLATION
Gas Connection